February 28, 2003
TO: Richard Calloway, Via fax 512.477.7259
FROM: Bridgette George, Assistant Development Manager
SUBJECT: A&M Methodist Church Fellowship Hall
Staff reviewed the above -mentioned engineering documents as requested. The
following page is a list of staff review comments detailing items that need to be
addressed. Please address the comments and submit the following information
for further staff review and approval of the plans:
One (1) certified hydrant pressure report.
If you have any questions or need additional information, please call Spencer
Thompson or myself at 764.3570.
Attachments: Staff Review Comments
Cc: A&M Methodist Church, Via fax 879.846.3387
Veronica J. B. Morgan, Mitchell & Morgan, L.L.P., Via fax 260-3564
Case file no.
Home of Texas ABM University
ev -
11111�0 U T, 14 1 wl�
ENGINEERING REVIEW
COMMENTS No. 1
1. Please provide at least one "certified" hydrant pressure report such that it can
be determined what extant pressure is to be placed in the calculations and
where.
2. If calculations were made by using a software package, please provide the
input/output page from the program. Otherwise, please provide sample
calculations utilized in spreadsheet.
3. Please state reasoning as to why 2,000 gpm in particular should be placed at
the "Bryan" node to simulate the interconnect.
Reviewed by: Spencer Thompson Date: February 27, 2003