(7A■ilil0i111:i[OW67:\7:\ilk.`fibi/�176YiJ»4'�7] %\�171.YiJu1 /\71_�1
Attached to this memo, please find the summaries for the ELECTRICAL LOAD
DEMAND and SEWER/SUPPLY DEMAND for the building expansion at University
Lutheran Chapel, 315 College Main. Brazos Valley Engineering completed these
calculations. The calculations are based upon the now completed drawings for our
building expansion. Please forward these Demand Summaries to the appropriate
individuals as necessary.
Thank you for your assistance.
Visit our website: www2.txcyber.com/—ulctamu
Serving The Aggieland Campus Community
University Lutheran (LCMS)
• Chapel & Student Center 315 College Main
X 77840
• All Nations Christian Center Phone/ station, 84
Phone/Fax (979) 846-6687-6687
• Lutheran Student Fellowship E-mail: ulctamu@txcyber.com
November 13, 2001
ELECTRICAL LOAD DEMAND ESTIMATE for
Building Expansion At
University Lutheran Chapel
315 College Main.
LOAD SUMMARY: NEW BUILDING , 1,150 SF
LOAD (WATTS)
GENERAL RECEPTACLE CONNECTED
2,700
LIGHTING CONNECTED
7,412
HVAC CONDENSING UNITSMEAT PUMPS
19,918
ELECTRIC HEAT W/AHU
0
MOTOR LOADS, <40HP
0
MOTOR LOADS, >40HP
0
COOKINGMEATING EQUI
0
WATER HEATERS
0
MISCELLANEOUS
0
EXISTING SERVICE
24,800
25% CONTINUOUS LOAD
1,853
25% LARGEST MOTOR
2,490
TOTAL DEMAND 59,173
120 240 VOLTS 1 PH 247
Visit our website: www2.txcyber.com/—ulctamu
Serving The Aggieland Campus Community
University Lutheran (LCMS)
• Chapel & Student Center 315 College Main
X 77840
• All Nations Christian Center College Station, 84
Phone/Fax (979) 846-6687-6687
• Lutheran Student Fellowship E-mail: ulctamu@txcyber.com
November 13, 2001
SEWER/SUPPLY DEMAND ESTIMATE for
Building Expansion At
University Lutheran Chapel
315 College Main.
Y
DESCRIPTION
FU I
MIN
I MAX
I AVG
NEW SANITARY SEWER
33 10
GPD
11500 GP
30 GPD
NEW DOMESTIC WATER
38
10 GPM
2fi.3 GPM
<1 GPM
NOTE
1. PLUMBING FIXTURE UNIT DEMAND INCREASE, NEGUGBLE SEE FIXTURE
COUNT ON SITE ' - a js
3 SEWER/ SUPPLY DEMAND DETAIL
SCALE: NTS
Visit our website: www2.txcyber.com/ulctamu