HomeMy WebLinkAboutWater ReportWATER REPORT FOR FALCON POINT CONDOS COLLEGE STATION, TEXAS OCTOBER 2012 REVISED NOVEMBER 2012 MBESI# io62-0031 SUBMITTED BY: McCLURE & BROWNE, ENGINEERING/SURVEYING, INC. 1008 Woodcreek Dr., Suite 103 College Station, Tx. 77845. (979) 693-3838 Engineer Reg, No. F-458 1314 101h Street. Suite 210 - Hunts,iilo, Tx.9G320 (936) 294-9]49 Survey Reg, N, 101033-00 WATER AND SEWER SYSTEM ANALYSIS for FALCON POINT CONDOS General Information Anticipated land use: Anticipated number oflots: Notes on surrounding development: Primary water supply line. Software model: Average dailyflow: Total Fixture Units: Domestic Peak Flow: Estimated fire demand.' Pipe material: Proposed Building Size: Proposed Building Material: Items Min. Pressure Max. Velocih Conclusion: Applicable Exhibits: Exhibit A Exhibit B Exhibit C Exhibit D Exhibit E Exhibit F Exhibit G Exhibit H Residential (Condos) 4 lots This development is located near the comer of Holleman Drive and Dartmouth Drive in College Station. Post Oak Mall is located east of the development, a building owned by USDA is located south of the site and existing apartment buildings are located north of the development. Water System Analysis Existing 6" line on Holleman Drive Existing 6" line on Dartmouth Drive PIPE2000 (Kentucky Pipe Network Model) 105 gpd (all lots combined) (fixture unit method) 276 105 gpm 1,750 gpm (split between two hydrants) (per International Fire Code) PVC (C909) Building #1 = 6,480 sf Building #2 = 23,658 sf Type VA (protected) Notes .99 20 (min) Fire flow — — 84 12 (max) _ Fire flow The proposed water system exceeds the requirements of TCEQ and the City of College Station Schematic Water System Layout Static Flow Model Output "' Fire Flow Model Output ..�....... City of College Station Fire Flow Test Report 1 '-kY L. R City of College Station Fire Flow Test Report 2 ? 9474 Table B 105.1 from International Fire Code Fixture Unit Table Proposed Site Plan Falcon t Condos MBE #]0620031 Exhibit A Schematic Water System Layout Falcon Point Condos MBEST #10620031 Ex. 6' i i W/L i WATER MODEL M4R SCALE: Hor: 1° = 100' \' o so' ioo' zoo' — Holleman Drive R.O.W. Varies WATER LINE ANALYSIS MAP FALCON POINT CONDOS COLLEGE STATION, BR4ZOS COUNTY, TEXAS MCCLURE & BROWNE ENGINEERING/SURVEYING, INC. IC96 Woodcreck 0,W,, Sate IW, Co1,9e S &,, a 77M (979) 693-3 Fox: (9�) 693-2S 4 Firm RegNo. F-4 Exhibit B Static Flow Model Output Falcon Point Condos MRRSI #10620031 Exhibit B Static Flow Model Output + + + + + a + + * + K Y P I P E 5 * * + + + + + + + + * Pipe Network Modeling Software - * Copyrighted by KYPIPE LLC - Version 5 - February 2010 * Date s Time: Wed Nov 28 09:27:53 2012 Master File £:\1062 - clarke s wyndhem inc\0031 - holleman - dartmouth plat\docs\10620031-stat. KYP\10620031- stat.P2K S U M M A R Y O F O R I G I N A L D A T A U N I T S S P E C I F I E➢ FLOWRATE ............ = gallons/minute HEAD (HGL) .......... = feet PRESSURE ............ = psig P I P E L I N E D A T A STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P I P E NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR N A M E #1 #2 (ft) (in) COEFF. LOSS COEFF. --------- - -- --------------------------------------------- -- - ------------ P-1 VP-1 J-5 75.00 6.00 125.0000 0.00 P-2 J-3 J-1 100.00 8.00 125.0000 0.00 P-3 J-9 J-3 688.00 8.00 125.0000 0.00 P-9 J-2 VP-2 15.00 6.00 125.0000 0.00 P-5 J-1 J-2 437.00 8.00 125.0000 0.00 P-6 J-5 J-9 137.00 8.00 125.0000 0.00 P U M P/L O S S E L E M E N T D A T A THERE IS A DEVICE AT NODE VP-1 DESCRIBED BY THE FOLLOWING DATA: (I➢= 1) HEAD FLOWRATE EFFICIENCY (ft) (Apm) (8) 258.46 0.00 75.00 235.38 1455.00 75.00 175.15 2910.00 75.00 THERE IS A DEVICE AT NODE VP-2 DESCRIBED BY THE FOLLOWING DATA: (ID= 2) HEAD FLOWRATE EFFICIENCY (ft) (gPm) (8) 249.23 0.00 75.OD 230.77 1500.00 75.00 182.58 3000.00 75.00 N 0 D E D A T A NODE NODE EXTERNAL JUNCTION EXTERNAL NAME TITLE DEMAND ELEVATION GRADE (gPrD (ft) (ft) J-1 0.00 271.00 J-2 0.00 272.00 '- J-3 52.00 271.00 J-4 52.00 269.50 J-5 0.00 269.50 VP-1 ---- 270.00 270.00 VP-2 ---- 271.00 271.00 O U T P U T O P T I O N D A T A OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE TABULATED OUTPUT MAXIMUM AND MINIMUM PRESSURES 3 MAXIMUM AND MINIMUM VELOCITIES = 4 MAXIMUM AND MINIMUM HEAD LOSS/1000 = 4 S Y S T E M C O N F I G U R A T I O N NUMBER OF PIPES ...................(p) = 6 NUMBER OF END NODES ...............(j) = 5 NUMBER OF PRIMARY LOOPS ...........(1) 0 NUMBER OF SUPPLY NODES = ............(2 NUMBER OF SUPPLY ZONES .. ..... ..... (a) ) = 1 --____ Case: 0 RESULTS OBTAINED AFTER 19 TRIALS: ACCURACY = 0.00000 S I M U L A T I O N D E S C R I P T I O N (L A B E L) P I P E L I N E R E S U L T S STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P I P E NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HE/ N A M E #1 #2 LOSS LOSS VELD. 1000 1000 (gpm) (ft) (ft) (ft/s) (ft/ft) (ft/ft) _______ __________________________________________________ P-1 VP-1 J-5 104.00 0.09 0.00 1.18 1.21 1.21 P-2 J-3 J-1 0.00 0.00 0.00 0.00 0.00 0.00 P-3 J-4 J-3 52.00 0.06 0.00 0.33 0.08 0.08 P-4 J-2 VP-2 0.00 0.00 0.00 0.00 0.00 0.00 P-5 J-1 J-2 0.00 0.00 0.00 0.00 0.00 0.00 P-6 J-5 J-4 104.00 0.04 0.00 0.66 0.30 0.30 P U M P/L O S S E L E M E N T R E S U L T S INLET OUTLET PUMP EFFIC- USEFUL INCREMTL TOTAL #PUMPS #PUMPS NPSH NAME FLOWRATE HEAD HEAD HEAD ENCY POWER COST COST PARALLEL SERIES Avail. (gpm) (ft) (ft) (ft) (%) (Hp) ($) ($) (ft) _______________________________ __ _________ VP-1 104.00 0.00 258.29 258.3 75.00 0. 0.0 0.0 ** ** 33.2 Device "VP-2" is closed VP-2 0.00 0.00 257.10 0.0 75.00 0. 0.0 0.0 ** ** 33.2 N 0 D E R E S U L T S NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE (gpm) (ft) (ft) (£t) (Psi) ------------------------------------------------------------------------------ J-1 0.00 528.10 271.00 257.10 111.41 J-2 0.00 528.10 272.00 256.10 110.99 J-3 52.00 528.10 271.00 257.10 111.41 J-4 52.00 528.16 269.50 258.66 112.08 J-5 0.00 528.20 269.50 258.70 112.10 VP-1 ---- 528.29 270.00 258.29 111.92 VP-2 ---- 528.10 271.00 257.10 111.41 M A X I M U M A N D M I N I M U M V A L U E S P R E S S U R E S JUNCTION MAXIMUM JUNCTION MINIMUM NUMBER PRESSURES NUMBER PRESSURES (psi) (Psi) _____________________ _____________________ J-5 112.10 J-2 110.98 J-4 112.08 J-3 111.41 VP-1 111.92 J-1 111.41 V E L O C I T I E S PIPE MAXIMUM PIPE MINIMUM "- NUMBER VELOCITY NUMBER VELOCITY (£t/s) (£t/s) P-1 1.18 P-3 _________0.33__ P-6 0.66 P-6 0.66 H L+ M L PIPE MAXIMUM PIPE MINIMUM NUMBER HL+ML/1000 NUMBER HL+ML/1000 (ft/ft) (ft/ft) ___________________ P-1 1.21 P-3 0.08 P-6 0.30 P-6 0.30 H L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL/1000 NUMBER HL/1000 (ft/£t) (£t/ft) __________________ __ ___- ________________ P-1 1.21 P-3 0.08 P-6 0.30 P-6 0.30 S U M M A R Y O F I N F L O W S A N D O U T F L O W S (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE _-________- - VP-1 104.00 NET SYSTEM INFLOW = 104.00 -- NET SYSTEM OUTFLOW 0.00 NET SYSTEM DEMAND = 104.00 ***** HYDRAULIC ANALYSIS COMPLETED ***�* Exhibit C Fire Flow Model Output Falcon Point Condos MBESI #10620031 Exhibit C Fire Flow Model Output K Y P I P E 5 x Pipe Network Modeling Software * Copyrighted by KYPIPE LLC * Version 5 - February 2010 Date 6 Time: Wed Nov 28 09:25:36 2012 Master File £:\1062 - clarke 5 wyndham inc\0031 - holleman - dartmouth plat\docs\10620031-fire.KYP\10620031- fire.P2K S U M M A R Y O F O R I G I N A L D A T A x+xxxxxx+++++xxx+++xxx+xx++++xxxxxxxxx+++++++.x+ U N I T S S P E C I F I E D FLOWRATE ............ = gallons/minute HEAD (HGL) .......... = feet PRESSURE ............ = psig P I P E L I N E D A T A "- STATUS CODE: XX -CLOSED PIPE CV -CHECK VALUE P I P E NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR N A M E #1 #2 (ft) (in) COEFF. LOSS COEFF. -------------------- ----------------- ----------------- P-1 VP-1 J-5 75.00 6.00 125.0000 0.00 P-2 J-3 J-1 100.00 8.00 125.0000 0.00 P-3 J-4 J-3 688.00 8.00 125.0000 0.00 P-4 J-2 VP-2 15.00 6.00 125.0000 0.00 P-5 J-1 J-2 437.00 8.00 125.0000 0.00 P-6 J-5 J-4 137.00 8.00 125.0000 0.00 P U M P/L 0 S S E L E M E N T D A T A THERE IS A DEVICE AT NODE VP-1 DESCRIBED BY THE FOLLOWING DATA: (ID= 1) HEAD FLOWRATE EFFICIENCY (ft) (gpm) (8) 258.46 0.00 75.00 235.38 1455.00 75.00 175.15 2910.00 75.00 THERE IS A DEVICE AT NODE VP-2 DESCRIBED BY THE FOLLOWING DATA: (ID- 2) HEAD FLOWRATE EFFICIENCY (£t) (gpm) (&) 249.23 0.00 75.00 230.77 1500.00 75.00 182.58 3000.00 75.00 N 0 D E D A T A NODE NODE EXTERNAL JUNCTION EXTERNAL NAME TITLE DEMAND ELEVATION GRADE (gpm) (ft) (ft) J-1 0.00 271.00 - J-2 0.00 272.00 J-3 927.00 271.00 J-4 927.00 269.50 J-5 0.00 269.50 VP-1 --- 270.00 270.00 - VP-2 ---- 271.00 271.00 O U T P U T O P T I O N D A T A OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE TABULATED OUTPUT MAXIMUM AND MINIMUM PRESSURES = 3 MAXIMUM AND MINIMUM VELOCITIES = 4 MAXIMUM AND MINIMUM BEAD LOSS/1000 = 4 S Y S T E M C O N F I G U R A T I O N NUMBER OF PIPES ...................(.P) = 6 - NUMBER OF END NODES ...............(j) = 5 NUMBER OF PRIMARY LOOPS ...........(1) 0 NUMBER OF SUPPLY NODES ............(f) = 2 NUMBER OF SUPPLY ZONES ............(z) 1 Case: 0 RESULTS OBTAINED AFTER 4 TRIALS: ACCURACY 0.00000 S I M U L A T I O N D E S C R I P T I O N (L A B E L) P I P E L I N E R E S U L T S STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P I P E NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ N A M E #1 #2 LOSS LOSS VELD. 1000 1000 ----------------------------------------------------------------------------------------- (gpm) (£t) (ft) (ft/s) (ft/ft) (ft/ft) P-1 VP-1 J-5 1043.37 6.47 0.00 11.84 86.27 86.27 P-2 J-3 J-1-B10.63 1.33 0.00 5.17 13.32 13.32 P-3 J-4 J-3 116.37 0.25 0.00 0.74 0.37 0.37 P-4 J-2 VP-2-810.63 0.81 0.00 9.20 54.05 5405 P-5 J-1 J-2-810.63 5.82 0.00 5.17 13.32 13.32 - P-6 J-5 J-4 1043.37 2.91 0.00 6.66 21.25 21.23 P U M P/L 0 S S E L E M E N T R E S U L T S INLET OUTLET PUMP EFFIC- USEFUL INCREMTL TOTAL #PUMPS #PUMPS NISH NAME FLOWRATE HEAD HEAD HEAD ENCY POWER COST COST PARALLEL SERIES Avail. NPW (ft) (ft) (ft) (8) (Hp) (S) ($) (ft) -------------------------------------------------------------------------------------------------------- VP-1 1043.37 0.00 246.00 246.0 75.00 0. 0.0 0.0 * 33.2 VP-2 810.63 0.00 243.32 243.3 75.00 0. 0.0 0.0 ** ** 33.2 N 0 D E R E S U L T S NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE _ (qpm) (ft) (ft) (ft) (psi) ------------------------------------------------------------------------------ J-1 0.00 507.69 271.00 236.69 102.57 J-2 0.00 513.51 272.00 241.51 104.66 J-3 927.00 506.36 271.00 235.36 101.99 J-9 927.00 506.61 269.50 237.11 102.75 J-5 0.00 509.53 269.50 240.03 104.01 - VP-1 ---- 516.00 270.00 246.00 106.60 VP-2 --- 514.32 271.00 243.32 105.99 - M A X I M U M A N D M I N I M U M V A L U E S P R E S S U R E S JUNCTION MAXIMUM JUNCTION MINIMUM NUMBER PRESSURES NUMBER PRESSURES -------------------- (psi) ----------- (psi) - - VP-1 106.60 J-3 ----- 101.99 VP-2 105.99 J-1 102.57 J-2 109.66 J-9 102.75 V E L O C I T I E S PIPE MAXIMDM PIPE MINIMUM - NUMBER VELOCITY NUMBER VELOCITY (ft/6) (ft/6) P-1 11.84 P-3 0.74 P-9 9.20 P-2 5.17 _ P-6 6.66 P-5 5.17 H L+ M L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL+ML/1000 NUMBER HL+ML/1000 ----------- (£t/ft) --------- ------ --- (ft/ft) --- ------ P-1 86.27 P-3 0.37 P-9 54.05 P-2 13.32 P-6 21.25 P-5 13.32 H L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL/1000 NUMBER. HL/1000 (ft/ft) (ft/ft) P-1 86.27 P-3 0.37 P-9 54.05 P-2 13.32 P-6 21.25 P-5 13.32 S U M M A R Y O F I N F L 0 W S A N D O U T F L O W S (+) INFLOWS. INTO THE SYSTEM FROM SUPPLY NODES - (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (9pm) TITLE - -------------------------------------------- VP-1 1043.37 VP-2 810.63 NET SYSTEM INFLOW 1854.00 NET SYSTEM OUTFLOW = 0.00 NET SYSTEM DEMAND = 1854.00 ***** HYDRAULIC ANALYSIS COMPLETED ***** Exhibit D City of College Station Fire Flow Test Report 1 Falcon Point Condos MUSI#10620031 EXHIBIT D college Station Utilities Reliable, Affordable, Community Owned Date test completed Friday September 28, 2012 Time completed 3:15 P.M. Test completed by Vincent Rodriquez Witness Floyd Anderson, Lawrence Chavarria FLOW HYDRANT Location 1907 Dartmouth Nozzle size 2.5 Hydrant number E-029 Pitot reading in PSI 75 Flow in G.P.M. 1455 STATIC HYDRANT Location 1907 Dartmouth Hydrant number E-030 Static PSI 112 Residual PSI 102 Comments Requested Exhibit E City of College Station Fire Flow Test Report 2 Falcon Point Condos MBESI #10620031 EXHIBIT E alege Station utilities Rehab e, Affordable, Community Owned Date test completed Friday September 28, 2012 Time completed 2:30 P.M. Test completed by Vincent Rodriquez Witness Floyd Anderson, Lawrence Chavarria Location 1001 Holleman Dr. E. Nozzle size 2.5 Hydrant number E-153 Pitot reading in PSI 80 Flow in G.P.M. 1500 HYDRANT Location Hydrant number Static PSI Residual PSI Comments 1001 Holleman Dr. E. E-152 108 100 Requested Exhibit F Table B105.1 from International Fire Code Falcon Point Condos MBESI 410620031 FIRE -FLOW REQUIREMENTS FOR BUILDINGS TABLE 6105.1 MINIMI IM RFrl Umm noc .. n ., n FIRE -FLOW CALCULATION AREA (square feet) •V V• `v„YV' FIRE FLOW (gallons per minute)` 1,500 FLOW DURATION (hours) Type IA and Ieb 0-22,700 Type IIA and IIIAb 0-12,700 Type IV and V-A° 0-8,200 Type 11B and IIIeb 0-5,900 Type V-Bb 0-3,600 22,701-30,200 12,701-17,000 8,201-10,900 5,901-7,900 3,601-4,800 1,750 30,201-38,700 17,001-21,800 10,901-12,900 7,901-9,800 4,801-6,200 2,000 38,701-48,300 21,801-24,200 12,901-17,400 9,801-12,600 6,201-7,700 2,250 2 48,301-59,000 24,201-33,200 17,401-21,300 12,601-15,400 7,701-9,400 2,500 59,001-70,900 33,201-39,700 21,301-25,500 15,401-18,400 9,401-11,300 2,750 70,901-83,700 39,701-47,100 25,501-30,100 18,401-21,800 11,301-13,400 3,000 83,701-97,700 47,101-54,900 30,101-35,200 21,801-25,900 13,401-15,600 3,250 97,701-112,700 54,901-63,400 35,201-40,600 25,901-29,300 15,601-18,000 3,500 3 112,701-128,700 63,401-72,400 40,60146,400 29,301-33,500 18,001-20,600 3,750 128,701-145,900 72,401-82,100 46,401-52,500 33,501-37,900 20.601-23,300 4,000 145,901-164,200 82,101-92,400 52,501-59,100 37,901-42,700 23,301-26,300 4,250 164,201-183,400 92,401-103,100 59,101-66,000 42,701-47,700 26,301-29,300 4,500 183,401-203,700 103,101-114,600 66,001-73,300 47,701-53,000 29,301-32,600 4,750 203,701-225,200 114,601-126,700 73,301-81,100 53,001-58,600 32,601-36,000 5,000 225,201-247,700 126,701-139,400 81,101-89,200 58,601-65,400 36,001-39,600 5,250 247,701-271,200 139,401-152,600 89,201-97,700 65,401-70,600 39,601-43,400 5,500 271,201-295,900 152,601-166,500 97,701-106,500 70,601-77,000 43,401-47,400 5,750 106,501-115,800 77,001-83,700 47,401-51,500 6,000 4 01-125,500 83,701-9Q600 51,501-55,700 6,250 01- 135,500 90,601-97,900 55,701-60,200 6,500 m 01-145,800 97,901-106,800 60,201-64,800 6,750 01-156,700 L 106,801-113,200 64,801-69,600 7,000 01-167,900 113,201-121,300 69,601-74,600 7,250 01-179,400 121,301-129,600 74,601-79,800 7,500 - 179,401-191,400 129,601-138,300 79,801-85,100 7,750 - - 191,40LGreater 138,301-Greater 85.101-Greater 8,000 ror St: 1 square toot = 0.0929 in,, 1 gallon per minute = 3.785 Um, 1 pound per square inch = 6.895 kPa. a. The minimum required fire Flow shall be permitted to be reduced by 25 percent for Group R. b. Types of construction are based on the International Building Code. c. Measured at 20 psi. 372 2003 INTERNATIONAL FIRE CODE® Exhibit G Fixture Unit Table Falcon Point Condos MBESI A10620031 TABLE El W3 1(2) t nAn Ue I f fee ASS!Cmen ..a..,.,,e��. RX URE OCCUPANCY TYPE OFSUPPLY CONTROL LOAD VALUES. IN WATER SUPPLY R%TURE UNM jw a.) Cop Hot Totsl Bml400m gaup Privalz Flushmnk 1] IS 36 BnUucum group Mf ,, Flusht.Avr 6.0 3.0 SA Bathml* Print, Fmfret LO 1.0 1.4 Bmhmb Public F.vfcet ko 3.0 1.0 Hider Pdvole Fmcei 15 t3 +0 Cambmmion [wars Pdwt, Faaca Zdi 225 30 Duhw:vhin, ma:hi0, Prmte Aarofmtic 11 L4 Drink'mg fuvnOio Dlfwzc, tt,. ';R'valvr 015 (12G Kiminn sink Pmnte Flmwt 1.0 1.0 L 4 Kirzhnsint H,nel. rntaurue Faucet 3.0 3.0 4A Lmnfdre Imes 11 w Priem, Faucet to 1.0 L 4 L.,,,, Ptivmz Fnuoet 0.5 05 0.7 Lavnmry Publk Wm tit 1.5 15 �h Sercim sink Of&rs. roc. Fang 2.25 +±5 g0 Shower Mad pubic NI.i, J,a 3.0 3.0 jr1 Shower hied privat. NIW.- cdw 1 0 10 1.1 Vriw1 Public I"[lurch valve 100 IG9 UnfN Public 3/q"gush valve +9 5A L4fml Pobli, Flnsh dnk 3.0 til Wtl hing mahm, IS 15, Privet, Ant...c 10 10 14 W ;vhln_rwchmzi3 lb, Vublk Anmmxic 2>5 30 W'aldng fna-hirt. (15Ih1 Public Aummati< 3.0 :.p 40 W'mzrelacet Pdnte Wash calve ti0 Ulf Wmer.:les,t Private Flush rank _ R'uzrclosor PPblir Flush vmve Wo 100 Winer clmrt Publk Flush tank 5a 5m tamer closet PPblk erpfienP Fluahanvmrtank Jl — ±(f Fcr51: 1 inch= Ts q mnr. 1 pwn0=O.1.V �. a. Forlumic. mtliued.loadx shauld be.uxumed b9 eampvingeho Gzrufe a>anaiucd u+i¢;wu,rmsimilvqu.wGmxandm9milarruex. The msi"nzl kcade4a Gxmm whh b.qh M1ul and roN wat,r.wme Peen for spssote ha .and cold cwta[ Imd: end (nr mul leas. The sryvmrx Mf aui ooW water IoaJae:np rime,-fourzhx afrhe tuall id fcr the Gv., ufe . in,acA ease. TABLE E103.3(2y- ntlnued TABLE FOR ESTIMATING DEMAND SUPPLY SYSTELIS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEMS PREDOMfiJANLLY MR FLUSH VALVES Lmtl Dem.w Loan Demand (Water SUPPIYF .00hs) (Gallonswminule) (CUNCRe tPelminuW) (Welef SUppiy R%mMunds) (Genoes elminule p ) (CulJfc feet minute) 275 80.0 196944 275 104.5 13.9w56 30 850 113638 300 Iwo Il4374 400 105.0 14D3e 300 12710 1697316 500 1110 16.57632 500 I.430 19.11614 750 110.0 227256 ]50 177D 238W36 LOGO Ms") r805N 1.000 2AS0 _J.80i. 1S0 239.0 3141952 (2W 239_0 31,94957 IJ9u 169.0 119599' 1,5m 29.0 35.95992 1 -50 Iwo M970296 1750 197.0 39,M296 41,"6 2A00 i*5.0 43J 25(µJ 1800 - 7984 2:m 3w.0 5U.7981 33M(I 4330 578si 3,p 433.0 57.88311 1_U10 SxSg 70.18'_ 4mo 525.0 N.162 lorq 5910 7427224 S.w 593.0 7927-1 Exhibit H Proposed Site Plan Falcon Point Condos MBESI # 10620031 }34�A� IY'�T� m •- ��I - �l➢y 4o � HI F E 3 b fE a Mc(.'L;LJRE?. c& BROWNE, EiNGINEI+RING/StIRVI+',YIN , INC, 1008 Woodcreek Dr'., Suite 103. College Station, Tx. 77845 (979) E93-3838 1314 loth Street. Suite 210 - Huntsville, Tx. 77320 (936) 294-9749 February 18, 2013 Ms. Erika Bridges, PE City of College Station Post Office Box 9960 College Station, TX 77842 Re.: FIRE FLOW LETTER Falcon Point Condos MBESI No. 1000-0243 Dear Ms. Bridges: Engineer Reg, No. F 458 Survey Reg. No, 101033-00 The purpose of this letter is to confirm that the buildings proposed with the Falcon Point Condos project conform with the assumptions made in the Falcon Point Water Report in November 2012. An additional fire hydrant will be necessary in order to provide a hydrant within 100' of the fire department connection of building #2. Sincerely, Je R bertson, PE Pr 'ect Engineer F C050 - Edelweiss Gartens Venture=08 - Edetweiss Gartens Phase 131CooespondencelLetler Acknowledging City Standards wpd