MEMORANDUM
May 2, 2005
TO: Sahara Realty Group, Ltd, Via fax 822.1763
FROM: Bridgette George, Development Coordinator
SUBJECT: HENTON-LINCOLN LOTS 3R & 4R(FP-REPLAT) - Final Plat
Staff reviewed the above-mentioned final plat as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments
have been addressed and the following information submitted by Thursday, December
15, 10:00 a.m., your project will be placed on the next available Planning and Zoning
Commission meeting scheduled for, Thursday, January 6, 2005, in the City Hall Council
Chambers, 1101 Texas Avenue.
Ten (10) 11" x 17" copies of the revised final plat;
Two (2) 24" x 36" copies of the revised final plat;
One (1) Mylar original of the revised final plat; and
One (1) copy of the digital file of the final plat on diskette or e-mail to
nmanhart@ci.college-station.tx.us
Upon receipt of the required documents for the Planning & Zoning meeting, your project
will be considered formally filed with the City of College Station. Please note that if all
comments have not been addressed your project will not be scheduled for a Planning &
Zoning Commission meeting. Your project may be placed on a future agenda once all
the revisions have been made and the appropriate fees paid. If you have any questions
or need additional information, please call Carol Cotter or myself at 764-3570.
Attachments: Staff review comments
cc: David Scarmardo, Via fax 822.1763
Stewart Kling, Kling Engineering & Surveying, Via fax 846.8252
Case file#04-00500269
Home of Texas A&M University
STAFF REVIEW COMMENTS NO. 2
Project: HENTON-LINCOLN LOTS 3R & 4R (FP-REPLAT) - 04-00500269
Planning
1. The Replat does not match the utility layout (page C4.1 of construction documents). There
are numerous locations where this does not match. Please revise and resubmit.
Reviewed by: Jennifer Reeves Date: 04-27-05
ELECTRICAL
1. Developer installs conduit per city specs and design
2. Developer provides concrete transformer pad(s) per city specs and design.
3. Developer installs pull boxes as per city specs and design.(pull boxes provided by
the city).
4. Preliminary plan has been provided to developer for electric system design, showing
locations of proposed conduit routes, transformer pads and pull boxes.
5. Developer provides easements for electric infrastructure as installed. Temporary
Blanket easement will be required for construction purposes. Once complete
developer provides as build descriptive easement to have temporary blanket
easement released.
7. All easement as shown on plat cover existing electric infrastructure on site.
To discuss any of the above electrical comments, please contact Tony Michalsky at
979.764.3438.
Reviewed by: Tony Michalsky Date: 4-28-05
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review. 2 of 2
TRANSMISSION VERIFICATION REPORT
TIME : 05/02/2005 09:43
NAME : COGS DEVELOPMENT SER
FAX : 9797643496
TEL : 9797643570
SER. # : BROE2J341073
DATE,TIME 05/02 09:43
FAX NO./NAME 98221763
DURATION 00: 00:3 3
PAGE(S) 02
RESULT OK
MODE STANDARD
ECM
Grir
CITY OF COLLECE STATION
Negronins crDevelnptncnt Servicer
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
May 2, 2005
TO: Sahara Realty Group, Ltd, Via fax 822.1763
FROM: Bridgette George, Development Coordinator
SUBJECT; HENTQN-LINCOLN LOTS 2R&4R(FP-REPL4T) -Final Plat
Staff reviewed the above-mentioned final plat as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments
have been addressed and the following information submitted by Thursday, December
15, 10:00 a.m., your project will be placed on the next available Planning and Zoning
Commission meeting scheduled for, Thursday, January 6, 2005, in the City Hall Council
Chambers, 1101 Texas Avenue,
Ten (10) 11"x 17" copies of the revised final plat;
Two (2) 24" x 36" copies of the revised final plat;
One (1) Mylar original of the revised final plat; and
Griffilliiilliiiiiiii
CITY OF COLLEGE STATION
Planning 6'Development Services
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
May 2, 2005
TO: Stewart Kling, Kling Engineering & Surveying, Via fax 846.8252
FROM: Bridgette George, Development Coordinator
SUBJECT: HENTON-LINCOLN LOTS 3R & 4R(FP-REPLAT) - Final Plat
Staff reviewed the above-mentioned final plat as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments
have been addressed and the following information submitted by Thursday, December
15, 10:00 a.m., your project will be placed on the next available Planning and Zoning
Commission meeting scheduled for, Thursday, January 6, 2005, in the City Hall Council
Chambers, 1101 Texas Avenue.
Ten (10) 11" x 17" copies of the revised final plat;
Two (2) 24" x 36" copies of the revised final plat;
One (1) Mylar original of the revised final plat; and
One (1) copy of the digital file of the final plat on diskette or e-mail to
nmanhart@ci.college-station.tx.us
Upon receipt of the required documents for the Planning & Zoning meeting, your project
will be considered formally filed with the City of College Station. Please note that if all
comments have not been addressed your project will not be scheduled for a Planning &
Zoning Commission meeting. Your project may be placed on a future agenda once all
the revisions have been made and the appropriate fees paid. If you have any questions
or need additional information, please call Carol Cotter or myself at 764-3570.
Attachments: Staff review comments
cc: Sahara Realty Group, Ltd, Via fax 822.1763
David Scarmardo, Via fax 822.1763
Case file #04-00500269
Home of Texas A&M University
STAFF REVIEW COMMENTS NO. 2
Project: HENTON-LINCOLN LOTS 3R &4R (FP-REPLAT) - 04-00500269
Planning
1. The Replat does not match the utility layout (page C4.1 of construction documents). There
are numerous locations where this does not match. Please revise and resubmit.
Reviewed by: Jennifer Reeves Date: 04-27-05
ELECTRICAL
1. Developer installs conduit per city specs and design
2. Developer provides concrete transformer pad(s) per city specs and design.
3. Developer installs pull boxes as per city specs and design.(pull boxes provided by
the city).
4. Preliminary plan has been provided to developer for electric system design, showing
locations of proposed conduit routes, transformer pads and pull boxes.
5. Developer provides easements for electric infrastructure as installed. Temporary
Blanket easement will be required for construction purposes. Once complete
developer provides as build descriptive easement to have temporary blanket
easement released.
7. All easement as shown on plat cover existing electric infrastructure on site.
To discuss any of the above electrical comments, please contact Tony Michalsky at
979.764.3438.
Reviewed by: Tony Michalsky Date: 4-28-05
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review. 2 of 2
TRANSMISSION VERIFICATION REPORT
TIME : 05/02/2005 09: 45
NAME : COCS DEVELOPMENT SER
FAX : 9797643496
TEL : 9797643570
SER.# : BROE2J341073
DATE,TIME 05/02 09: 45
FAX NO./NAME 98468252
DURATION 00: 00:33
PAGE(S) 02
RESULT OK
MODE STANDARD
ECM
CITY OFF COLLEGE STATION
PIanni zg 6.Development Servicer
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764,3496
MEMORANDUM
May 2, 2005
TO: Stewart Kling, Kling Engineering & Surveying, Via fax 846.8252
FROM: . Bridgette George, Development Coordinator
SUBJECT: HENTON-LINCOLN LOTS 3R & 4R(FP-REPLA7) - Final Plat
Staff reviewed the above-mentioned final plat as requested. The following page is a list
of staff review comments detailing items that need to he addressed. If all comments
have been addressed and the following information submitted by Thursday, December
15, 10:00 a.m., your project will be placed on the next available Planning and Zoning
Commission meeting scheduled for, Thursday, January 6, 2005, in the City Hall Council
Chambers, 1101 Texas Avenue.
Ten (10) 11" x 17" copies of the revised final plat;
Two (2) 24" x 36" copies of the revised final plat;
One (1) Mylar original of the revised final plat; and
4ffil51111111111
CITY OF COLLEGE STATION
Planning&Development Services
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
May 2, 2005
TO: David Scarmardo, Via fax 822.1763
FROM: Bridgette George, Development Coordinator
SUBJECT: HENTON-LINCOLN LOTS 3R 8 4R(FP-REPLAT) - Final Plat
Staff reviewed the above-mentioned final plat as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments
have been addressed and the following information submitted by Thursday, December
15, 10:00 a.m., your project will be placed on the next available Planning and Zoning
Commission meeting scheduled for, Thursday, January 6, 2005, in the City Hall Council
Chambers, 1101 Texas Avenue.
Ten (10) 11" x 17" copies of the revised final plat;
Two (2) 24" x 36" copies of the revised final plat;
One (1) Mylar original of the revised final plat; and
One (1) copy of the digital file of the final plat on diskette or e-mail to
nmanhart@ci.college-station.tx.us
Upon receipt of the required documents for the Planning & Zoning meeting, your project
will be considered formally filed with the City of College Station. Please note that if all
comments have not been addressed your project will not be scheduled for a Planning &
Zoning Commission meeting. Your project may be placed on a future agenda once all
the revisions have been made and the appropriate fees paid. If you have any questions
or need additional information, please call Carol Cotter or myself at 764-3570.
Attachments: Staff review comments
cc: Sahara Realty Group, Ltd, Via fax 822.1763
Stewart Kling, Kling Engineering & Surveying, Via fax 846.8252
Case file#04-00500269
Home of Texas A&M University
STAFF REVIEW COMMENTS NO. 2
Project: HENTON-LINCOLN LOTS 3R & 4R (FP-REPLAT) - 04-00500269
Planning
1. The Replat does not match the utility layout (page C4.1 of construction documents). There
are numerous locations where this does not match. Please revise and resubmit.
Reviewed by: Jennifer Reeves Date: 04-27-05
ELECTRICAL
1. Developer installs conduit per city specs and design
2. Developer provides concrete transformer pad(s) per city specs and design.
3. Developer installs pull boxes as per city specs and design.(pull boxes provided by
the city).
4. Preliminary plan has been provided to developer for electric system design, showing
locations of proposed conduit routes, transformer pads and pull boxes.
5. Developer provides easements for electric infrastructure as installed. Temporary
Blanket easement will be required for construction purposes. Once complete
developer provides as build descriptive easement to have temporary blanket
easement released.
7. All easement as shown on plat cover existing electric infrastructure on site.
To discuss any of the above electrical comments, please contact Tony Michalsky at
979.764.3438.
Reviewed by: Tony Michalsky Date: 4-28-05
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review. 2 of 2
pue 'raid pull. pas!AeJ auj o leu!6!Jo Je1.60,1 auo
'mild pug peelneJ sa!doo k9E X ktrZ (e) omj.
!field leu!j pes!nei aqua sa!doa L x j G I. (0 M,) ual —.
'anuany sexa j 1.0 L I, `siagwag3
l!Ounoo IIeH X3!3 au; ul `900Z '9 fuenuer `itepsJngi `.10j palnpay3s 6u!maew uo!SS WWo0
6u!uo2 pue 6uluueld elgel1ene xxeu eq uo paaeld aq paid mnbA "Lire 00:01. '91.
isgweoaa 'itepsinq j Aq pamwgns uo!;ewaoou! 6u!molla au; pue passemppe ueaq aney
sluawwon Ile it •passaappe eq a} paeu ;au; suuaa! Bu!I!e;ep s;uewwoo rna!na,J guts Jv
$!l
e s! abed 6u!molloi. oia •palsanbal se geld Ieu!4 pauo!luew-anoge aur peme!naJ }}els
Mid leuid- (1117d3el-dd)WI aS 5107 N7031411-1-NOINglI :103rens
JoJeu!pJao0;uawdolanaa 46.1oa9 ageOpug
£9L l'ZZ9 xeJ e!A 'op iewJeoS p!nea :01
900'7 yew
FifICINVIIOnami
96-K1794'6L6 Xe4 / OLS£1791;64,6 auOLTd
ZtrSLL saxai, 'upping asafl0J
0966 'cog Od `t fOS anuany s'exa,L, TOY j
sovin g you dgar37.p;u:uund
NOLL .LS 3O8"I'1O) dO A 0
•I Faro 4r).
WO3
adVaNb1S 3a0W
710 13nS3d
Z0 (s)39d
EE:00 :00 NOIlddfa
E9LtZZ86 3140N/'ON Xdd
tb :60 70/90 31AII1'31va
ELOI1Er630e!S : #' 135
OL9Eb9L6L6 : l31
96t'E129L6L6 : Xb3
a3S IN3Wd013A311 SO00 : 3140N
Zb:60 5002/70/50 : 3WIl
ldOd3el NOIl"OIdId3A NOISSIWSNdJl
STAFF REVIEW COMMENTS NO. 1
Project: PUTZ-MEYER DRIVEWAY (SP) — 04-220
Construction of any portion of a commercial site (such as a driveway) requires the
property to be platted, a site plan, and a development permit.
After review of the materials, staff has determined that this does not meet the
requirements for a complete site plan submittal. Additional plans and reports are
necessary for a complete submittal (e.g., signal modification, drainage report,
landscaping plan, color and material samples, water and sewer reports). A complete
site plan may be a phase of the overall plan but must include a building, parking, drive,
etc. The following comments do not constitute a complete review, but are provided for
general guidance.
ENGINEERING
1. The site plan shows off-site improvements. A written agreement allowing the
improvements is needed from the Richard Smith property owner.
2. Please submit a TxDOT permit application for any construction proposed within the
state right-of-way including the drive, utilities, and signal modification.
3. FYI for platting: The required throat depth for shopping centers is 130 feet. Please
provide the cross access easement to this point.
Reviewed by: Alan Gibbs Date: September 9, 2004
NOTE: Any changes made to the plans,that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review.
Page 2 of 2
We have a PAC Monday with Scarmardo for his development on University. He's not showing the
access that Bobby Cox was hoping for. He is showing an off-site drainage structure on Cox's property.
Would anyone like to comment on these comments and/or try to get these two in a room and facilitate
a discussion? We would like some input so we can be clear of what our REQUIREMENTS will be prior to
meeting with Scarmardo. As a reminder, Scarmardo is hoping to construct this driveway prior to full
site plan.
4. I I 5 I I I 111 I I I
CITY OF COLLEGE STATION
Planning eT Development Services
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
November 24, 2004
TO: David Scarmardo, Via fax 822.1763 t/
FROM: Bridgette George, Assistant Development Manager
SUBJECT: HENTON SUBDIVISION - REPLAT - Final Plat
Staff reviewed the above-mentioned final plat as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments
have been addressed and the following information submitted by Thursday, December
15, 10:00 a.m., your project will be placed on the next available Planning and Zoning
Commission meeting scheduled for, Thursday, January 6, 2005, in the City Hall Council
Chambers, 1101 Texas Avenue.
Ten (10) 11" x 17" copies of the revised final plat;
Two (2) 24" x 36" copies of the revised final plat;
One (1) Mylar original of the revised final plat; and
One (1) copy of the digital file of the final plat on diskette or e-mail to
nmanhart@ci.college-station.tx.us
Upon receipt of the required documents for the Planning & Zoning meeting, your project
will be considered formally filed with the City of College Station. Please note that if all
comments have not been addressed your project will not be scheduled for a Planning &
Zoning Commission meeting. Your project may be placed on a future agenda once all
the revisions have been made and the appropriate fees paid. If you have any questions
or need additional information, please call Carol Cotter or myself at 764-3570.
Attachments: Staff review comments
cc: Sahara Realty Group, Ltd, Via fax 822.1763 /
Stewart Kling, Kling Engineering & Surveying, Via fax 846.8252 ✓
Case file #03-00500099
STAFF REVIEW COMMENTS NO. 1
Project: HENTON SUBDIVISION - REPLAT - 04-00500269
PLANNING/ENGINEERING
1. Lot 1R (Homestead Suites) will need to be included as part of this plat, as
it was part of the original building plot.
2. Please note on plat that Lot 1R (Homestead Suites) will have shared
signage (as noted on the University Town Center site plan).
Reviewed by: Jennifer Reeves/Alan Gibbs Date: 11-19-04
ELECTRICAL
1. Developer installs conduit per city specs and design
2. Developer provides concrete transformer pad(s) per city specs and design.
3. Developer installs pull boxes as per city specs and design.(pull boxes provided by
the city).
4. Preliminary plan has been provided to developer for electric system design, showing
locations of proposed conduit routes, transformer pads and pull boxes.
5. Developer provides easements for electric infrastructure as installed. Temporary
Blanket easement will be required for construction purposes. Once complete
developer provides as build descriptive easement to have temporary blanket
easement released.
6. Need to verify and mark 15 ft. PUE back lot line of lot 4R by existing detention pond.
7. Need 15 ft PUE along complete back lot line of lot 3R.
8. All easement as shown on plat cover existing electric infrastructure on site.
To discuss any of the above electrical comments, please contact Tony Michalsky at
979.764.3438.
Reviewed by: Tony Michalsky Date: 11-22-04
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review.
Page 2 of 2
COLLEGE STATION
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone (979) 764-3570 / Fax (979) 764-3496
MEMORANDUM
TO: Stewart Kling @ Kling Engineering & Surveying, via fax 846.8252
FROM: Molly Hitchcock, Staff Planner
SUBJECT: PUTZ-MEYER DRIVEWAY (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address
the comments and submit the following information for further staff review:
Six (6) complete sets of construction documents for the proposed
development with the revised site and landscaping plans attached (please
submit additional copies to be stamped for your records).
Two (2) revised site plans; and
One (1) landscaping plan.
OR
One (1) revised site and landscaping plan.
$ Parkland Dedication fees prior to issuance of a building permit.
Easement Dedication Sheet and required documents.
Please note that the Easement Dedication Sheet and the necessary documents are
required prior to the issuance of a building permit. If there are comments that you are
not addressing with the revised site plan, please attach a letter explaining the details. If
you have any questions or need additional information, please call me at 979.764.3570.
STAFF REVIEW COMMENTS NO. 1
Project: PUTZ-MEYER DRIVEWAY (SP) — 04-220
Construction of any portion of a commercial site (such as a driveway) requires the
property to be platted, site plan, and development permit.
After review of the materials, staff has determined that this does not meet the
requirements for a complete site plan submittal. Additional plans and reports are
necessary for a complete submittal (e.g., drainage report, landscaping plan, color and
material samples, water and sewer reports). The following comments do not constitute
a complete review, but are provided for general guidance.
ENGINEERING
1. The site plan shows off-site improvements. A written agreement allowing the
improvements is needed from the Richard Smith property owner.
2. Please submit a TxDOT permit application for any construction proposed within the
state right-of-way.
3. FYI for platting: The required throat depth for shopping centers is 130 feet. Please
provide the cross access easement to this point.
Reviewed by: Alan Gibbs Date: September 9, 2004
NOTE: Any changes made to the plans,that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review.
Page 3 of 1
`. CITY OF COLLEGE STATION
`$ DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
COL<EU. STATIONCollege Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
August 18, 2004
TO: Stewart Kling
David Scarmardo
FROM: Jennifer Prochazka, Staff Planner
SUBJECT: Building Plot Determination and Allowed Signage for The
Henton-Lincoln Subdivision and the Putz-Meyer Property
I am providing this memo to you as a summary of the discussion in our meeting
on Tuesday, August 17, 2004 regarding the allowed signage for the proposed
retail center. The Henton-Lincoln Subdivision and the Putz-Meyer property, as
configured in the attached document, have been determined to consist of three
separate and distinct building plots for the purposes of signage. These building
plots have been determined using the criteria in Section 7.1.G of the Unified
Development Ordinance (UDO).
Building Plot or Premises
A building plot, as defined by the UDO, consists of all of the land within a project,
whether one or more lots, developed according to a common plan or design for
similar or compatible uses, that may have shared access or parking, and that
singularly or in phases is treated as such for site plan review purposes.
Size of Freestanding signs
Each building plot with more than 150 feet of frontage shall be allowed to use
one Freestanding Commercial Sign or any number of Low Profile Signs as long
as there is a minimum separation between Low Profile Signs of 150 feet.
The size of the freestanding sign is based on the following chart (frontage is
separate for each building plot):
Home of Texas A&M University
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
August 18, 2004
TO: Stewart Kling
David Scarmardo
FROM: Jennifer Prochazka, Staff Planner
SUBJECT: Building Plot Determination and Allowed Signage for The
Henton-Lincoln Subdivision and the Putz-Meyer Property
I am providing this memo to you as a summary of the discussion in our meeting
on Tuesday, August 17, 2004 regarding the allowed signage for the proposed
retail center. The Henton-Lincoln Subdivision and the Putz-Meyer property, as
configured in the attached document, have been determined to consist of three
separate and distinct building plots for the purposes of signage. These building
plots have been determined using the criteria in Section 7.1.G of the Unified
Development Ordinance (UDO).
Building Plot or Premises
A building plot, as defined by the UDO, consists of all of the land within a project,
whether one or more lots, developed according to a common plan or design for
similar or compatible uses, that may have shared access or parking, and that
singularly or in phases is treated as such for site plan review purposes.
Size of Freestanding signs
Each building plot with more than 150 feet of frontage shall be allowed to use
one Freestanding Commercial Sign or any number of Low Profile Signs as long
as there is a minimum separation between Low Profile Signs of 150 feet.
The size of the freestanding sign is based on the following chart (frontage is
separate for each building plot):
Home of Texas A&M University
Allowable Area For Freestanding Signs
Frontage Feet Maximum Area is.f.
0-75
Low Profile only
76-100
50
101-150
75
151-200
100
201-250
125
251-300
150
301-350
175
351-400
200
401-450
225
451-500
250
501-550
275
551-600+
300
Using this chart, and the frontages provided by you, the following freestanding
signs would be permitted:
Building plot #1 would be allowed one 300 sq. ft. freestanding sign
(Per previous written agreement on March 6, 2004 allowing 300 sq. ft.)
Building plot #2 would be allowed one 300 sq. ft. freestanding sign
Building plot #3 would be allowed one 250 sq. ft. freestanding sign
Opportunity for "Extra" signage for Pad sites:
Any site defined as a single building plot, and containing one or more pad sites,
shall be permitted to erect a Freestanding Commercial Sign in accordance with
Section 7.4.M, Freestanding Commercial Signs, and to the standards of Section
7.4.M.1.a, Allowable Area, with the maximum area not to exceed 200 square
feet. In addition, each pad site will be permitted to erect one Low Profile Sign per
pad site according to the restrictions of 7.4.F, Sign Standards.
The UDO defines a pad site as the portion of a building plot that is located on the
periphery of the site and has at least 75 feet of frontage on a public street
classified as a collector or greater on the Thoroughfare Plan. A pad site contains
a stand alone, single tenant structure and meets all site plan requirements within
the pad site area. The total area of all pad sites within a defined building plot
may not be more than 1/3 of the total area of the building plot.