HomeMy WebLinkAboutMiscCHEATHAM AND ASSOCIATES June 3, 1999 'D City of College Station P.O. Box 960 1 College Station, TX 77842 Attn: Development Services Veronica J.B. Morgan, P.E. Re: 1019-001, College Station Independent School District Drainage Study Reflecting Impact of Installation of Temporary Buildings Veronica, C~C~D~JG AIN igss D. At the request of the College Station Independent School District, we have reviewed the drainage studies prepared for the City of College Station to check any impact created by the installation of temporary buildings, as reflected on the site plans included, to the water surface elevations in the tributaries adjacent and as to any upstream or downstream impact. The sites are: Exhibit A College Station Jr. High Exhibit B College Hills Elementary Exhibit C Pebble Creek Elementary Exhibit D A & M Consolidated High School Since the maximum run off from the temporary buildings, using two as a criteria, is less than 1 cfs, we can state that no rise in water surface will be noticeable and probably beyond computation. All of the drainage studies prepared over the years, for the referenced school sites which the City has copies of, are for all design frequencies and have 1 foot of freeboard available. Each location in question discharges into a major tributary or a chain of detention facilities, therefore it is our opinion that no downstream or upstream impact or noticeable rise in water surface elevation will occur. Cheatham and Associates Eddie Cheatham, P.E. F:\WORD\cou.EC,E\001utr.Morgan.drainaEE-r4O,INEERS • PLANNERS • SURVEYORS A Subsidiary Firm of Southwest Planning and Design, Inc. 1601 E. Lamar Blvd. • Suite 200 • Arlington, Texas 76011 817/548-0696 • Metro 265-8836 • Fax 817/265-8532 All buildings will have covered porches with ADA quality access ramps including an accessible sidewalk access to each building. Handrails will be provided in conformance with ADA requirements. The fire alarms will be equipped with both audio and visual alarms. A copy of Cheatham & Associates' letter and site plans for each school is forwarded herewith. Their evaluation of the effect of the relocation of these buildings as shown appears to have minimal effect on respective rising water surface elevations. The location of the building at College Hills encroaches upon the utility easement behind the multi-purpose building. We feel this encroachment is minor and provides ample space for maintenance of the utility lines. Should it become necessary to move this building in the future for maintenance of this line, the school district will cooperate fully. All of these buildings are temporary. At this time we anticipate the junior high school building to be in use until the opening of A & M Consolidated Middle School in August 2000. The buildings at Pebble Creek Elementary and College Hills Elementary are for potential peak student enrollment between now and 2003 when we anticipate opening Forrest Ridge Elementary School, our next elementary school. The building located at the athletic office is anticipated to be a permanent facility and will be replaced in the future only when we fund a project to increase the field house facilities. Please call me if there are any questions. I can be available for a hearing should it be necessary. Thank you for your assistance in this issue. Yours truly, J. Construction Manage WJS/b Enclosure cc: D. Neal R. Thomas File UP G yy~G6 ST~'~2 T V d M a Fy ,5 0 O~'YT S C 1101 College Station Independent School District EXceQence In Education... t Investment In Th Future June 8, 1999 Letter No. 1931 Ms. Natalie Ruiz Development Coordinator City of College Station 1101 Texas Avenue College Station, Texas 77842 Subject: Temporary Classroom Buildings Relocation from A & M Consolidated High School Dear Ms. Ruiz: In 1997 we received City approval to locate five temporary double classroom buildings in our parking lot West of the high school building along Welsh Street. We will no longer need these building and plan to move these buildings to the following schools: College Hills Elementary School 1101 Williams College Station Junior High School 900 Rock Prairie Road Pebble Creek Elementary School 200 Parkview Athletic Office 2118 Welsh 1 - 24'x 64' Double Classroom Building 1 - 24'x 64' Double Classroom Building 2 - 24'x 64' Double Classroom Buildings 1 - 24'x 64' Double Classroom Building All of the above buildings are to be connected with electrical power, telephone, technology, video fire alarms, school communication and security where available. The building at the junior high school, 900 Rock Prairie Road, will require a change in City transformer voltage rating and the building at College Hills will connect directly to an existing City pad mount transformer for service. All other utilities and services mentioned will be extensions of existing services that are currently in service at each location and will not require additional utilities from the City, telephone company, cable vision, etc. There will be no need of water, sewer or gas services for any of these buildings. Construction Services 1812 Welsh Street College Station, TX 77840 409-694-5610 FAX 409-694-5612 JIM SCALES, Ph.D. Superintendent of Schools STAFF REVIEW COMMENTS No. 1 Project: CSISD Portable Buildings cage letter, regarding all sites, needs to be sealed. 2. For all sites, show floodway and floodplain. If there is none, then state that and reference the applicable FEMA map. If a building is to be within the floodplain, then show finished floor elevation. 3. For each site, state whether the building will be raised or at grade. If at grade, we will need grading information. 4. It appears that in some instances the building separation will be less than 15 feet. Coordinate with Building Official to determine the additional requirements for separation distances of < 15 feet. 5. The College Hills Elementary Site shows the portable building encroaching into a utility easement. We cannot allow that unless a license to encroach has been granted. Reviewed by: Jessica Jimmerson staff Review Comments pw i of 1 0022/88 STAFF REVIEW COMMENTS No. 2 Project: CSISD Portable Buildings 1. The addition of the portable buildings to the existing school sites is not considered a significant change and will not require new conditional use permits. 2. The site plans and information submitted were only reviewed in regards to the proposed changes. 3. The building department has been notified that the proposed building placements may have less than 15 feet of separation distance and will be looking for necessary fire compliance. 4. Pebble Creek Elementary and College Station Jr. High are approved at this time. 5. The Site Plan for the A&M Consolidated High School Athletics Facility requires an elevation certificate. The elevation certificate will be issued based upon the regulatory floodplain at the time of permitting. The Morrison Hydrology Study has not been submitted to FEMA at this time. Reviewed by: Jessica Jimmerson Date: 7/19/99 Staff Review Comments Page 1 of 1 We will engage a moving contractor to move this building to the new location. A local general contractor will be contracted to construct install underpinning, a covered porch, access ramp connected to existing sidewalks and provide the necessary handrails, etc. required for TAS and ADA accessible facilities. An electrical contractor will connect and energize electrical service to this building, install and extend services from existing fire alarms, telephones, school intercommunication system, technology wiring for computer and video education devices. Electrical service is proposed to be supplied from the metered bus between the Kindergarten and Cafeteria buildings. We have reviewed this with the City of College Station Public Utility Department. The above requirements have been reviewed with the City Building Official and Fire Department for their familiarization only. Their final approval will be secured along with the respective moving, building and occupancy permits. Please advise us of all fees that may be due, our participation in any hearings or meetings required and of any additional information you may require. We are available to assist you in any way that will expedite the issuance of the conditional use permit for this temporary classroom building. Yours truly, Constructio nager WJS/ceb Enclosure - City of College Station Memorandum dated June 23, 1999 (1 Copy) Cheatham Exhibit B letter dated July 2, 1999 (2 Copies) Cheatham Site Plan Exhibit B (2 copies) A & M Consolidated High School Temp. Building Layout (2 copies) cc: D. Neal File UP College Station Independent School District E.xceffence In Education... An Investment in 9 he future July 15, 1999 Letter No. 2084 Ms. Natalie Ruiz Development Coordinator City of College Station 1101 Texas Avenue College Station, Texas 77842 Subject: College Station Junior High School Conditional Use Permit for Temporary Classroom Building Dear Ms. Ruiz: In our letter No. 2024 requesting a Conditional Use Permit for the temporary classroom building proposed to be located at College Station Junior High School we promised you a corrected site plan deleting a 10 foot which was accidently left on the plan. We received the corrected site plan (2 copies attached) and found that the proposed separation of 16 feet between buildings was omitted. We have marked the drawing to indicate the 16" separation. We regret this omission and are requesting that Cheatham & Associates forward another set of drawings including this dimension. As soon as the corrected drawing arrives we will forward two copies to you. Any consideration toward issuing a Conditional Use Permit for this building based upon this letter and marked drawing will be appreciated. This building is needed for start of school. If we do not have it in place and ready for use our only recourse is to bus students to two classrooms which will be very disruptive. I enclosure: Cheatham Revised Site Plan Exhibit A (2 copies) WJS/ceb cc: David Neal File UP Construction Services 1812 Welsh Street College Station, TX 77840 409-694-5610 FAX 409-694-5612 JIM SCALES, Ph.D. Superintendent of Schools College Station Independent School District EXcellence In Education.....An Investment In The Future July 9, 1999 Ms. Natalie Ruiz Development Coordinator City of College Station 1101 Texas Avenue College Station, Texas 77842 Letter No. 2049 Subject: A & M Consolidated High School Athletic Facilities Conditional Use Permit for Temporary Building Dear Ms. Ruiz: In 1997 we received City approval to locate five temporary double classroom buildings in our parking lot West of the high school building along Welsh Street. We will no longer need these buildings and plan to move them to other locations within the District. College Station ISD requests a Condition Use Permit to relocate Building No. "E" from its present location at A & M Consolidated High School to a new location at A & M Consolidated High School Athletic Office, 2118 Welsh, College Station, Texas. The location of this building at A & M Consolidated High School Athletic Office is shown on the enclosed site plan titled Exhibit "D" prepared by Cheatham & Associates. Cheatham has modified and sealed their letter (2 copies) and has incorporated information on the site plan drawing (2 copies) requested in City of College Station Memorandum dated June 23, 1999 (copy attached). Also included are maps showing the existing and proposed conditions of Bee Creek Tributary B Flood Plain and Floodway as requested. The building is on a raised pier and beam foundation, wood framing, metal siding and roof, insulated suspended ceilings, prefinished wood paneling interior walls, carpeted floors, has a 150 A 120/240 volt primary electrical service panel, flourescent lighting, grounded duplex electrical outlets, electrical HVAC thru wall units for each of two rooms. This building was constructed at the A & M Consolidated High School site and was fully inspected by the City of College Station Building Inspection Department. Records of the City inspection of the construction of this building should be on file. Construction Services 1812 Welsh Street College Station, TX 77840 409-694-5610 FAX 409-694-5612 JIM SCALES, Ph.D. Superintendent of Schools College Station Independent School District E,xce!lence In Education... .An Investment In'ZTie Future July 9, 1999 Ms. Natalie Ruiz Development Coordinator City of College Station 1101 Texas Avenue College Station, Texas 77842 Letter No. 2049 Subject: Pebble Creek Elementary School Conditional Use Permit for Temporary Buildings Dear Ms. Ruiz: In 1997 we received City approval to locate five temporary double classroom buildings in our parking lot West of the high school building along Welsh Street. We will no longer need these buildings and plan to move them to other locations within the District. College Station ISD requests a Condition Use Permit to relocate Buildings No. "C" and No. "D" from their present location at A & M Consolidated High School to a new location at Pebble Creek Elementary School, 200 Parkview, College Station, Texas. The location of these buildings at Pebble Creek Elementary School is shown on the enclosed site plan titled Exhibit "C" prepared by Cheatham & Associates. Cheatham has modified and sealed their letter (2 copies) and has incorporated information on the site plan drawing (2 copies) requested in City of College Station Memorandum dated June 23, 1999 (copy attached). Please note that the location of these buildings is different from the initial issue of the site plan. Each building is on a raised pier and beam foundation, wood framing, metal siding and roof, insulated suspended ceilings, prefinished wood paneling interior walls, carpeted floors, has a 150 A 120/240 volt primary electrical service panel, flourescent lighting, grounded duplex electrical outlets, electrical HVAC thru wall units for each of two rooms. These buildings were constructed at the A & M Consolidated High School site and were fully inspected by the City of College Station Building Inspection Department. Records of the City inspection of the construction of this building should be on file. Construction Services 1812 Welsh Street College Station, TX 77840 409-694-5610 FAX 409-694-5612 JIM SCALES, Ph.D. Superintendent of Schools G ti~~GF STA k'~y z d o a ANT scH0 College Station Independent School District E,xcelfence In Education... .An Investment In The Future July 9, 1999 Ms. Natalie Ruiz Development Coordinator City of College Station 1101 Texas Avenue College Station, Texas 77842 Letter No. 2046 Subject: College Station Junior High School Conditional Use Permit for Temporary Classroom Building Dear Ms. Ruiz: In 1997 we received City approval to locate five temporary double classroom buildings in our parking lot West of the high school building along Welsh Street. We will no longer need these buildings and plan to move them to other locations within the District. College Station ISD requests a Condition Use Permit to relocate Building No. "B" from its present location at A & M Consolidated High School to a new location at College Station Junior High School, 900 Rock Prairie Road, College Station, Texas. The location of this building at College Station Junior High School is shown on the enclosed site plan titled Exhibit "A" prepared by Cheatham & Associates. Cheatham has modified and sealed their letter (2 copies) and has incorporated information on the site plan drawing (2 copies) requested in City of College Station Memorandum dated June 23, 1999 (copy attached). A dimension of 10' was accidently left on the drawing and has been deleted in red and initialed by the undersigned. We are requesting a corrected site plan. Due to the urgent need of this classroom we request that the City consider this request from these two altered plans. Every attempt will be made to forward corrected drawings as soon as possible. This building is on a raised pier and beam foundation, wood framing, metal siding and roof, insulated suspended ceilings, prefinished wood paneling interior walls, carpeted floors, has a 150 A 120/240 volt primary electrical service panel, flourescent lighting, grounded duplex electrical outlets, electrical HVAC thru wall units for each of two classrooms. Construction Services 1812 Welsh Street College Station, TX 77840 409-694-5610 FAX 409-694-5612 JIM SCALES, Ph.D. Superintendent of Schools This building was constructed at the A & M Consolidated High School site and was fully inspected by the City of College Station Building Inspection Department. Records of the City inspection of the construction of this building should be on file. We will engage a moving contractor to move this building to the new location. A local general contractor will be contracted to construct install underpinning, a covered porch, access ramp connected to existing sidewalks and provide the necessary handrails, etc. required for TAS and ADA accessible facilities. An electrical contractor will connect and energize electrical service to this building, install and extend services from existing fire alarms, telephones, school intercommunication system, technology wiring for computer and video education devices. City electrical transformer change out has been arranged for with the City of College Station Public Utility Department and a request has been issued for the change. The above requirements have been reviewed with the City Building Official and Fire Department for their familiarization only. Their final approval will be secured along with the respective moving, building and occupancy permits. Please advise us of all fees that may be due, our participation in any hearings or meetings required and of any additional information you may require. We are available to assist you in any way that will expedite the issuance of the conditional use permit for this temporary classroom building. This temporary classroom building is essential to the start of school. Please advise me of the anticipated schedule of reviews, hearings, meetings, etc. so we may evaluate our need to make other arrangements for the classes scheduled for this building. WJS/b Enclosure - City of College Station Memorandum dated June 23, 1999 (1 Copy) Cheatham Exhibit A letter dated July 2, 1999 (2 Copies) Cheatham Site Plan Exhibit A (2 copies) A & M Consolidated High School Temp. Building Layout (2 copies) Sketches of Proposed Building and Electrical (2 copies) cc: D. Neal File UP G yyEG F. STgCollege Station Independent School District o ~ Exre!lence In Education... .sin Investment In glue Future c^'J'd O FNT Sc"O' July 22, 1999 Letter No. 2101 Ms. Natalie Ruiz Development Coordinator City of College Station 1101 Texas Avenue College Station, Texas 77842 Subject: College Hills Elementary School Conditional Use Permit for Temporary Classroom Building Dear Ms. Ruiz: In 1997 we received City approval to locate five temporary double classroom buildings in our parking lot West of the high school building along Welsh Street. We will no longer need these buildings and plan to move them to other locations within the District. College Station ISD requests a Condition Use Permit to relocate Building No. "B" from its present location at A & M Consolidated High School to a new location at College Hills Elementary School, 1101 Williams Street, College Station, Texas. The location of this building at College Hills Elementary School is shown on the enclosed site plan titled Exhibit "B" prepared by Cheatham & Associates. Cheatham has modified and sealed their letter (2 copies) and has incorporated information on the site plan drawing (2 copies) requested in City of College Station Memorandum dated June 23, 1999 (copy attached). Please note that the location of this building has been moved to avoid the utility easement as shown on the site plan. This building is on a raised pier and beam foundation, wood framing, metal siding and roof, insulated suspended ceilings, prefinished wood paneling interior walls, carpeted floors, has a 150 A 120/240 volt primary electrical service panel, flourescent lighting, grounded duplex electrical outlets, electrical HVAC thru wall units for each of two classrooms. There will be no gas, water or sewer connections to this building. This building was constructed at the A & M Consolidated High School site and was fully inspected by the City of College Station Building Inspection Department. Records of the City inspection of the construction of this building should be on file. Construction Services 1812 Welsh Street College Station, TX 77840 409-694-5610 FAX 409-694-5612 JIM SCALES, Ph.D. Superintendent of Schools C~~EGE ST,,T'oy College Station Independent School District • F Y U a A F y EXceffence In Education-An Investment In The Future Fy Q d~NT Sc"00 July 22, 1999 Letter No. 2102 Ms. Natalie Ruiz Development Coordinator City of College Station 1101 Texas Avenue College Station, Texas 77842 Subject: College Station Junior High School Corrected Site Plan for Temporary Classroom Building Dear Ms. Ruiz: Attached are two copies of the corrected site plans for subject school indicating the sixteen feet separation between buildings. This corrected copy is for your records. Yours truly, Constructio anager WJSIceb Enclosure cc: D. Neal File UP Construction Services 1812 Welsh Street College Station, TX 77840 409-694-5610 FAX 409-694-5612 JIM SCALES, Ph.D. Superintendent of Schools We will engage a moving contractor to move this building to the new location. A local general contractor will be contracted to remove and replace fencing, install underpinning, construct a covered porch, access ramp connected to existing sidewalks and provide the necessary handrails, etc. required for TAS and ADA accessible facilities. An electrical contractor will connect and energize electrical service to this building, install and extend services from existing fire alarms, telephones and technology wiring for computers. The above requirements have been reviewed with the City Building Official and Fire Department for their familiarization only. Their final approval will be secured along with the respective moving, building and occupancy permits. Please advise us of participation in any hearings or meetings that may be required, of all fees that may be due and of any additional information you may require. We are available to assist you in any way that will expedite the issuance of the conditional use permit for these temporary classroom buildings. Yours truly, W. J. a e Construction Manager WJS/b Enclosure - Copy of City of College Station Memorandum June 23, 1999 (1 copy) Cheatham Sealed Drainage Impact Letter July 2, 1999 (2 copies) Cheatham Site Plan Exhibit D (2 Copies) Bee Creek Tributary B Flood Map - Existing Conditions (2 copies) Bee Creek Tributary B Flood Map - Proposed Conditions (2 copies) Sketch - A&M Consolidated High School Temp. Classroom Plan -(2 copies) Sketches - Proposed Building and Electrical Installation (2 copies) cc: D. Neal File UP Date *1 If City of College Station Public Utilities Department Electrical Division P.O. Box 9960 College Station. TX 77842 4091764-3438 4091764-3452 FAX Contacts: Tony Michaisky, Operations Coordinator, 409-764-3438 Ray Havens, Superintendent, 409-764-3502 We the undersigned of hereby request, The City of College Station Electrical Division to: S.er r T2our.~o•~.nyt T T s~ri.~. <<.~r2w„ ~.o....rr ~O~ ~~...y~a ~er ~.~oac. T i0 y •Si~uitt ~~r ~~et~cr Business name /&"02rz.&cr fn~~! f-r/-7 - e:UEQr 1,q ►i ~~•d~ 00~cw Location 'VDO /4fcr Owners name .occ a -e f~•~~' .1jo0 - Billing address /w4x-v GoGL x ee -Tessa.. , Phone Fax number Estimated needed complete 6/zs /94 - -45-C. We further understand that we are to pay the City of College Station for the total cost {10 60193 ,4axW services performed for the following project. • , Thank you, Owner (Letter ftst-be signed) MAIL OR FAX TO ABOVE ADDRESS