HomeMy WebLinkAboutDPItem
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
C3 Development Phase 1
Engineer's Estimate of Construction Costs
May 22, 2015
Description Unit Unit Price
Site Preparation
Mobilization L.S. $18,500.00
Clearinq and Grubbinq Ac. $1,500.00 ,, '·. Site Preparation Subtotal
Water System Co nstruction
8" PVC, C900 Cl 200, Water Line, Str. Backfill L.F. $70.00
6" PVC, C900 Cl 200, Water Line, Str. Backfill L.F. $60.00
8" DIP, Water Line, Str. Backfill L.F. $85.00
6" DIP, Water Line, Str. Backfill L.F. $75.00
8" x 45 deq M.J. Bend EACH $800.00
8"x22.5 M.J. deo. Bend EACH $800.00
8" x 6" M.J. Tee EACH $1 ,000.00
8"x 6" M.J. Reducer EACH $400.00
8" M.J. Gate Valve EACH $1,200.00
6"x6" M.J. Tee EACH $800.00
6" M.J. Gate Valve EACH $900.00
6" M.J. Gate Valve & Box with LockinQ Lid EACH $1, 100.00
6"x45 M.J. dea. Bend EACH $700.00
8" x 1-1 /2" Service Saddle EACH $200.00
8" x 2" Service Saddle EACH $250.00
6" x 1-1/2" MJ Reducer EACH $200.00
1" Type K Copper Tubinq with Structural Backfill L.F. $100.00
1-1/2" Type K Copper Tubini:i with Structural Backfill L.F. $125.00
2" Tvoe K Coooer TubinQ with Structural Backfill L.F. $150.00
Bacteria Test L.S. $2,000.00
Pressure Test L.S. $3,500.00
Trench Safetv L.F. $5.00
Connect to Existinq Svstem EACH $2,000.00
Std. Fire Hvdrant Assemblv EACH $4,000.00
. . Water System Subtotal
Erosion Control Co nstruction
1t:.ros1on Lontro1 t-'lan & ::;earmentatron Lontrol (rnc1uaes srn tencrng,
construction exits, straw bale barriers, inlet protection, grass seeding, L.S. $5,000.00 and any other sedimentation control devices)
. Erosion Control Subtotal
. Total Construction Cost
Quantity Total
1.0 $18,500
0.5 $750
$19 250
537 $37 ,590
509 $30,540
40 $3,400
20 $1 ,500
17 $13,600
3 $2,400
4 $4,000
1 $400
3 $3,600
4 $3,200
7 $6,300
4 $4,400
6 $4,200
1 $200
3 $750
1 $200
24 $2,400
114 $14,250
113 $16,950
1 $2,000
1 $3,500
958 $4,790
1 $2,000
3 $12,000
$174 170
1.0 $5,000
$5 000
$198 420
The above construction estimate is based on the engineer's preliminary opinion of probable construction costs. This estimate
constitutes our best judgment at this time. Please note that the engineer does not have any control over contractor or supplier
workloads and the degree to which inflation may affect project costs between now and the bid date. During construction, additional
features may become apparent as the work progresses, which will result in an increan· cost. ,.,,.,.,,,,,,,,,
-----::"(, 'C. OF rs:\\\ . .::' "\I>-.. ... • .. •• -t. ,,, \
: <::i ..... *·· ... -,IS', ,# * .. · .... ,, ,,, *... ... * ~ , .... : .......................... :· ..... .z ~.~~~.9.~!~~.~:!?:.~9B§~~.~ Veron ca JB Mor
~ l\ 77689 /$ J 11 '7-
1,,01(\· ... ~~G a«-<:>/ffi ~ Y'\)"l+tA f-14-tf J t '.-" · . ., /STE"/ ~ .::' ,, '\S's ........... ~0 .:
'''\/ONAL € ........ --.,,,,,, ..... ~
Date
Page 1 of 1
...
Erika Bridges, EIT, CFM
City of College Station
Planning & Development Services
PO Box 9960
College Station, TX 77842
MITCHELL
MORGAN
RE: SANITARY SEWER CAPACITY LETTER FOR THE C3 DEVELOPMENT-PHASE 1
Dear Erika:
April 7, 2015
This letter is intended to show that the existing public sanitary sewer system built with the
Cottages of College Station development has adequate capacity for Phase 1 of the C3
Development project. The C3 Phase 1 Development is located near the Market Street and
Holleman Drive intersection, bounded by the existing Cottages of College development,
Dowling Road and the future extension of Junction Boys Road. The sanitary sewer system for
this phase will be private and connect to an existing 8" sanitary sewer stubout constructed with
the Cottages of College Station development.
We have attached the Phase 1 site plans and sanitary sewer plan sheets, as well as two exhibits
to this letter. Exhibit A shows the Phase 1 area to be served and Exhibit B is a spreadsheet
showing the capacity of the Phase 1 sanitary sewer line as designed. The 2011 Capstone
Cottages sanitary sewer report assumed a total proposed flow of 0.748 cfs, based on 20
du/acre and 5340 gpd/acre and Retail B3 at 3500 gpd/acre (Exhibit 4 of the 2011 report). From
Exhibit B, the flow in pipe segment L9 represents the proposed total flow for Phase 1 at 0.304
cfs, less than the assumed value from the original 2011 report. A copy of that report is
attached as Appendix B.
If you have any comments, or wou19ft~~~uss this further, please feel free to contact me .
.:-=:_7:-\ ...... ~~:r-4~'•1 ,;' e;, .... ~ .... 1< ,,
n erely, !**./ ~ ....... ::-:·.~--'~ ~vERoNicA·:;;~:-~-~~~-~ ~·-~:.:···"'"77689 /$ J
.. , ~ .... «,.Q/,ffe $ 11 o,<-,-..~€G1s1~~ .. ··& ~ PE CFM 11t ~.s"· ......... ·e.~.?'
I I t\, SIONf>-\.. v--
Managing Partner ·fi~)f-~\#3
Cc : file
3204 EARL RUDDER FWY. S. • COLLEGE STATION, TX 77845 • T 979.260 6963 • F 979.260 3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@m1tchellandmorgan com • www m1tchellandmorgan com
FOR OFFICE USE ONLY
CASE NO.: IS-g€?
CITY or Col.LEGE STATION
Homt o/Ttxas A&M Univm ity'
DATE susMITTED: ot · oa · 1s
TIME: f¢: ciZO
SITE PLAN APPLICATION
GENERAL
STAFF: +B-'-'75=---------
MINIMUM SUBMITTAL REQUIREMENTS:
$932 Site Plan Application Fee.
$350 Non-Residential Architectural Standards I Northgate Building Review Application Fee (if applicable).
$600 (minimum) Development Permit Application I Public Infrastructure Review and Inspection Fee. Fee is
1 % of acceptable Engineer's Estimate for public infrastructure, $600 minimum (if fee is > $600, the balance is
due prior to the issuance of any plans or development permit).
Application completed in full. This application form provided by the City of College Station must be used
and may not be adjusted or altered.
Six (6) folded copies of site plan.
One (1) folded copy of the landscape plan.
One (1) copy of the following for Non-Residential Architectural Standards building review or Northgate
B~ilding Review (if applicable).
I Building elevations to scale for all buildings.
A list of building materials for all facade and screening.
Color samples for all buildings or list colors to be used from the approved color palette.
Electronic copy of Site Plan e-mailed to csuelectdesign@cstx.gov.
Two (2) copies of the grading, drainage, and erosion control plans with supporting drainage report.
Two (2) copies of the Public infrastructure plans and supporting documents (if applicable).
Traffic Impact Analysis or calculations of projected vehicle trips showing that a TIA is not necessary for the
proposed request (if applicable). {frt'Ylckv Wi.ff? /<e:Zt>Y1 ~.,,~CJ)
The attached Site Plan Non-Residential Architectural Standards Building Review and Northgate Building
Review checklists (as applicable) with all items checked off or a brief explanation as to why they are not
check off.
Date of Optional Preapplication or Stormwater Management Conference .:..;cM.:..;::a:.:..;rc""'"h'-1'--'8~2-"-0""'"""15"-----------
NAME OF PROJECT C3 Development Phase 1
ADDRESS 2415 Junction Boys Road
LEGAL DESCRIPTION (Lot, Block, Subdivision) -=Cc:.:ra:..:wfi:..:..o:::..:rd-=-=8:.=u:.:..::mc:.:e:.:::tt:L....:.:Tra=ct:...:8::....:1J....;..8..:....:1.=2-=-1 ___________ _
APPLICANT/PROJECT MANAGER'S INFORMATION (Primary contact for the project):
Name Mitchell & Morgan, LLP, C/O Veronica Morgan, PE E-mail v@mitchellandmorgan.com
Street Address 3204 Earl Rudder Freeway South
City College Station State Texas Zip Code _7_78_4_5 ____ _
Phone Number 979-260-6963 Fax Number 979-260-3564
---------------~
PROPERTY OVVNER'S INFORMATION:
Name Capstone-CS, LLC CIO Rob Howland, COO E-mail rhowland@capstonemail.com
Street Address 431 Office Park Drive
City Birmingham State Alabama Zip Code _3_52_2_3 ____ _
Phone Number 205-414-6400 Fax Number 205-414-6405
---------------~
Revised 9/14 Page 1 of 11
ARCHITECT OR ENGINEER'S INFORMATION:
Name Amanda Wallis, Project Manager E-mail awa/lis@capstonemail.com
Street Address 431 Office Park Drive
City Birmingham State Alabama Zip Code _3_52_2_3 ____ _
Phone Number 205-414-6400 Fax Number 205-414-6405
~--------------~
OTHER CONTACTS (Please specify type of contact):
Name Eric McNair, Landscape Architect E-mail emcnair@capstonemail.com
Street Address 431 Office Park Drive
City Birmingham State Alabama Zip Code _3_52_2_3 ____ _
Phone Number 205-414-6400 Fax Number 205-414-6405
~--------------~
Current zoning _P_D_D __________________________________ _
Present use of property Irrigation Pond & Vacant-Undeveloped
Proposed use of property Irrigation/Retention Pond & Multi-Family
Number of parking spaces required ___ 2_2_8-'S..L.p...;;.;a..;;...ce"-'s'----Number of parking spaces proposed ---=2:..::.3..:...1....:::S:.c:.P.::::.ac::..::e:.::s=-----
Is there Special Flood Hazard Area (Zone A or Zone AE on FEMA FIRM panels) on the property? I Yes IX No
This .information is necessary to help staff identify the appropriate standards to review the application and will be used to
help determine if the application qualifies for vesting to a previous ordinance. Notwithstanding any assertion made,
vesting is limited to that which is provided in Chapter 245 of the Texas Local Government Code or other applicable law.
Is this application a continuation of a project that has received prior City platting approval(s) and you are requesting the
application be reviewed under previous ordinance as applicable?
IX Yes
I No
If yes, provide information regarding the first approved application and any related subsequent applications (provide
additional sheets if necessary):
Project Name: The Cottages of College Station
City Project Number (if known): 08-00500007
Date I Timeframe when submitted: P&Z Approval -February 21 , 2008
Revised 9/14 Page 2of11
CERTIFICATIONS REQUIRED FOR ALL DEVELOPMENT
Owner Certification:
1. No work of any kind may start until a permit is issued.
2. The permit may be revoked if any false statements are made herein .
3. If revoked, all work must cease until permit is re-issued.
4. Development shall not be used or occupied until a Certificate of Occupancy is issued.
5. The permit will expire if no significant work is progressing within 24 months of issuance.
6. Other permits may be required to fulfill local, state, and federal requirements. Owner will obtain or show
compliance with all necessary State and Federal Permits prior to construction including NOi and SWPPP.
7. If required, Elevation Certificates will be provided with elevations certified during construction (forms at slab pre-
pour) and post construction.
8. Owner hereby gives consent to City representatives to make reasonable inspections required to verify
compliance.
9. If, stormwater mitigation is required, including detention ponds proposed as part of this project, it shall be
designed and constructed first in the construction sequence of the project.
10. In accordance with Chapter 13 of the Code of Ordinances of the City of College Station, measures shall be taken
to insure that all debris from construction, erosion, and sedimentation shall not be deposited in city streets, or
existing drainage facilities. All development shall be in accordance with the plans and specifications submitted to
and approved by the City Engineer for the above named project. All of the applicable codes and ordinances of the
City of College Station shall apply.
11 . The information and conclusions contained in the attached plans and supporting documents will comply with the
current requirements of the City of College Station, Texas City Code, Chapter 13 and associated BCS Unified
Design Guidelines Technical Specifications, and Standard Details. All development has been designed in
accordance with all applicable codes and ordinances of the City of College Station and State and Federal
Regulations.
12. Release of plans to ---· (name or firm) is authorized for bidding purposes
only. I understand that final approval and release of plans and development for construction is contingent on
contractor signature on approved Development Permit.
13. I, THE OWNER, AGREE TO AND CERTIFY THAT ALL STATEMENTS HEREIN, AND IN ATTACHMENTS FOR
THE DEVELOPMENT PERMIT APPLICATION, ARE, TO THE BEST OF MY KNOWLEDGE, TRUE, AND
ACCURA~A ~ ~ ~~ _L-l_/_1
1
+--}J_S __ _
Property Owner{s) Date
Engineer Certification:
1. The project has been designed to ensure that stormwater mitigation, including detention ponds, proposed as part
of the project will be constructed first in the construction sequence.
2. I will obtain or can show compliance with all necessary Local, State and Federal Permits prior to construction
including NOi and SWPPP. Design will not preclude compliance with TPDES: i.e., projects over 10 acres may
require a sedimentation basin.
3. The information and conclusions contained in the attached plans and supporting documents comply with the
current requirements of the City of College Station, Texas City Code, Chapter 13 and associated BCS Unified
Design Guidelines. All development has been designed in accordance with all applicable codes and ordinances
of the City of College Station and State and Federal Regulations. ~~
4. I, TJtNGINEER, AGREE TO AND CERTIFY THAT ALL STATEMENTS HEREIN, AN ,,.t~s
FO E DEVELOPMENT PERMIT APPLICATION, ARE, TO THE BEST OF MY KN_. • ~b€':~
AC U ATE. S * / Jlf( _ \ '* ~ ~.~ .. ~ ............................. NI
. \(\\ I fl \ ~ \ \ \C... ~ VER0~~9,~.~:~:.~cr····~ ,, \'\.\J\i ' J ,, ..... :..... : ~ --~ -0\ 77689 ,:f.li ~ ---~1---'·----------.-i ~ " ¢ ... {ii~
Engineer Date 111~,i.;;_.?,~G1srf.!',~~"&~ .,, ~.'\9. ......... 'C..~ .::-
Revised 9/14 Page 4of11
· The following CERTIFICATIONS apply to development in Special Flood Hazard Areas.
Required for Site Plans, Final Plats, Construction Plans, Fill /Grading Permits, and Clearing Only
Permits:*
certify, as demonstrated in the attached drainage study , that the
alterations or development covered by this permit, shall not:
(i) increase the Base Flood elevation;
(ii) create additional areas of Special Flood Hazard Area;
(iii) decrease the conveyance capacity to that part of the Special Flood Hazard Area that is not in the floodway
and where the velocity of flow in the Base Flood event is greater than one foot per second. This area can
also be approximated to be either areas within 100 feet of the boundary of the regulatory floodway or
areas where the depth of from the BFE to natural ground is 18 inches or greater;
(iv) reduce the Base Flood water storage volume to the part of the Special Flood Hazard Area that is beyond
the floodway and conveyance area where the velocity of flow in the Base Flood is equal to and less than
one foot per second without acceptable compensation as set forth in the City of College Station Code of
Ordinances, Chapter 13 concerning encroachment into the Special Flood Hazard Area; nor
(v) increase Base Flood velocities.
beyond those areas exempted by ordinance in Section 5.11 .3a of Chapter 13 Code of Ordinances.
Engineer Date
Initial
D * If a platting-status exemption to this requirement is asserted, provide written justification under separate
letter in lieu of certification.
Required for Site Plans, Final Plats, Construction Plans, and Fill/ Grading Permits:
NJ Pr , certify to the following: B. I,
(i)
~~~---1--=-I+-'-~~~~~~~~~~
that any nor/residential or multi-family structure on or proposed to be on this site as part of th is application is
designed to prevent damage to the structure or its contents as a result of flooding from the 100-year storm.
N/ft I
Engineer Date
Additional certification for Floodway Encroachments:
c. I, ~/I} , certify that the construction, improv~ment, or fill cov~red by thi s
permit shall not mcfease the base flood elevation. I will apply for a variance to the Zoning Board of Adjustments.
N)lt •
Engineer Date
Page 5 of 11
Revised 9/14
Required for all projects proposing structures in Special Flood Hazard Area (Elevation Certificate
required).
Residential Structures:
D. I, N/A , certify that all new construction or any substantial improvement
of any residential structure shall have the lowest floor, including all utilities, ductwork and any basement, at an
elevation at least one foot above the Base Flood Elevation. Required Elevation Certificates will be provided with
elevations certified during construction (forms at slab pre-pour) and post construction.
NIA
Engineer I Surveyor Date I
Commercial Structures:
E. I, JJ/A , certify that all new construction or any substantial improvement
of any commercial, industrial, or other non-residential structure are designed to have the lowest floor, including all
utilities, ductwork and basements, elevated at least one foot above the Base Flood Elevation
N//r I
Engineer I Surveyor Date
OR
I, N/f'J , certify that the structure with its attendant utility , ductwork,
basement and sartitary facilities is designed to be flood-proofed so that the structure and utilities, ductwork,
basement and sanitary facilities are designed to be watertight and impermeable to the intrusion of water in all
areas below the Base Flood Elevation, and shall resist the structural loads and buoyancy effects from the
hydrostatic and hydrodynamic conditions.
Required Elevation Certificates will be provided with elevations certified during construction (forms at slab pre-
pour) and post construction.
Engineer I Surveyor Date
Conditions or comments as part of approval:
Revised 9/14 Page 6 of 11
CITY OF C oll.EGE STATION
Home of Texas A&M University"
SITE PLAN MINIMUM REQUIREMENTS
(ALL CITY ORDINANCES MUST BE MET)
INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
[81 Sheet size -24" x 36" (minimum).
[81 A key map (not necessarily to scale).
[81 Title block to include:
[81 Name, address, location, and legal description
[81 Name, address, and telephone number of applicant
[8J Name, address, and telephone number of developer/owner (if differs from applicant)
[8J Name, address, and telephone number of architect/engineer (if differs from applicant)
[8J Date of submittal
[8J Total site area
[8J North arrow.
[8] Scale should be largest standard engineering scale possible on sheet.
[8J Ownership and current zoning of parcel and all abutting parcels.
[8J The total number of multi-family buildings and units to be constructed on the proposed project site.
[8] The density of dwelling units per acre of the proposed project.
[8] The gross square footage of all buildings and structures and the proposed use of each. If different uses are to be
located in a single building, show the location and size of the uses within the building. Building separation is a
minimum of 15 feet w/o additional fire protection.
Locations of the following on or adjacent to the subject site:
Designate between existing and proposed
[8J The density of dwelling units per acre of the proposed project.
[8J Phasing. Each phase must be able to stand alone to meet ordinance requirements.
[8J Buildings (Existing and Proposed).
[8J Setbacks according to UDO, Article 5.
Geography
[8J Water courses.
[8J 100 yr. floodplain and floodway (if applicable) on or adjacent to the proposed project site. Please note if there is none
on the site with confirming FEMA/FIRM map number.
[8J Existing topography (2' max or spot elevations) and other pertinent drainage information. (If plan has too much
information, show drainage on separate sheet.)
[8J Proposed grading (1 ' max for proposed or spot elevations) and other pertinent drainage information. (If plan has too
much information, show drainage on separate sheet.)
Streets, Parking, and Sidewalks
lg] Existing streets and sidewalks (R.O.W.).
lg] Existing Driveways, both opposite and adjacent to the site according to UDO, Article 7.
lg] Proposed drives. Minimum drive aisle width according to UDO, Article 7
lg] Indicate proposed driveway throat length according to UDO, Article 7
lg] Proposed curb cuts.
rgi For each proposed curb cut (including driveways, streets, alleys, etc.) locate existing curb cuts on the same and
opposite side of the street to determine separation distances between existing and proposed curb cuts.
lg] Proposed curb and pavement detail.
lg] A 6" raised curb is required around all edges of all parts of all paved areas without exception. (To include island,
planting areas, access ways, dumpster locations, utility pads, etc.) No exception will be made for areas
designated as "reserved for future parking".
~Proposed medians.
lg] Proposed sidewalks (both public and private).
~Proposed pedestrian/bike circulation and facilities for non-residential buildings (UDO, Article 7).
lg] Off-Street parking areas with parking spaces drawn, tabulated, and dimensioned.
lg] Designate number of parking spaces required by ordinance and provided by proposal.
[8] Handicap parking spaces.
[8] Parking Islands drawn and dimensioned with square footage calculated according to UDO, Section 7.2 or 7.9 fornon-
residential buildings.
[8] Parking setback from R.O.W. to curb of parking lot as required.
Nm. Wheelstops may be required when cars overhang onto property not owned by the applicant or where there may be 'F conflict with pedestrian or bike facilities, handicap accessible routes or above ground utilities, signs or other conflicts.
[8] Security gates, showing swing path and design specs with colors.
~Guardrails. Include design and colors.
[8] Traffic Impact Analysis for non-residential development (UDO, Article 7).
lg] Please note if none is required.
[8] Will there be access from a TxDOT R.O.W.? D Yes [8] No
If yes, then TxDOT permit must be submitted with this application.
Easements and Utilities
[8] Easements -clearly designate as existing or proposed and type (utility, access, etc.)
[8] Utilities (noting size and designate as existing or proposed) within or adjacent to the proposed site, including building
transformer locations, above ground and underground service connections to buildings, and drainage inlets.
[8] Sewer Design Report (if applicable).
[8] Water Design Report and/or Fire Flow Report (if applicable).
[8] Drainage Report with a Technical Design Summary.
[8] Meter locations, existing and proposed (must be located in public R.O.W. or public utility easement).
[8] Provide a water and sanitary sewer legend to include
lg] Minimum water demands
[8] Maximum water demands
lg] Average water demands in gallons per minute, and
lg] Maximum sewer loadings in gallons per day
[8] Will there be access from a TxDOT R.O.W.? D Yes [8] No
If yes, then TxDOT permit must be submitted with this application.
Revised 9/14 Page 8of11
Fire Protection
(81 Show fire lanes. Fire lanes with a minimum of 20 feet in width with a minimum height clearance of 14 feet must be
established if any portion of the proposed structure is more than 150 feet from the curb line or pavement edge of a
public street or highway.
(81 Show proposed and existing fire hydrants. Fire hydrants must be located on the same side of a major street as a
project, and shall be in a location approved by the City Engineer. Any structure in any zoning district other than R-1 ,
R-1A, or R-2 must be within 300 feet of a fire hydrant as measured along a public street, highway or designated fire
lane.
NOTE: Fire hydrants must be operable and accepted by the City, and drives must have an all weather surface before a
building permit can be issued.
(81 Will building be sprinkled? (81 Yes D No {5C>(Yt12)
If the decision to sprinkle is made after the site plan has been approved, then the plan must be resubmitted. If Yes,
(81 Show fire department connections. FDC's should be within 100' of the fire hydrant. They shall be accessible from
the parking lot without being blocked by parked cars or a structure.
Landscaping
(81 Landscape plans as required in Article 7 of the Unified Development Ordinance. The landscaping plan can be shown
on a separate sheet if too much information is on the original site plan. If requesting protected tree points, then those
trees need to be shown appropriately barricaded on the landscape plan. Attempt to reduce or eliminate plantings in
easements.
Include information on the plans such as:
(8) required point calculations
~ additional streetscape points required . Streetscape compliance is required on all streets.
QS] calculations for # of street trees required and proposed (proposed street tree points will accrue toward total
landscaping points.)
(8) proposed new plantings with points earned
(81 proposed locations of new plantings
~screening of parking lots, 50% of all shrubs used for screening shall be evergreen.
~ screening of dumpsters, concrete retaining walls, off street loading areas, utility connection points, or other
\ areas potentially visually offensive.
fl:P'existing landscaping to remain
~show existing trees to be barricaded and barricade plan. Protected points will only be awarded if barricades are
up before the first development permit is issued. \1ftl Buffer as required in Article 7 of the Unified Development Ordinance.
(8) Show irrigation system plan. (or provide note on how irrigation system requirement will be met prior to issuance of C.
0 .) All plans must include irrigation systems for landscaping. Irrigation meters are separate from the regular water
systems for buildings and will be sized by city according to irrigation demand submitted by applicant and must
include backflow prevention protection.
(8) Is there any landscaping in TxDOT R.O.W.? D Yes (8) No
If yes, then TxDOT permit must be submitted at the time of application.
Other
! Common open spaces sites
Loading docks
Detention ponds
tij). Retaining walls
(8) Sites for solid waste containers with screening. Locations of dumpsters are accessible but not visible from streets or
residential areas. Gates are discouraged and visual screening is required. (Minimum 12 x 12 pad required.)
(8) Are there impact fees associated with this development? D Yes (8) No
NOTE: Signs are to be permitted separately.
Revised 9/14 Page 9of11
CITY OF Coll.EGE STATION
Home of Texas A&M Univmity0
NRA BUILDING REVIEW MINIMUM REQUIREMENTS
(ALL CITY ORDINANCES MUST BE MET)
INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
Refer to UDO Section 7.9 Non-Residential Architectural Standards, as appropriate.
~ Sheet size -24" x 36" (minimum).
tfJ1r Title block to include:
~ Name, address, location, and legal description
"$. Name, address, and telephone number of applicant
i Name, address, and telephone number of developer/owner (if differs from applicant)
Name, address, and telephone number of architect/engineer (if differs from applicant)
Date of submittal
Scale should be largest standard scale possible on sheet. t . V-0 List of colors from the City of College Station color palette to be utilized or proposed equivalents.
}f/# Color samples.
"¢1-List of materials to be utilized.
~ Elevations of each non-residential building and screening structure. Show placement of materials and colors on
, the facades according to UDO Section 5.6.B or 7.9. N/h lnc[ude the following dimensions:
~ Total vertical square footage minus openings (for each fac;;ade separately) % Total vertical square footage of transparency (for each fac;;ade separately in Northgate)
~ Total vertical square footage of each building material (for each fac;;ade separately)
iJ//b Total vertical square footage of each color (for each fac;;ade separately)
lfk Graphic representation and/or description of existing buildings in building plot to show material, color, and r architectural harmony.
Revised 9/14 Page 10 of 11
I •
CITY OF C OLLEGE STATION
Home o/Texas A&M University•
NORTHGATE BUILDING REVIEW MINIMUM REQUIREMENTS
(ALL CITY ORDINANCES MUST BE MET)
INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
Refer to UDO Section 5.6. Design Districts, B. Northgate Districts (NG)
M/B Sh~aj size :: 24~ ~ ~" (minimuml
i, Title block to include:
Name, address, location, and legal description
Name, address, and telephone number of applicant
'tJj. Name, address, and telephone number of developer/owner (if differs from applicant) If# Name, address, and telephone number of architect/engineer (if differs from applicant)
!f/p Date of submittal
1fQA Scale should be largest standard engineering scale possible on sheet.
tqh, List of colors from the City of College Station Northgate color palette to be utilized or proposed
Mh... equivalents with color samples.
'[f.11' List of materials to be utilized.
lffA Elevations of each building and screening structure. Show placement of materials and colors
;· on the facades and identify public entrances.
Include the following dimensions: t Total vertical square footage minus openings (for each fa<;ade separately)
>{/lJ Total vertical square footage of each building material (for each fa<;ade separately)
tW Total vertical square footage of each color (for each fa<;ade separately)
If/Jc Total vertical square footage of transparency between zero and eight feet (0-8') above ground
, level (for each non-residential fa<;ade)
'7'J1 Graphic representation and/or description of existing buildings in building plot to show material,
color, and architectural harmony.
Revised 9/14 Print Form I · Page 11 of 11
Erika Bridges, EIT, CFM
City of College Station
Planning & Development Services
PO Box 9960
College Station, TX 77842
MITCHELL
MORGAN
RE: LETTER OF ACKNOWLEDGEMENT FOR C3 DEVELOPMENT PHASE 1
Dear Erika:
April 1, 2015
The purpose of this letter is to acknowledge that the construction plans for the site design
drawings for the C3 Development Phase 1 project, to the best of my knowledge do not deviate
from the B/CS Design Guidelines Manual.
I also acknowledge, to the best of my knowledge that the details provided in the construction
plans are in accordance with the Bryan/College Station Standard Details.
If you have any comments, or would like to discuss this further, please feel free to contact me.
~~''• .:?'"\~ .··········· ... -1'..ot •• ,
-C:) ••• * · ... <S',.. ,, ,;'* .· ·."?'I ~*/ ...... ~ it' .•... : .••...•••.•......•..•••••.•••••• I'! ~-~~~9.~!~~-~:~:.~.9~~~-~
. ~ ~.... 77689 /41 ! Veronica J.B. organ, PE, CFM "1,~\ -9~ «.-G/.ffi ~ . 1 ~-.. G1srE'i\ ... 0~.=-Managing Partner •t,''.s's············G~-.:-\\' IONA\.. v ...... \\' ....................... ~
Cc: file fltUJ. F-1#3
3204 EARL RUDDER FWY S. • COLLEGE STATION, TX 77845 • T 979.260.6963 • F 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@m1tchellandmorgan com • www m1tchellandmorgan com
CAPSTONE COLLEGIATE COMMUNITY (C3) DEVELOPMENT
WATER LINE ANALYSIS
April 201s
PREPARED FOR:
CAPSTONE -CS, LLC
431 OFFICE PARK DRIVE
BIRMINGHAM, ALABAMA 35223
Submitted to
e ll ~
CITY OF COLLEGE STATION
• '"' '""' of 111' Rnwrh Vn/ky
By
MITCHELL
M M
MORGAN
ENGINEERS & CONSTRUCTORS
3204 EARL RUDDER FREEWAY SOUTH
COLLEGE STATION, TX 77845
0FFlCE(979)260-6963
FAX (979) 260-3564
-
CERTIFICATION
This report for the water design for Capstone Collegiate Community C3 Development in College
Station was prepared under my supervision in accordance with provisions of the Bryan/College
Station Unified Design Guidelines for the owners of the property.
___,
Veronica J.B. orga l E., C.F.M .
Registered Professional Engineer
State of Texas No. 77689
,.., ............ "'''' _,.-.. -;~OF TE_ \\l .: -<..~ •.....•••••.••• ..r-f. •tr -~ .·· * ··.IS'_..,, ::' •. ·· ·· ..... l !..~./ ....................... .':· .. ~ .. \ ~VERONICA J.B. MORGAN "-~·····:············· .............. :f:i:.··J ~ "13 \ 77689 /!J.J J i, 16·.. '9 <:> ••• {ii .I '' -x:-;:. ••• ~G1sre.'?:.«!.··~~.: 1,, ''.S. ······ .... .._~v.: \\\°SIONA\.. v ... --
'''''''''"""" Pultu, t P-\44 3
Capstone Collegiate Community C3 Development -College Station Page 1
-
WATERLINE ANALYSIS
CAPSTONE COLLEGIATE COMMUNITY CJ DEVELOPMENT
APRIL 2015
INTRODUCTION
The Capstone Collegiate Community C3 Development will be located in College Station, Texas,
at 2415 Junction Boys Road, just southwest of the intersection of FM2818 and Holleman Drive.
C3 will be a cottage style multifamily development consisting of twenty residential buildings
being a mix of cottages, duplexes and townhome units, a maintenance shop, and trash
compactor in Phase 1 on the west side of Junction Boys Road. Placement of the buildings in
Phase 1 can be seen on the proposed site plan, Exhibit 1. There will be a second phase on the
east side of Junction Boys Road as seen on the proposed site plan, Exhibit 1A. It is not the
intent of these 2 phases to be constructed to stand alone, rather simply permitted separately to
allow the construction on the smaller phase to proceed first. The property is currently unplatted
and will be platted as Lot 3 Block 1 of the Cottages of College Station Subdivision as part of the
development of the property.
The tract is bounded to the north by Market Street, on the south by North Dowling Road and on
the east by Holleman Drive South. South of the tract is the City of College Station Dowling
Road Water Storage Facility and the Quail Run Subdivision .
FIRE FLOW DESIGN CRITERIA
An updated City of College Station system MikeURBAN model was used to model hydraulic
events on the existing distribution system. Select Node and Link labels located near the
proposed project can be seen on Exhibits 2 & 3 respectively. In order to determine if this model
is sufficient, two calibration runs were performed:
• Run 1 -Average Day Conditions without C3 Development (Exhibit 4A&B)
• Run 2 -Average Day Conditions without C3 Development and 1300 gpm Fire Flow at
Node 59414 (Exhibit 5A&B)
The results from these runs were compared to the fire flow pressure test performed by the City
of College Station Utilities Department (Exhibit 6). College Station Utilities performed the fire
flow test at 9:30 o'clock in the morning and utilized hydrants 0-137 as the flow hydrant and
hydrant 0-138 as the static hydrant. In order to closely replicate actual system conditions during
the field tests, RUNS 1&2 were modeled during an average day scenario.
Utilizing results obtained from RUN 1 static pressure at Node 59412 was found. Shown on
Tables 1, the modeled pressure (83.42 psi) was slightly higher than actual observed pressure in
the field of 80 psi . A simulated fire flow of 1300 gpm was then added to Node 59414 (RUN 2).
The modeled residual pressure at Node 59412 (82 .25 psi) was higher than the actual observed
residual pressure (75 psi). The calibration runs show that the pressure drops shown in the
model are slightly lower at the static hydrant, i.e. 1.2 psi drop in modeled vs. 5 psi drop in
measured. A comparison of measured and modeled values for the fire flow calibration run can
be found on Table 1:
Capstone Collegiate Community C3 Development -College Station Page 2
-
Table 1-Fire Flow of 1300 gpm placed at Node 59414 (Hydrant #0-137)
and Corresponding Pressure Measured at Node 59412 (Hydrant #0-138)
FLOW HYDRANT
Measured Modeled
Node Number 59414
Nozzle size 2.5
Pitot reading in PSI 60 84.98
Flow in G.P.M. 1300 1300
STATIC HYDRANT
Measured Modeled
Node Number 59412
Static PSI 80 83.42
Residual PSI 75 82.25
Since the model returned values relatively similar to those actually observed during the
calibration event it is considered a reasonable base model. This base model was used to
determine C3's effects on the system during Average, Peak and Fire Flow conditions.
C3 DEMANDS
C3 will consist of 20 structures in total on the Phase 1 site and 54 structures on the Phase 2
site. The largest structures will be the 3-story multi-family residential buildings and the
clubhouse in Phase 2. Exhibits 7 & 8 show the detailed information for each proposed building
in Phase 1 & 2, respectively. Demands for the residential buildings were based on the B/CS
Unified Design Guidelines information for water demands of 100 gallons/capita/day. To give a
more conservative peak day demand, the day was considered to be 16 hours instead of the
classic 24 hours. Demand for the maintenance building was determined based upon the fixture
unit count method. The peak day demand for the maintenance building is 1.25 gpm with an
average demand of 0.313 gpm. Exhibits 7 & 8 provide a detailed peak and average day
demand per building for the entire project along with meter sizes.
C3 FIRE FLOWS
PHASE 1
Each building will be constructed using Type V-B construction. Referring to Exhibit 7 illustrating
the building sizes, Building 14 is the largest structure at 11,970 SF but is equipped with a fire
sprinkler system. Using Table B105.1 of the International Fire Code 2012 (Exhibit 9) the
required fire flow for a building this size and construction type is 3,000 GPM and when reduced
by 50% equates to a fire flow of 1500 GPM. Since not all structures will have fire suppression
systems, one of the largest of the non-sprinklered buildings should be checked for maximum fire
flow requirements. The largest non-sprinklered building is the 5 bed Duplex Manor which is
3, 776 SF. A fire flow for this building is 1750 GPM, with Building 3 being the most remote.
Capstone Collegiate Community C3 Development -College Station Page 3
-
When modeling this fire flow, the lines in Phase 2 were closed to understand how Phase 1 will
operate before Phase 2 is complete. The required fire flow for Building 14 was split between
Nodes C3-3 and C3-4 during peak day demands. The results for this run can be seen in Exhibit
11 A&B and it shows that the minimum pressure under this fire flow condition occurs at node C3-
3A and is 32.68 psi while the maximum velocities for this scenario occur in Links 4152 and C3-
1000 and are 11 .58 and 11 .20 fps , respectively. These pressures are in compliance with the
required minimum pressure of 20 psi and the maximum velocity of 12fps.
Exhibits 12A&B illustrate the fire flow scenario with Building 3 on fire. In this run a fire flow of
1750 GPM was split between nodes C3-3 and C3-3A. The minimum pressure occurs at Node
C3-3A and is 20.39 psi while the maximum velocities occur in Link 4152 and C3-1000 and are
13 .21 and 12.83 fps, respectively. The pressure values are in compliance with the required
minimum pressure of 20 psi , however since the fire flows are all being fed from the 8-inch
waterline at the Cottages development, the maximum velocities in Lines 4152 and C3-1000
exceed the maximum of 12 fps under peak day fire flow conditions. This occurrence is not a
permanent conditions but rather a temporary one until the Phase 2 lines are constructed. It is
not the intent to request any certificate of occupancy for any building in Phase 1 or 2 until all
underground infrastructure is complete.
Exhibits 13A&B illustrate the fire flow scenario with Building 3 on fire with Phase 2 complete. As
seen on these exhibits, the pressures meet the required minimum pressure of 20 psi as well as
the maximum velocity of 12 fps under peak day fire flow conditions. This run verifies that the
system operates within all code requirements once the Phase 2 waterlines are complete.
PHASE 2
In addition to modeling the fire flows for Phase 1, Phase 2 was also checked for fire flow.
Several fire flow runs were made to check for largest sprinklered building fire flow, largest and
most remote unsprinklered building, most remote building , the clubhouse and gameroom fire
flow operations.
Building 66
In Phase 2, the largest building is Building 66 at 11,970 SF but it is sprinklered. Using Table
B 105.1, the fire flow for this building would be 3000 GPM and with a 50% reduction it will reduce
the fire flow to 1500 GPM. The required fire flow for Building 66 was split between Nodes C3-11
and C3-12 during peak day demands. The results for this run can be seen in Exhibit 14A&B
which shows that the minimum pressure under this fire flow condition occurs at node C3-3A and
is 59.12 psi while the maximum velocity for this scenario occurs in Link C3-1018 and is 8.8 fps.
These values are in compliance with the required minimum pressure of 20 psi and maximum
velocity of 12 fps under peak day fire flow conditions.
Gameroom
In Phase 2, one of the remote buildings is the Gameroom/Poolhouse which is located just south
of the sand volleyball court and swimming pool. The Gameroom is constructed with Type V-B
construction, is 2080 SF and is not sprinklered . Using Table B105.1, the fire flow for this
building would be 1500 GPM. This fire flow was placed on Node C3-11 during peak day
demands. The results for this run can be seen on Exhibits 15A&B which show that the
minimum pressure under this fire flow condition occurs at node C3-3A and is 59.08 psi while the
Capstone Collegiate Community C3 Development -College Station Page 4
-
maximum velocity for this scenario occurs in Link C3-1018 and is 8.83 fps. These values are in
compliance with the required minimum pressure of 20 psi and maximum velocity of 12 fps under
peak day fire flow conditions.
Building 59
One of the remote buildings on a 6-inch loop line is Building 59, located on the northeast corner
of the site close to Holleman Drive. Building 59 is 2712 SF and is not sprinklered. The required
fire flow for Building 59 is 1500 GPM which is split between nodes C3-17 and C3-13. The
results for this run can be seen on Exhibits 16A&B which show that the minimum pressure
under this fire flow condition occurs at node C3-3A and is 59.78 psi while the maximum velocity
for this scenario occurs in Link C3-1018 and is 9.26 fps. These values are in compliance with
the required minimum pressure of 20 psi and maximum velocity of 12 fps under peak day fire
flow conditions.
Building 49 w/ Link C3-1008 as 6-inch line
The largest building that is not sprinklered in Phase 2 is Building 49 at 3776 SF. According the
IFC 2012, the fire flow for this building is 1750 GPM. The required fire flow for Building 49 was
split between Nodes C3-8 and C3-9 during peak day demands. The results for this run can be
seen in Exhibit 17 A&B and it shows that the minimum pressure under this fire flow condition
occurs at node C3-3A and is 56.56 psi while the maximum velocity for this scenario occurs in
Link C3-1008 and is 12.66 fps. The pressure values are in compliance with the required
minimum pressure of 20 psi, however the velocity exceeds the maximum velocity of 12 fps
under peak day fire flow conditions. As a result of this another run was made increasing the line
size for C3-1008 to 8 inches from the 6-inches originally modeled and a new run was
completed.
Building 49 wl Link C3-1008 as 8-inch line
As stated previously, the velocities in Link C3-1008 slightly exceeded the 12 fps threshold . As
seen in Exhibit 18A&B, with this line size increased to 8-inches, the minimum pressure under
this fire flow condition occurs at node C3-3A and is 57 .26 psi while the maximum velocity for this
scenario occurs in Link C3-1008 and is 7.42 fps. The pressure values are in compliance with
the required minimum pressure of 20 psi and now the velocities are also in compliance with the
maximum velocity of 12 fps.
Building 56
Building 56 is located on a 6-inch loop line and it is 3684 SF non-sprinklered building. A such,
the fire flow for this building would be 1750 GPM. This is split between nodes C3-17 and C3-13.
The results for this run can be seen on Exhibits 19A&B which show that the minimum pressure
under this fire flow condition occurs at node C3-3A and is 58.64 psi while the maximum velocity
for this scenario occurs in Link C3-1020 and is 11 .59 fps. These values are in compliance with
the required minimum pressure of 20 psi and maximum velocity of 12 fps under peak day fire
flow conditions .
Capstone Collegiate Community C3 Development -College Station Page 5
-
Building 28
One of the most remote buildings is Building 28 located at the end of a radial 8-inch line. It is
2717 SF and is non-sprinklered. Using Table B105.1 , the fire flow for this building would be
1500 GPM and it is placed all on Node C3-6. The results for this run can be seen on Exhibits
20A&B which show that the minimum pressure under this fire flow condition occurs at node C3-
3A and is 58.32 psi while the maximum velocity for this scenario occurs in Link C3-1018 and is
8.23 fps . These values are in compliance with the required minimum pressure of 20 psi and
maximum velocity of 12 fps under peak day fire flow conditions.
Building 67
Another remote building is Building 67 at 3864 SF and is non-sprinklered. Using Table B105.1 ,
the fire flow for this building would be 1750 GPM. This is split between nodes C3-11 and C3-12.
The results for this run can be seen on Exhibits 21A&B which show that the minimum pressure
under this fire flow condition occurs at node C3-3A and is 57.77 psi while the maximum velocity
for this scenario occurs in Link C3-1018 and is 9.87 fps. These values are in compliance with
the required minimum pressure of 20 psi and maximum velocity of 12 fps under peak day fire
flow conditions.
Clubhouse
In Phase 2, the largest non-residential building is the clubhouse at 8,478 SF and it is
sprinklered. Using Table B105.1, the fire flow for this building would be 5000 GPM and with a
50% reduction it will reduce the fire flow to 2500 GPM. The results for this run can be seen on
Exhibits 22A&B which show that the minimum pressure under this fire flow condition occurs at
node C3-3A and is 54.22 psi. Originally Link C3-1018 was sized as an 8-inch line and when this
Clubhouse fire flow run was made the velocities in this line exceeded the 12 fps. To correct this
situation this line was changed to a 12-inch line. With that upgrade shown in Exhibit 22B, the
velocity in Link C3-1018 has been reduced to 6.04 fps and the highest velocity now occurs in
Link C3-117 at 9.04 fps. These values are in compliance with the required minimum pressure of
20 psi and maximum velocity of 12 fps under peak day fire flow conditions. It is this final
Clubhouse run that contains the correct line sizes for all lines within the C3 development.
SYSTEM UPGRADES
C3 will require infrastructure to be placed as shown on Exhibit 1 & 1A. A combination of an 8-
inch water main along a portion of Junction Boys Road and a 8-inch and 6-inch main line within
the Phase 1 area will be constructed to adequately supply C3 during Average, Peak, and Fire
Flow Demands for the project. In addition, three (3) fire hydrants will be added within Phase 1
of the project to supply adequate fire coverage for all structures. Similarly in Phase 2 there is a
main 8-inch loop to Holleman with a small portion of that line as it approaches Holleman Drive
being a 12-inch line and smaller 6-inch loops off that main line. Nine (9) fire hydrants will be
constructed within Phase 2 to supply adequate fire coverage for all structures.
CONCLUSION
The model results show that the current system along with the C3 water distribution system can
sufficiently serve the domestic and fire flow needs of the Capstone Collegiate Community C3
Phase 1 and 2 Developments.
Capstone Collegiate Community C3 Development -College Station Page 6
ATTACHMENTS
EXHIBIT 1
EXHIBIT 1A
EXHIBIT 2
EXHIBIT 3
EXHIBIT 4A
EXHIBIT 4B
EXHIBIT SA
EXHIBIT SB
EXHIBIT 6
EXHIBIT 7
EXHIBIT 8
EXHIBIT 9
EXHIBIT 10A
EXHIBIT 10B
EXHIBIT 11A
EXHIBIT 11B
EXHIBIT 12A
EXHIBIT 12B
EXHIBIT 13A
EXHIBIT 13B
EXHIBIT 14A
EXHIBIT 14B
EXHIBIT 15A
EXHIBIT 15B
EXHIBIT 16A
EXHIBIT 16B
EXHIBIT 17A
EXHIBIT 17B
EXHIBIT 18A
EXHIBIT 18B
EXHIBIT 19A
Overall Site Layout -Phase 1
Overall Site Layout -Phase 2
MikeURBAN Node Locations
MikeURBAN Link Locations
Average Day Demands on Existing System Node Results
Average Day Demands on Existing System Link Results
Average Day Calibration Run with Fire Flow at 0-137 Node Results
Average Day Calibration Run with Fire Flow at 0-137 Link Results
Hydrant 0 -137 Flow Test
Phase 1 Building Information and Water Demands
Phase 2 Building Information and Water Demands
IFC Fire Flow Table
Peak Day Demands with System Improvements Node Results
Peak Day Demands with System Improvements Link Results
Peak Day Demands Fire Flow -Phase 1 ONLY-Bldg 14 with System
Improvements Node Results
Peak Day Demands Fire Flow -Phase 1 ONLY -Bldg 14 with System
Improvements Link Results
Peak Day Demands Fire Flow -Phase 1 ONLY -Bldg 3 with System
Improvements Node Results
Peak Day Demands Fire Flow -Phase 1 ONLY -Bldg 3 with System
Improvements Link Results
Peak Day Demands Fire Flow -Phase 1 & Phase 2 -Bldg 3 with System
Improvements Node Results
Peak Day Demands Fire Flow -Phase 1 & Phase 2 -Bldg 3 with System
Improvements Link Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 66 with System Improvements
Node Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 66 with System Improvements
Link Results
Peak Day Demands Fire Flow -Phase 2 -Gameroom with System Improvements
Node Results
Peak Day Demands Fire Flow -Phase 2 -Gameroom with System Improvements
Link Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 59 with System Improvements
Node Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 59 with System Improvements
Link Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 49 with System Improvements
Node Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 49 with System Improvements
Link Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 49 with 8-inch Line with System
Improvements Node Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 49 with 8-inch Line with System
Improvements Link Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 56 with System Improvements
Node Results
Capstone Collegiate Community C3 Development -College Station Page 7
EXHIBIT 19B
EXHIBIT 20A
EXHIBIT 20B
EXHIBIT 21A
EXHIBIT 21B
EXHIBIT 22A
EXHIBIT 22B
Peak Day Demands Fire Flow -Phase 2 -Bldg 56 with System Improvements
Link Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 28 with 8-inch Line with System
Improvements Node Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 28 with 8-inch Line with System
Improvements Link Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 67 with System Improvements
Node Results
Peak Day Demands Fire Flow -Phase 2 -Bldg 67 with System Improvements
Link Results
Peak Day Demands Fire Flow -Phase 2 -Clubhouse with System Improvements
Node Results
Peak Day Demands Fire Flow -Phase 2 -Club house with System Improvements
Link Results
Capstone Collegiate Community C3 Development -College Station Page 8
EXHIBIT 2
MikeURBAN Node Identifiers
Description: Select MikeURBAN Node Locations
C3 Development Exhibit 2
EXHIBIT 3
Mike URBAN Link Identifiers
Description: Select MikeURBAN Link Locations
59 8859370
0
CRE0-6,
CRE0-39 CRE0-~0'.--~=;--CRi:'b.38c~llll-l S!ll.,87 59650 __ --,.-er CRE0-41 oCRE~2 ° t>~ o CRE0010.155 CRED-1
CRE0-11CREO.g o 59650A
oCRE0-32 o CflE0-10 "''-tP -"~51
.... 0 :19428 ~().34 "" t§> 0 0 (iE0.35 i.°' CREO.J1o CRE0-12 j9419
0 ~ 59425
,.. 59477
"959476-A :R~-15
~
:;: 59476 "'o ~ ... 14459473 0
• 59441 4176
59445
0
" 0
4135 .... 059432
~ ...
4179 59429 0
59552 0 5951 059569 059553 0
~ 59518 °o
5"'16 o59527
0 '59524
4181 59537 0
C3 Development
CJ-5 •
"' 'l1> § ~ C'\ ..
ll C3.J C3-1021 CJ-4
0
CJ.JA 0
Exhibit 3
EXHIBIT4A
Mike URBAN Node Identifiers
Description: Average Day with Phase 1 & 2 Improvements -NO Fire Flow
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 83.42
59413 1.93 84.70
59414 5.63 86.40
59520 14.72 84.61
C3-1 4.69 82.47
C3-10 2.71 81.92
C3-11 11.88 82.90
C3-12 8.44 83.98
C3-13 0.00 84.55
C3-14 3.33 83.39
C3-15 0.31 83.42
C3-16 5.00 83.84
C3-17 4.17 84.69
C3-2 3.96 81.30
C3-3 2.08 80.30
C3-3A 4.48 79.43
C3-4 6.25 80.61
C3-5 2.60 81.28
C3-6 6.88 84.56
C3-7 4.48 83.39
C3-8 6.25 83.30
C3-9 6.25 82.00
C3 Development Exhibit 4A
EXHIBIT 4B
Mike URBAN Link Identifiers
Description: Average Day with Phase 1 & 2 Improvements -NO Fire Flow
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 315.25 0.89 0.30 130
4116 12 313.32 0.89 0.30 130
4117 12 307.70 0.87 0.29 130
4118 12 -486.89 1.38 0.67 130
4152 8 -73.17 0.47 0.14 130
C3-1000 8 -87.89 0.56 0.16 150
C3-1001 8 -3.61 0.02 0.00 150
C3-1002 8 -7.57 0.05 0.00 150
c3-1003 6 4.48 0.05 0.00 150
C3-1004 6 11.14 0.13 0.01 150
C3-1005 6 8.53 0.10 0.01 150
C3-1006 8 80.43 0.51 0.13 150
C3-1007 8 6.88 0.04 0.00 150
C3-1008 8 9.17 0.06 0.00 150
C3-1009 6 2.92 0.03 0.00 150
C3-1010 6 -3.33 0.04 0.00 150
C3-1011 6 -31.52 0.36 0.09 150
C3-1012 6 -37.56 0.43 0.13 150
C3-1013 6 -19.12 0.22 0.04 150
C3-1014 6 -30.32 0.34 0.09 150
C3-1015 8 100.95 0.64 0.20 150
C3-1016 8 -89.65 0.57 0.16 150
C3-1017 8 -123.30 0.79 0.29 150
C3-1018 12 -171.64 0.49 0.07 150
C3-1019 6 48.03 0.54 0.21 150
C3-1020 6 38.86 0.44 0.14 150
C3-1021 6 -14.13 0.16 0.02 150
C3-1022 6 43 .03 0.49 0.17 150
C3-1023 6 38.86 0.44 0.14 150
C3 Development Exhibit 4B
EXHIBIT SA
Mike URBAN Node Identifiers
Description: Average Day Calibration Run -No System Improvements (lines closed) with Fire
Flow @ Node 59414
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 82.25
59413 1.93 83.40
59414 1305.63 84.98
59520 14.72 83.34
C3-1 4.69 -4042367 .so
C3-10 2.71 -4042368.00
C3-11 11.88 -4042367 .00
C3-12 8.44 -4042366.00
C3-13 0.00 -4042365.50
C3-14 3.33 -4042366.50
C3-15 0.31 -4042366.50
C3-16 5.00 -4042366.25
C3-17 4.17 -4042365.25
C3-2 3.96 -4042368. 75
C3-3 2.08 -4042369. 75
C3-3A 4.48 -4042370.50
C3-4 6.25 -4042369.25
C3-5 2.60 -4042368.75
C3-6 6.88 -4042365.50
C3-7 4.48 -4042366.50
C3-8 6.25 -4042366. 75
C3-9 6.25 -4042368.00
C3 Development Exhibit SA
EXHIBIT SB
MikeURBAN Link Identifiers
Description: Average Day Calibration Run -No System Improvements (lines closed) with Fire
Flow@Node 594 14
Link Results
Name Diameter Flow Velocity Headless Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 827.65 2.35 1.79 130
4116 12 825.72 2.34 1.78 130
4117 12 -479.91 1.36 0.65 130
4118 12 -869.52 2.47 1.96 130
4152 8 56.60 0.36 0.09 130
C3-1000 8 0.00 0.00 0.00 150
C3-1001 8 13.88 0.09 0.00 150
C3-1002 8 9.92 0.06 0.00 150
c3-1003 6 4.48 0.05 0.00 150
C3-1004 6 -5.16 0.06 0.00 150
C3-1005 6 -7 .77 0.09 0.00 150
C3-1006 8 -15.54 0.10 0.00 150
C3-1007 8 6.87 0.04 0.00 150
C3-1008 8 11.16 0.07 0.00 150
C3-1009 6 4.91 0.06 0.00 150
C3-1010 6 -1.34 0.02 0.00 150
C3-1011 6 2.28 0.03 0.00 150
C3-1012 6 -1.78 0.02 0.00 150
C3-1013 6 -6.54 0.07 0.00 150
C3-1014 6 -7.11 0.08 0.00 150
C3-1015 8 6.97 0.04 0.00 150
C3-1016 8 -17.04 0.11 0.00 150
C3-1017 8 -27.48 0.18 0.00 150
C3-1018 12 0.00 0.00 0.00 150
C3-1019 6 14.08 0.16 0.00 150
C3-1020 6 4.92 0.06 0.00 150
C3-1021 6 3.36 0.04 0.00 150
C3-1022 6 9.08 0.10 0.00 150
C3-1023 6 4.92 0.06 0.00 150
C3 Development Exhibit 58
EXHIBIT 6
Hydrant 0-137 Flo w Test
Description: Hydrant 0-137 Flowed at 1300 gpm (Node 59414) and Res idual Pressures Tested
at Hydrant 0-138 (Node 59412)
College Station Utilities
Reliable, Afford,1b/e, Community Owned
Date test completed Monday, March 02, 2015
Time completed 9:30 A.M.
Test completed by Howard Mitchell
Witness Eugene Marshall
FLOW HYDRANT
Location Cottages of College Station
Nozzle size 2.5
Hydrant number 0-137
Pitot reading in PSI 60
Flow in G.P.M. 1300
ST A TIC HYDRANT
Location Holleman Dr. West
Hydrant number 0-138
Static PSI 80
Residual PSI 75
Comments Requested
C3 Development Exhibit 6
EXHIBIT 7
PHASE 1 Building Information
WATER DEMANDS
Building Average Average Peak Water Water Water Fire Line Building Building Type Building Description Gross Area Building Bedroom Water Water Water Fixture Meter Line Size Size (in) Number (SF) Height (FT) Count Demand Demand Demand Units Size (in) per per MEP (gpd) (gpm) (gpm) MEP
1 Foxglove 5 BED DUPLEX MANOR 3684 10 1000 1.042 4.167 44 --
2 Cayenne 5 BED DUPLEX MANOR 3684 10 1000 1.042 4.167 1.5 1.5 44 --
3 Ginger 5 BED DUPLEX MANOR 3776 10 1000 1.042 4.167 44 --
4 Saffron 5 BED DUPLEX MANOR 1.5 1.5 3776 10 1000 1.042 4.167 44 -
5 Chicory 5 BED DUPLEX MANOR 3776 10 1000 1.042 4.167 44 --
6 Ginger 5 BED DUPLEX MANOR 1.5 1.5 3776 10 1000 1.042 4.167 44 --
7 Saffron 5 BED DUPLEX MANOR 3776 10 1000 1.042 4.167 44 --
8 Sassafras 5 BED COTTAGE 1.5 1.5 1,832 5 500 0.521 2.083 22 -
9 Riverbirch 5 BED COTTAGE 1,832 5 500 0.521 2.083 22 -
10 Alder 5 BED COTTAGE 1.5 1.5 1,832 5 500 0.521 2.083 22 -
MAINTENANCE BUILDING 300 0.313 1.250 15 --
11 Indigo 3 Unit 4 BED/ 3 UNIT TOWNHOUSE 5,109 12 1200 1.250 5.000 57 1.5 1.5 4
12 Snapdragon 7 Unit 4 BED/ 7 UNIT TOWNHOUSE 11 ,961 28 2800 2.917 11 .667 133 2 2 4
13 Snapdragon 5 Unit 4 BED I 5 UNIT TOWNHOUSE 8,532 20 2000 2.083 8.333 95 2 2 4
14 Indigo 7 unit 4 BED I 7 UNIT TOWNHOUSE 11 ,970 28 2800 2.917 11 .667 133 2 2 4
15 Cayenne 5 BED DUPLEX MANOR 3,684 10 1000 1.042 4.167 44 1 1 --
16 Chicory 5 BED DUPLEX MANOR 3776 10 1000 1.042 4.167 44 1 1 --
17 Ginger 5 BED DUPLEX MANOR 3776 10 1000 1.042 4.167 44 -
18 Foxglove 5 BED DUPLEX MANOR 3684 10 1000 1.042 4.167 1.5 1.5 44 --
19 Cayenne 5 BED DUPLEX MANOR 3684 10 1000 1.042 4.167 44 --
20 Aspen 5 BED COTTAGE 1832 5 500 0.521 2.083 22 1.5 1.5 --
Exhibit 8
Phase 2 -Water Demands
Building Average Average Peak Water Water Water Fire Line Building Building Type Gross Area Building Bedroom Water Water Water Fixture Meter Line Size Size (in) Node Number (SF) Height (FT) Count Demand Demand Demand Units Size (in) per per MEP (gpd) (gpm) (gpm) MEP
21 Candlebrush 2712 6 600 0.625 2.500 30 C3-7
22 Foxglove 3684 10 1000 1.042 4.167 30 C3-7
23 Alder 1,832 5 500 0.521 2.083 22 C3-6
24 Aspen 1,832 s SOD O.S21 2.083 22 C3-6
2S Sassafras 1,832 s SOD O.S21 2.083 22 C3-6
26 Cypress 1,346 3 300 0.313 l.2SO lS C3-6
27 Sweetbay 2712 6 600 0.62S 2.500 30 C3-6
28 Sweetbay 2712 6 600 0.625 2.SOO 30 C3-6
29 Riverbirch 1,832 s SOD 0.521 2.083 22 C3-6
30 Ironwood 1,346 3 300 0.313 l.2SO lS C3-6
31 Sassafras 1,832 s 500 0.521 2.083 22 C3-6
32 Ironwood 1,346 3 300 0.313 l.2SO lS C3-6
33 Chicory 3776 10 1000 1.042 4.167 44 C3-6
34 Ginger 3776 10 1000 1.042 4.167 44 C3-6
3S Sweet bay 2712 6 600 0.625 2.SOO 30 C3-7
36 Sassafras 1,832 s SOD 0.521 2.083 22 C3-7
37 Sweetbay 2712 6 600 0.62S 2.500 30 C3-7
38 Blackwood 3684 10 1000 1.042 4.167 44 C3-7
39 Cayenne 3684 10 1000 1.042 4.167 44 C3-8
40 Foxglove 3684 10 1000 1.042 4.167 44 C3-8
41 Daffodil 3684 10 1000 1.042 4.167 44 C3-9
42 Cayenne 3684 10 1000 1.042 4.167 44 C3-9
43 Blackwood 3684 10 1000 1.042 4.167 44 C3-10
44 Candlebrush 2712 6 600 0.62S 2.500 30 C3-10
4S Chicory 3776 10 1000 1.042 4.167 44 C3-10
46 Clover 3776 10 1000 1.042 4.167 44 C3-9
47 Saffron 3776 10 1000 1.042 4.167 44 C3-9
48 Ginger 3776 10 1000 1.042 4.167 44 C3-9
49 Saffron 3776 10 1000 1.042 4.167 44 C3-9
so Chicory 3776 10 1000 1.042 4.167 44 C3-8
Sl Clover 3776 10 1000 1.042 4.167 44 C3-8
S2 Ginger 3776 10 1000 1.042 4.167 44 C3-8
S3 Daffodil 3684 10 1000 1.042 4.167 44 C3-8
S4 Riverbirch 1,832 s SOD 0.521 2.083 22 C3-12
SS Riverbirch 1,832 s SOD O.S21 2.083 22 C3-12
S6 Cayenne 3684 10 1000 1.042 4.167 44 C3-12
S7 Riverbirch 1,832 s SOD 0.521 2.083 22 C3-12
S8 Cypress 1,346 3 300 0.313 l.2SO lS C3-17
S9 Sweet bay 2712 6 600 0.625 2.500 30 C3-17
60 Mulberry 1,346 3 300 0.313 l.2SO lS C3-17
61 Snapdragon 7 Un it 11,961 28 2800 2.917 11.667 133 4 C3-17
62 Indigo 7 Unit 11,970 28 2800 2.917 11.667 133 4 C3-16
63 Snapdragon 5 Unit 8,S32 20 2000 2.083 8.333 95 4 C3-16
64 Indigo 7 Unit 11,970 28 2800 2.917 11.667 133 4 C3-12
6S Indigo 3 Unit 5,109 12 1200 l.2SO S.000 57 4 C3-12
66 Indigo 7 Unit 11,970 28 2800 2.917 11.667 133 4 C3-11
67 Cayenne 3684 10 1000 1.042 4.167 44 C3-11
68 Amaryllis 4 Unit 6,812 16 1600 1.667 6.667 76 4 C3-12
69 Indigo 7 Unit 11,970 28 2800 2.917 11.667 133 4 C3-11
70 Snapdragon 7 Unit 11,961 28 2800 2.917 11.667 9S 4 C3-11
71 Snapdragon 5 Unit 8,532 20 2000 2.083 8.333 9S 4 C3-ll
72 Amaryllis 4 Unit 6,812 16 1600 1.667 6.667 76 4 C3-14
73 Amaryllis 4 Unit 6,812 16 1600 1.667 6.667 76 4 C3-14
74 Mulberry 1,346 3 300 0.313 1.250 15 C3-15
Clubhouse C3-12
Gameroom C3-11
APPENDIX B
TABLE 8105.1
MINIMUM REQUIRED FIRE-FLOW AND FLOW DURATION FOR BUILDINGS
FIRE-FLOW CALCULATION AREA (square feet) FIRE-FLOW FLOW DURATION
Type IA and 18' Type llA and lllA' Type IV and V·A' Type llB and 1118' Type v.s• (gallons per minute)" (hours)
0-22 .700 0-12.700 0-8.200 0-5.900 0-3,600 1.500
22,701 -30,200 12. 701-17 ,000 8,201-10,900 5,901-7,900 3,601-4,800 1,750
30.201 -38.700 17.001-21.800 10.901 -12,900 7,901-9,800 4,80 l ·6.200 2,000 2 38,701-48.300 21,801-24,200 12,901-17,400 9,801-12,600 6,201-7,700 2,250
48,301-59,000 24,201-33,200 17,401 -21,300 12.601-15,400 7,701-9,400 2,500
59.001 -70,900 33.201-39.700 21.301 -25,500 15.40I-I8.400 9,40I-I l.300 2,750
70.901-83,700 39,70I-47,IOO 25,50 I-30.100 18. 401-21.800 I 1,301-13.400 3,000
83,701 -97,700 47,101-54,900 30,IOl -35,200 2I,80I-25,900 I3,401-15,600 3,250 3 97.701-112,700 54,901-63.400 35,20 I-40,600 25.901-29,300 I5.60I-18.000 3,500
112.701 -128,700 63,401-72.400 40,601 -46,400 29,30 I-33,500 I8.001-20,600 3,750
128.701 -145,900 72,40I-82,IOO 46,401-52,500 33,501-37,900 20.60I ·23,300 4,000
145.90I -I64.200 82,IOI-92.400 52,501-59.IOO 37.901-42.700 23,301-26,300 4,250
164.201-I83.400 92.40I-103.l00 59,101 -66,000 42.70I-47.700 26,30I-29,300 4.500
183,40I-203.700 I03,101-114,600 66.00I-73,300 47,701-53,000 29,301-32,600 4,750
203,70I -225,200 114.60I-I26.700 73.30l·8I,100 53,001-58,600 32,60I -36,000 5,000
225.20I -247.700 I26,70I-139,400 81.lOI -89,200 58.601-65,400 36,001-39,600 5.250
247.70I-271 ,200 139.401-152,600 89,201 -97.700 65.40I-70.600 39,601-43,400 5,500
271,201 -295,900 152,601-I66.500 97,701-106,500 70,60I-77,000 43,401-47,400 5,750
295,901-Greater 166,50 I-Greater 106,50 l-l I 5,800 77.001-83,700 47,401 -51.500 6.000 4
--115,801-125,500 83. 70I-90,600 5l.50I-55.700 6.250
--125,501 -135,500 90,601-97,900 55,701-60.200 6,500
--135,501-145,800 97.901-I06,800 60,201-64.800 6.750
--145,801-156,700 106,801-113,200 64,801-69.600 7,000
--156,701-167,900 113,201-121,300 69,601-74,600 7,250
--167,90I-I79,400 121,301-129,600 74.601-79.800 7,500
--179,401-191.400 129.601 -138,300 79,801-85,100 7.750
--191, 40 I-Greater 138,30 I-Greater 85, 10 I -Greater 8,000
For SI: I square foot • 0.0929 m2, I gallon per minute • 3.785 L{m, I pound per square inch • 6.895 kPa.
a. Types of construction are based on the fnrematlonal Building Code.
b. Measured at 20 psi residual pressure.
Exhibit 9
446 2012 INTERNATIONAL FIRE CODE•
EXHIBIT lOA
Mike URBAN Node Identifiers
Description: Peak Day with Phase 1 & 2 Improvements -NO Fire Flow
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 69.63
59413 7.72 70.84
59414 22.50 72.48
59520 58.89 70.19
C3-1 18.75 68.07
C3-10 10.83 67.56
C3-11 47.50 68.65
C3-12 33.75 69.77
C3-13 0.00 70.37
C3-14 13.33 69.28
C3-15 1.25 69.46
C3-16 20.00 69.79
C3-17 16.67 70.58
C3-2 15.83 66.90
C3-3 8.33 65.91
C3-3A 17.92 65.04
C3-4 25.00 66.22
C3-5 10.42 66.88
C3-6 27 .50 70.21
C3-7 17.92 69.04
C3-8 25.00 68.95
C3-9 25.00 67.65
C3 Development Exhibit lOA
EXHIBIT lOB
MikeURBAN Link Identifiers
Description: Peak Day with Phase 1 & 2 Improvements -NO Fire Flow
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 648.21 1.84 1.14 130
4116 12 640.49 1.82 1.11 130
4117 12 617.99 1.75 1.04 130
4118 12 -1136.58 3.22 3.21 130
4152 8 -94.49 0.60 0.23 130
(3-1000 8 -153.38 0.98 0.44 150
(3-1001 8 16.28 0.10 0.01 150
(3-1002 8 0.45 0.00 0.00 150
c3-1003 6 17.92 0.20 0.03 150
(3-1004 6 20.42 0.23 0.04 150
(3-1005 6 10.00 0.11 0.01 150
(3-1006 8 178.41 1.14 0.58 150
(3-1007 8 27.50 0.18 0.02 150
(3-1008 6 '37 .3 1 0.42 0.13 150
(3-1009 6 12.31 0.14 0.02 150
(3-1010 6 -12.69 0.14 0.02 150
(3-1011 6 -71.21 0.81 0.43 150
(3-1012 6 -94.73 1.07 0.72 150
C3-1013 6 -56.89 0.65 0.28 150
(3-1014 6 -85.34 0.97 0.60 150
(3-1015 8 261.14 1.67 1.17 150
(3-1016 8 -247.72 1.58 1.06 150
(3-1017 8 -346.39 2.21 1.97 150
(3-1018 8 -488.38 3.12 3.72 150
(3-1019 6 140.74 1.60 1.51 150
(3-1020 6 104.07 1.18 0.86 150
(3-1021 6 -25.80 0.29 0.06 150
(3-1022 6 120.74 1.37 1.13 150
C3-1023 6 104.07 1.18 0.86 150
C3 Development Exhibit lOB
EXHIBIT llA
MikeURBAN Node Identifiers
Description: Peak Day with Fire flow at Building 14 -750gpm at Nodes C3-3 and C3-4
With Lines C3-1018, C3-1 006 & C3-101 1 CLOSED
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 67.30
59413 7.72 68.27
59414 22.50 69.69
59520 58.89 46.31
C3-1 18.75 39.61
C3-10 10.83 -7682901.50
C3-11 47.50 -7682901.50
C3-12 33.75 -7682899.50
C3-13 0.00 -7682899.50
C3-14 13.33 -7682900.00
C3-15 1.25 -7682900.00
C3-16 20.00 -7682899.50
C3-17 16.67 -7682899.50
C3-2 15.83 36.03
C3-3 758.33 33.55
C3-3A 17.92 32.68
C3-4 775.00 33.24
C3-5 10.42 36.12
C3-6 27.50 -7682898.50
C3-7 17.92 -7682900.00
C3-8 25.00 -7682900.00
C3-9 25.00 -7682901.50
C3 Development Exhibit l lA
•
EXHIBIT llB
MikeURBAN Link Identifiers
Description: Peak Day with Fire flow at Building 14 -75 0gpm at Nodes C3-3 and C3-4
With Lines C3 -101 8, C3-1006 & C3-1011 CLOSED
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 12S0.61 3.SS 3.84 130
4116 12 1242.89 3.S3 3.79 130
4117 12 1220.40 3.46 3.67 130
4118 12 -1330.20 3.77 4.30 130
4152 8 1814.31 11.58 SS.OS 130
(3-1000 8 17SS.42 11.20 39.73 lSO
(3-1001 8 1083.53 6.92 16.26 lSO
C3-1002 8 1067.70 6.81 l S.82 lSO
c3-1003 6 17.92 0.20 0.03 lSO
(3-1004 6 -S63.13 6.39 19.64 lSO
(3-1005 6 -S73.SS 6.51 20.32 lSO
(3-1006 8 0.00 0.00 0.00 lSO
(3-1007 8 27.SO 0.18 0.00 lSO
(3-1008 6 8.47 0.10 0.00 lSO
C3-1009 6 -16.S3 0.19 0.00 lSO
(3-1010 6 -41.S3 0.47 0.00 lSO
(3-1011 6 0.00 0.00 0.00 lSO
(3-1012 6 27.22 0.31 4.89 lSO
(3-1013 6 -9.91 0.11 6.07 lSO
(3-1014 6 -10.36 0.12 3.39 lSO
(3-1015 8 -2S.69 0.16 0.00 lSO
(3-1016 8 -24.04 O.lS 0.00 lSO
(3-1017 8 -47.73 0.30 0.00 lSO
(3-1018 8 0.00 0.00 0.00 lSO
(3-1019 6 30.60 0.3S 0.00 lSO
(3-1020 6 -6.07 0.07 19.0S lSO
(3-1021 6 291.4S 3.31 S.80 lSO
(3-1022 6 10.60 0.12 12.SO lSO
(3-1023 6 -6.07 0.07 0.00 lSO
C3 Development Exhibit llB
•
EXHIBIT 12A
Mike URBAN Node Identifiers
Description: Peak Day with Fire flow at Building 3 -875 gpm at Nodes C3-3 and C3-3A
With Lines C3-1018, C3-1006 & C3-1011 CLOSED
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 66.81
59413 7.72 67.75
59414 22.50 69.15
59520 58.89 40.33
C3-1 18.75 32.33
C3-10 10.83 -7682911.00
C3-11 47.50 -7682910.00
C3-12 33.75 -7682909.00
C3-13 0.00 -7682908.50
C3-14 13.33 -7682909.50
C3-15 1.25 -7682909.50
C3-16 20.00 -7682909.00
C3-17 16.67 -7682908.00
C3-2 15.83 27.56
C3-3 888.33 24.35
C3-3A 892.92 20.39
C3-4 25.00 26.05
C3-5 10.42 28.89
C3-6 27.50 -7682908.00
C3-7 17.92 -7682909.50
C3-8 25.00 -7682909.50
C3-9 25.00 -7682911.00
C3 Development Exhibit 12A
-EXHIBIT 12B
Mike URBAN Link Identifiers
Description: Peak Day with Fire flow at Building 3 -875 gpm at Nodes C3-3 and C3-3A
With Lines C3-1018, C3-1006 & C3-1011 CLOSED
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 1312.95 3.72 4.20 130
4116 12 1305.23 3.70 4.15 130
4117 12 1282.73 3.64 4.02 130
4118 12 -1392.54 3.95 4.68 130
4152 8 2069.31 13.21 70.24 130
C3-1000 8 2010.42 12.83 51.08 150
C3-1001 8 1344.79 8.58 24.26 150
C3-1002 8 1328.96 8.48 23.73 150
c3-1003 6 892.92 10.13 46.13 150
C3-1004 6 -556.88 6.32 19.24 150
C3-1005 6 -567.30 6.44 19.92 150
C3-1006 8 0.00 0.00 0.00 150
C3-1007 8 27.50 0.18 0.00 150
C3-1008 6 8.47 0.10 0.00 150
C3-1009 6 -16.53 0.19 0.00 150
C3-1010 6 -41.53 0.47 0.00 150
C3-1011 6 0.00 0.00 0.00 150
C3-1012 6 27.22 0.31 0.00 150
C3-1013 6 -9.91 0.11 0.00 150
C3-1014 6 -10.36 0.12 0.00 150
C3-1015 8 -25 .69 0.16 0.00 150
C3-1016 8 -24.04 0.15 0.00 150
C3-1017 8 -47.73 0.30 0.00 150
C3-1018 8 0.00 0.00 0.00 150
c3-1019 6 30.60 0.35 0.00 150
C3-1020 6 -6.07 0.07 0.00 150
C3-1021 6 -452.29 5.13 13.09 150
c3-1022 6 10.60 0 .1 2 0.00 150
c3-1023 6 -6.07 0 .07 0.00 150
C3 Development Exhibit 12B
-EXHIBIT 13A
MikeURBAN Node Identifiers
Description: Peak Day with Fire flow at Building 3 -875 gpm at Nodes C3-3 and C3 -3A
With Lines C3-1018, C3-1006 & C3 -1011 OPEN
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 65.74
59413 7.72 67.01
59414 22.50 68.71
59520 58.89 62.09
C3-1 18.75 59.11
C3-10 10.83 59.01
C3-11 47.50 61.56
C3-12 33.75 62.92
C3-13 0.00 63.83
C3-14 13.33 63.19
C3-15 1.25 64.51
C3-16 20.00 64.34
C3-17 16.67 64.63
C3-2 15.83 55.42
C3-3 888.33 52.87
C3-3A 892.92 48.91
C3-4 25.00 56.19
C3-5 10.42 57.37
C3-6 27.50 61.92
C3-7 17.92 60.75
C3-8 25.00 60.65
C3-9 25.00 59.12
C3 Development Exhibit 13A
-EXHIBIT 13B
MikeURBAN Link Identifiers
Description: Peak Day with Fire fl ow at Building 3 - 875 gpm at Nodes C3 -3 and C3-3A
With Lines C3 -1018, C3-1006 & C3 -1011 OPEN
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 383.19 1.09 0.43 130
4116 12 375.47 1.07 0.41 130
4117 12 352.97 1.00 0.37 130
4118 12 -1776.89 5.04 7.35 130
4152 8 755.18 4.82 10.86 130
C3-1000 8 696.29 4.44 7.17 150
C3-1001 8 1111.03 7.09 17.03 150
C3-1002 8 1095.20 6.99 16.58 150
c3-1003 6 892.92 10.13 46.13 150
C3-1004 6 -253.88 2.88 4.49 150
C3-1005 6 -264.30 3.00 4.84 150
C3-1006 8 697.79 4.45 7.20 150
C3-1007 8 27.50 0.18 0.02 150
C3-1008 6 149.40 1.70 1.68 150
C3-1009 6 124.40 1.41 1.20 150
C3-1010 6 99.40 1.13 0.79 150
C3-1011 6 -457.17 5.19 13.35 150
C3-1012 6 -368.60 4.18 8.96 150
C3-1013 6 -161.70 1.83 1.95 150
C3-1014 6 -254.40 2.89 4.51 150
C3-1015 8 892.61 5.70 11.35 150
C3-1016 8 -750.40 4.79 8.23 150
C3-1017 8 -1018.13 6.50 14.49 150
C3-1018 8 -1393.71 8.90 25.92 150
c3-1019 6 374.33 4.25 9.22 150
C3-1020 6 337.66 3.83 7.62 150
C3-1021 6 -686.05 7.78 28.32 150
c3-1022 6 354.33 4.02 8.33 150
c3-1023 6 337.66 3.83 7.62 150
C3 Development Exhibit 13B
-
EXHIBIT 14A
MikeURBAN Node Identifiers
Description: Peak Day Demand with Fire fl ow at Building 66 -75 0 gpm at Nodes C3-11 and
C3 -1 2
Node Results
Name Demand Pressure
(gpm) (psi)
59385 0.00 68.82
59412 0.00 66.29
59413 7.72 67.57
59414 22.50 69.27
59520 58.89 64.77
59522 0.00 62.54
C3-1 18.75 62 .23
C3-10 10.83 61.36
C3-11 797.50 61.74
C3-12 783.75 63.61
C3-13 0.00 64.50
C3-14 13.33 63 .77
C3-15 1.25 65.08
C3-16 20.00 64.95
C3-17 16.67 65.27
C3-2 15.83 61.01
C3-3 8.33 59.99
C3-3A 17.92 59.12
C3-4 25 .00 60.23
C3-5 10.42 60.96
C3-6 27.50 64.22
C3-7 17.92 63.05
C3-8 25 .00 62.95
C3-9 25 .00 61.46
C3 Development Exhibit 14A
-EXHIBIT 14B
MikeURBAN Link Identifiers
Description: Peak Day Demand with Fire flow at Building 66 -750 gpm at Nodes C3-l 1 and
C3-12
Link Results
Diameter Flow Velocity Head loss Roughness Name (in) (gpm) (ft/s) /1000 (ft) (millift)
4084 12 295.58 0.84 0.27 130
4115 12 325.80 0.92 0.32 130
4116 12 318.08 0.90 0.30 130
4117 12 295.58 0.84 0.27 130
4118 12 -1704.53 4.84 6.81 130
4152 8 515.16 3.29 5.35 130
4154 6 -5.83 0.07 0.01 130
4191 8 -13.05 0.08 0.01 130
4192 4 -7.22 0.18 0.06 130
(3-1000 8 456.27 2.91 3.28 150
(3-1001 8 127.49 0.81 0.31 150
(3-1002 8 111.66 0.71 0.24 150
c3-1003 6 17.92 0.20 0.03 150
(3-1004 6 -79.17 0.90 0.52 150
(3-1005 6 -89.59 1.02 0.65 150
(3-1006 8 -220.44 1.41 0.85 150
(3-1007 8 27.50 0.18 0.02 150
(3-1008 6 135.30 1.54 1.40 150
(3-1009 6 110.30 1.25 0.96 150
(3-1010 6 85.30 0.97 0.60 150
(3-1011 6 139.58 1.58 1.48 150
C3-1012 6 214.05 2.43 3.28 150
(3-1013 6 -284.02 3.22 5.53 150
C3-1014 6 -299.43 3.40 6.10 150
(3-1015 8 -39.72 0.25 0.04 150
(3-1016 8 -700.54 4.47 7.25 150
(3-1017 8 -1013.31 6.47 14.3 6 150
(3-1018 8 -1378.73 8.80 25.40 150
c3-1019 6 364.17 4.13 8.76 150
(3-1020 6 327.50 3.72 7.20 150
(3-1021 6 85.41 0.97 0.60 150
c3-1022 6 344.17 3.91 7.89 150
c3-1023 6 327.50 3.72 7.20 150
C3 Development Exhibit 14B
•
EXHIBIT 15A
Mike URBAN Node Identifiers
Description: Peak Day Demand with Fire flow at Gameroom -1500 gpm at Node C3-11
Node Results
Name Demand Pressure
(gpm) (psi)
59385 0.00 68.82
59412 0.00 66.29
59413 7.72 67.56
59414 22.50 69.27
59520 58.89 64.80
59522 0.00 62 .57
C3-1 18.75 62 .27
C3-10 10.83 60.84
C3-11 1547.50 59 .47
(3-12 33.75 63.82
(3-13 0.00 64.68
C3-14 13.33 63 .70
C3-15 1.25 65.07
C3-16 20.00 65 .00
C3-17 16.67 65 .38
C3-2 15.83 61.00
C3-3 8.33 59.95
C3-3A 17.92 59.08
C3-4 25.00 60.07
C3-5 10.42 60.90
C3-6 27.50 64.33
C3-7 17.92 63.16
C3-8 25.00 63.02
C3-9 25.00 61.00
C3 Development Exhi bit l SA
•
EXHIBIT 15B
MikeURBAN Link Identifiers
Description: Peak Day Demand with Fire flow at Gameroom -1500 gpm at Node C3-1 1
Link Results
Name Diameter Flow Velocity Head loss Roughnes
(in) (gpm) (ft/s) /lOOO(ft) s (millift)
4084 12 291.84 0.83 0.26 130
4115 12 322.06 0.91 0.31 130
4116 12 314.34 0.89 0.30 130
4117 12 291.84 0.83 0.26 130
4118 12 -1705.30 4.84 6.81 130
4152 8 510.65 3.26 5.26 130
4154 6 -5.83 0.07 0.01 130
4191 8 -13.05 0.08 0.01 130
4192 4 -7.22 0.18 0.06 130
C3-1000 8 451.76 2.88 3.22 150
C3-1001 8 192.23 1.23 0.66 150
C3-1002 8 176.40 1.13 0.56 150
c3-1003 6 17.92 0.20 0.03 150
C3-1004 6 -133.66 1.52 1.37 150
C3-1005 6 -144.08 1.63 1.57 150
(3-1006 8 -96.70 0.62 0.19 150
C3-1007 8 27.50 0.18 0.02 150
C3-1008 6 255.48 2.90 4.55 150
C3-1009 6 230.48 2.62 3.76 150
C3-1010 6 205.48 2.33 3.04 150
C3-1011 6 258.81 2.94 4.66 150
C3-1012 6 453.46 5.15 13.15 150
C3-1013 6 -612.62 6.95 22.96 150
C3-1014 6 -481.42 5.46 14.69 150
C3-1015 8 204.20 1.30 0.74 150
C3-1016 8 -543.75 3.47 4.53 150
C3-1017 8 -1038.50 6.63 15.03 150
C3-1018 8 -1383.24 8.83 25.56 150
c3-1019 6 343.49 3.90 7.86 150
C3-1020 6 306.82 3.48 6.38 150
C3-1021 6 150.15 1.70 1.70 150
c3-1022 6 323.49 3.67 7.04 150
c3-1023 6 306.82 3.48 6.38 150
C3 Development Exhibit lSB
EXHIBIT 16A
Mike URBAN Node Identifiers
Description: Peak Day Demand with Fire flow at Building 59 -750 gpm at Nodes C3-17 &
C3-13
Node Results
Name Demand Pressure
(gpm} (psi}
59412 0.00 66.26
59413 7.72 67.54
59414 22.50 69.26
59520 58.89 65.28
C3-1 18.75 62.84
C3-10 10.83 62.21
C3-11 47.50 63.16
C3-12 33.75 64.13
C3-13 750.00 62.69
C3-14 13.33 64.12
C3-15 1.25 64.93
C3-16 20.00 63.62
C3-17 766.67 62.72
C3-2 15.83 61.65
C3-3 8.33 60.65
C3-3A 17.92 59.78
C3-4 25.00 60.94
C3-5 10.42 61.62
C3-6 27.50 64.82
C3-7 17.92 63.66
C3-8 25.00 63.57
C3-9 25.00 62.29
C3 Development Exhibit 16A
EXHIBIT 16B
MikeURBAN Link Identifiers
Description: Peak Day Demand with Fire flow at Building 59 -750 gpm at Nodes C3 -17 &
C3-13
Link Results
Diameter Flow Velocity Head loss Roughness Name (in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 265.83 0.75 0.22 130
4116 12 258.11 0.73 0.21 130
4117 12 235.61 0.67 0.17 130
4118 12 -1716.19 4.87 6.89 130
4152 8 443.53 2.83 4.05 130
C3-1000 8 384.64 2.46 2.39 150
C3-1001 8 81.54 0.52 0.13 150
C3-1002 8 65.71 0.42 0.09 150
c3-1003 6 17.92 0.20 0.03 150
C3-1004 6 -41.05 0.47 0.15 150
C3-1005 6 -51.47 0.58 0.23 150
C3-1006 8 -232.88 1.49 0.94 150
C3-1007 8 27.50 0.18 0.02 150
C3-1008 6 -4.52 0.05 0.00 150
C3-1009 6 -29.52 0.33 0.08 150
C3-1010 6 -54.52 0.62 0.26 150
C3-1011 6 55.51 0.63 0.27 150
C3-1012 6 -9.84 0.11 0.01 150
C3-1013 6 101.18 1.15 0.82 150
C3-1014 6 -158.52 1.80 1.88 150
C3-1015 8 -191.98 1.23 0.66 150
C3-1016 8 -610.28 3.90 5.61 150
C3-1017 8 -782.13 4.99 8.89 150
C3-1018 8 -1450.36 9.26 27.90 150
C3-1019 6 666.98 7.57 26.88 150
C3-1020 6 -869.69 9.87 43.94 150
C3-1021 6 39.46 0.45 0.14 150
C3-1022 6 646.98 7.34 25.40 150
C3-1023 6 -119.69 1.36 1.12 150
C3 Development Exhibit 16B
EXHIBIT 17A
Mike URBAN Node Identifiers
Description: Peak Day Demand with Fire flow at Building 49 -875 gpm at Nodes C3-9 &
C3-8
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 65.73
59413 7.72 67.00
59414 22.50 68.71
59520 58.89 62.63
C3-1 18.75 59.76
C3-10 10.83 58.24
C3-11 47.50 61.22
(3-12 33.75 62.69
C3-13 0.00 63.62
C3-14 13.33 63.00
C3-15 1.25 64.41
C3-16 20.00 64.22
C3-17 16.67 64.47
C3-2 15.83 58.48
C3-3 8.33 57.43
C3-3A 17.92 56.56
C3-4 25.00 57.53
C3-5 10.42 58.37
C3-6 27.50 61.71
C3-7 17.92 60.54
C3-8 900.00 59.62
C3-9 900.00 57.68
C3 Development Exhibit 17A
EXHIBIT 17B
Mike URBAN Link Identifiers
Description: Peak Day Demand with Fire flow at Building 49 -875 gpm at Nodes C3-9 &
C3-8
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /lOOO(ft) (millift)
4115 12 342.16 0.97 0.35 130
4116 12 334.44 0.95 0.33 130
4117 12 311.94 0.88 0.29 130
4118 12 -1784.04 5.06 7.40 130
4152 8 702.01 4.48 9.49 130
(3-1000 8 643.12 4.10 6.19 150
(3-1001 8 200.97 1.28 0.72 150
(3-1002 8 185.14 1.18 0.62 150
c3-1003 6 17.92 0.20 0.03 150
(3-1004 6 -141.05 1.60 1.51 150
(3-1005 6 -151.47 1.72 1.73 150
C3-1006 8 -271.93 1.74 1.26 150
(3-1007 8 27.50 0.18 0.02 150
(3-1008 6 1115.84 12.66 69.71 150
(3-1009 6 215.84 2.45 3.33 150
(3-1010 6 -684.16 7.76 28.17 150
(3-1011 6 274.94 3.12 5.21 150
(3-1012 6 -420.05 4.77 11.42 150
(3-1013 6 -195.05 2.21 2.76 150
(3-1014 6 -272.51 3.09 5.12 150
(3-1015 8 889.33 5.68 11.28 150
(3-1016 8 -769.27 4.91 8.62 150
(3-1017 8 -1055.10 6.73 15.48 150
C3-1018 8 -1441.88 9.20 27.60 150
(3-1019 6 385.53 4.37 9.74 150
(3-1020 6 348.86 3.96 8.09 150
(3-1021 6 158.89 1.80 1.89 150
(3-1022 6 365.53 4.15 8.82 150
(3-1023 6 348.86 3.96 8.09 150
C3 Development Exhibit 17B
EXHIBIT 18A
Mike URBAN Node Identifiers
Description: Peak Day with Fire flow at Building 49 -875gpm at Nodes C3-9 & C3-8
Line C3-1008 as 8-inch L ine
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 65.70
59413 7.72 66.98
59414 22.50 68.69
59520 58.89 63.18
C3-1 18.75 60.43
C3-10 10.83 59.17
C3-ll 47.50 62.14
C3-12 33.75 63.58
C3-13 0.00 64.55
C3-14 13.33 63.98
C3-15 1.25 65.50
C3-16 20.00 65.25
C3-17 16.67 65.46
C3-2 15.83 59.17
C3-3 8.33 58.13
C3-3A 17.92 57.26
C3-4 25.00 58.29
C3-5 10.42 59.09
C3-6 27.50 62.39
C3-7 17.92 61.22
C3-8 900.00 60.91
C3-9 900.00 58.69
C3 Development Exhibit 18A
EXHIBIT 18B
Mike URBAN Link Identifiers
Description: Peak Day with Fire flow at Building 49 -875gpm at Nodes C3-9 & C3-8
Line C3-l 008 as 8-inch Line
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 292.06 0.83 0.26 130
4116 12 284.34 0.81 0.25 130
4117 12 261.84 0.74 0.21 130
4118 12 -1793.87 5.09 7.48 130
4152 8 642.07 4.10 8.04 130
C3-1000 8 583.18 3.72 5.16 150
C3-1001 8 176.11 1.12 0.56 150
C3-1002 8 160.28 1.02 0.47 150
c3-1003 6 17.92 0.20 0.03 150
C3-1004 6 -120.06 1.36 1.12 150
C3-1005 6 -130.48 1.48 1.31 150
C3-1006 8 -257.85 1.65 1.14 150
C3-1007 8 27.50 0.18 0.02 150
C3-1008 8 1163.04 7.42 18.54 150
C3-1009 6 263.04 2.98 4.80 150
C3-1010 6 -636.96 7.23 24.68 150
C3-1011 6 229.08 2.60 3.71 150
C3-1012 6 -418.71 4.75 11.35 150
C3-1013 6 -187.41 2.13 2.56 150
C3-1014 6 -278.79 3.16 5.34 150
C3-1015 8 950.61 6.07 12.76 150
C3-1016 8 -806.81 5.15 9.42 150
C3-1017 8 -1098.94 7.01 16.69 150
C3-1018 12 -1501.82 4.26 4.13 150
C3-1019 6 401.63 4.56 10.51 150
C3-1020 6 364.96 4.14 8.80 150
C3-1021 6 134.03 1.52 1.38 150
C3-1022 6 381.63 4.33 9.56 150
C3-1023 6 364.96 4.14 8.80 150
C3 Development Exhibit 188
EXHIBIT 19A
Mike URBAN Node Identifiers
Description: Peak Day Demand with Fire flow at Building 56 -875 gpm at Nodes C3-13 &
C3-17
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 65.64
59413 7.72 66.93
59414 22.50 68.66
59520 58.89 64.24
C3-1 18.75 61.71
C3-10 10.83 61.03
C3-11 47.50 61.99
C3-12 33.75 62.89
C3-13 875.00 60.76
C3-14 13.33 63.01
C3-15 1.25 63.99
C3-16 20.00 62.17
C3-17 891.67 60.75
C3-2 15.83 60.51
C3-3 8.33 59.50
C3-3A 17.92 58.64
C3-4 25.00 59.78
C3-5 10.42 60.48
C3-6 27.50 63.65
C3-7 17.92 62.48
C3-8 25.00 62.39
C3-9 25.00 61.11
C3 Development Exhibit 19A
EXHIBIT 19B
MikeURBAN Link Identifiers
Description: Peak Day Demand with Fire flow at Building 56 -875 gpm at Nodes C3-13 &
C3-17
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) {ft/s) /1000 {ft) (millift)
4115 12 181.02 0.51 0.11 130
4116 12 173.30 0.49 0.10 130
4117 12 150.80 0.43 0.08 130
4118 12 -1811.88 5.14 7.62 130
4152 8 513.03 3.27 5.31 130
C3-1000 8 454.14 2.90 3.25 150
C3-1001 8 91.56 0.58 0.17 150
C3-1002 8 75.73 0.48 0.12 150
c3-1003 6 17.92 0.20 0.03 150
C3-1004 6 -49.26 0.56 0.22 150
C3-1005 6 -59.68 0.68 0.31 150
C3-1006 8 -284.15 1.81 1.36 150
C3-1007 8 27.50 0.18 0.02 150
C3-1008 6 -9.45 0.11 0.01 150
C3-1009 6 -34.45 0.39 0.11 150
C3-1010 6 -59.45 0.67 0.31 150
C3-1011 6 73.75 0.84 0.46 150
C3-1012 6 3.47 0.04 0.00 150
C3-1013 6 126.86 1.44 1.24 150
C3-1014 6 -170.90 1.94 2.16 150
C3-1015 8 -248.18 1.58 1.06 150
C3-1016 8 -680.01 4.34 6.86 150
C3-1017 8 -864.23 5.52 10.70 150
C3-1018 8 -1630.86 10.41 34.67 150
C3-1019 6 765.38 8.68 34.68 150
C3-1020 6 -1021.29 11.59 59.17 150
C3-1021 6 49.48 0.56 0.22 150
C3-1022 6 745.38 8.46 33.02 150
C3-1023 6 -146.29 1.66 1.62 150
C3 Development Exhibit 19B
EXHIBIT20A
MikeURBAN Node Identifiers
Description: Peak Day Demand with Fire flow at Building 28 -l 500gpm at Node C3-6
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 66.34
59413 7.72 67.60
59414 22.50 69.30
59520 58.89 64.05
C3-1 18.75 61.36
C3-10 10.83 60.86
C3-11 47.50 62.76
C3-12 33 .75 63.96
C3-13 0.00 64.82
C3-14 13.33 64.13
C3-15 1.25 65.27
C3-16 20.00 65.18
C3-17 16.67 65.54
C3-2 15.83 60.19
C3-3 8.33 59.19
C3-3A 17.92 58.32
C3-4 25.00 59.50
C3-5 10.42 60.17
C3-6 1527.50 59.16
C3-7 17.92 61.84
C3-8 25.00 61.77
C3-9 25.00 60.88
C3 Development Exhibit 20A
EXHIBIT 20B
MikeURBAN Link Identifiers
Description: Peak Day Demand with Fire flo w at Building 28 -1500gpm at Node C3-6
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /lOOO(ft) (millift)
4084 12 368.20 1.04 0.40 130
4115 12 398.42 1.13 0.46 130
4116 12 390.70 1.11 0.44 130
4117 12 368.20 1.04 0.40 130
4118 12 -1688.36 4.79 6.69 130
4152 8 603.95 3.85 7.18 130
4154 6 -5.83 0.07 0.00 130
4191 8 -13.05 0 .08 0.01 130
4192 4 -7.22 0 .18 0.06 130
(3-1000 8 545.06 3.48 4.55 150
(3-1001 8 15.09 0 .10 0.01 150
(3-1002 8 -0.74 0 .00 0.00 150
c3-1003 6 17.92 0 .20 0.03 150
(3-1004 6 21.36 0 .24 0.05 150
(3-1005 6 10.94 0.12 0.01 150
(3-1006 8 -522.16 3.33 4.21 150
(3-1007 8 1527.50 9.75 30.71 150
(3-1008 6 -144.31 1.64 1.58 150
(3-1009 6 -169.31 1.92 2.12 150
(3-1010 6 -194.31 2.20 2.74 150
(3-1011 6 -73.35 0.83 0.45 150
(3-1012 6 -278.50 3.16 5.33 150
(3-1013 6 -103.61 1.18 0.85 150
(3-1014 6 -222.39 2.52 3.52 150
C3-1015 8 878.94 5.61 11.03 150
C3-1016 8 -703.69 4.49 7.31 150
C3-1017 8 -939.41 6.00 12.48 150
C3-1018 8 -1289.94 8.23 22.46 150
C3-1019 6 349.28 3.96 8.11 150
(3-1020 6 312.61 3.55 6.60 150
C3-1021 6 -26.99 0.31 0.07 150
C3-1022 6 329.28 3.74 7.27 150
C3-1023 6 312.61 3.55 6.60 150
C3 Development Exhibit 208
EXHIBIT 21A
Mike URBAN Node Identifiers
Description: Peak Day Demand with Fire flow at Building 67 -875 gpm at Nodes C3-l l &
C3 -1 2
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 65.68
59413 7.72 66.96
59414 22.50 68 .68
59520 58.89 63 .57
C3-1 18.75 60.89
C3-10 10.83 59.93
C3-11 922.50 60.10
C3-12 908.75 62.21
C3-13 0.00 63.18
C3-14 13.33 62.55
C3-15 1.25 64.18
C3-16 20.00 63.92
C3-17 16.67 64.11
C3-2 15.83 59.66
C3-3 8.33 58.64
C3-3A 17.92 57.77
C3-4 25.00 58.86
C3-5 10.42 59.61
C3-6 27.50 62.83
C3-7 17.92 61.67
C3-8 25 .00 61.56
C3-9 25 .00 60.03
C3 Development Exhibit 21A
EXHIBIT 21B
MikeURBAN Link Identifiers
Description: Peak Day Demand with Fire flow at Building 67 -875 gpm at Nodes C3-11 &
C3-12
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 254.64 0.72 0.20 130
4116 12 246.92 0.70 0.19 130
4117 12 224.42 0.64 0.16 130
4118 12 -1800.53 5.11 7.53 130
4152 8 597.99 3.82 7.05 130
C3-1000 8 539.10 3.44 4.46 150
C3-1001 8 141.34 0.90 0.37 150
C3-1002 8 125.51 0.80 0.30 150
c3-1003 6 17.92 0.20 0.03 150
C3-1004 6 -90.79 1.03 0.67 150
C3-1005 6 -101.21 1.15 0.82 150
C3-1006 8 -277.81 1.77 1.31 150
C3-1007 8 27.50 0.18 0.02 150
C3-1008 6 148.61 1.69 1.67 150
C3-1009 6 123.61 1.40 1.18 150
C3-1010 6 98.61 1.12 0.78 150
C3-1011 6 165.05 1.87 2.02 150
(3-1012 6 252.82 2.87 4.46 150
C3-1013 6 -328.67 3.73 7.25 150
C3-1014 6 -341.00 3.87 7.76 150
C3-1015 8 -83.78 0.53 0.14 150
C3-1016 8 -784.42 5.01 8.94 150
C3-1017 8 -1138.75 7.27 17.83 150
C3-1018 8 -1545.90 9.87 31.40 150
C3-1019 6 405.90 4.61 10.71 150
C3-1020 6 369.23 4.19 8.99 150
C3-1021 6 99 .26 1.13 0.79 150
C3-1022 6 385.90 4.38 9.76 150
C3-1023 6 369.23 4.19 8.99 150
C3 Development Exhibit 218
'
EXHIBIT 22A
Mike URBAN Node Identifiers
Description: Peak Day with Fire flow at Clubhouse -1250 gpm at Nodes C3-12 & C3-8
Node Results
Name Demand Pressure
(gpm) (psi)
59412 0.00 63 .75
59413 7.72 65.05
59414 22.50 66.78
59520 58.89 60.29
C3-1 18.75 57.28
C3-10 10.83 56.65
C3-11 47.50 58.03
C3-12 1283.75 58.97
C3-13 0.00 60.34
C3-14 13.33 60.47
C3-15 1.25 63 .37
C3-16 20.00 62.50
C3-17 16.67 62.05
C3-2 15.83 56.09
C3-3 8.33 55.09
C3-3A 17.92 54.22
C3-4 25.00 55.38
C3-5 10.42 56.07
C3-6 27.50 58.88
C3-7 17.92 57.71
C3-8 1275.00 57.43
C3-9 25.00 56.66
C3 Development Exhibit 22A
-
EXHIBIT 22B
Mike URBAN Link Identifiers
Description: Peak Day with Fire fl ow at Clubhouse -125 0 gpm at Nodes C3-12 & C3-8
Link Results
Name Diameter Flow Velocity Head loss Roughness
(in) (gpm) (ft/s) /1000 (ft) (millift)
4115 12 -44.18 0.13 0.01 130
4116 12 -51.90 0.15 0.01 130
4117 12 -74.40 0.21 0.02 130
4118 12 -2085.67 5.92 9.89 130
4152 8 764.03 4.88 11.10 130
C3-1000 8 705.14 4.50 7.34 150
C3-1001 8 79.55 0.51 0.13 150
C3-1002 8 63.72 0.41 0.09 150
c3-1003 6 17.92 0.20 0.03 150
C3-1004 6 -39.44 0.45 0.14 150
C3-1005 6 -49.86 0.57 0.22 150
C3-1006 8 -556.98 3.56 4.74 150
C3-1007 8 27.50 0.18 0.02 150
C3-1008 8 1079.60 6.89 16.15 150
C3-1009 6 -195.40 2.22 2.77 150
C3-1010 6 -220.40 2.50 3.46 150
C3-1011 6 51.91 0.59 0.24 150
C3-1012 6 -179.32 2.03 2.36 150
C3-1013 6 112.23 1.27 0.99 150
C3-1014 6 -339.05 3.85 7.68 150
C3-1015 8 568.04 3.63 4.92 150
C3-1016 8 -1205.04 7.69 19.80 150
C3-1017 8 -1557.42 9.94 31.83 150
C3-1018 12 -2129.86 6.04 7.89 150
C3-1019 6 571.19 6.48 20.17 150
C3-1020 6 534.52 6.07 17.84 150
C3-1021 6 37.47 0.43 0.13 150
C3-1022 6 551.19 6.25 18.88 150
C3-1023 6 534.52 6.07 17.84 150
C3 Development Exhibit 228