HomeMy WebLinkAbout12-78_Page_13feet above grade. Such screening shall be coordinated with the building architecture and
scale to maintain a unified appearance.
24. Provide a general note on the site plan that states the following: Exterior building and site
lighting will meet the standards of Section 7.10 of the Unified Development Ordinance. The
light source shall not project below an opaque housing and no fixture shall directly project
light horizontally. Fixtures will be mounted in such a manner that the projected cone of light
does not cross any property line.
25. Please note that any changes made to the plans, that have not been requested by the City
of College Station, must be explained in your next transmittal letter and "bubbled" on your
plans. Any additional changes on these plans that the City has not be made of aware of will
constitute a completely new review.
Reviewed by: Lauren A. Hovde, Staff Planner Date: May 3, 2012
LANDSCAPING/STREETSCAPING/BUFFER
1. Buffer plantings are required per Section 7.6 of the Unified Development Ordinance.
2. Notes 4 & 6 and 5 & 7 are repetitive.
3. The scale is V=20'. Please revise the two legends provided.
4. The total number of landscaping points required for this site, not including buffer plantings, is
6136. This requirement is being met, but please revise the calculations shown.
5. Parking spaces must be screened when abutting the right-of-way. This includes the sides of
parking spaces.
Reviewed by: Lauren A. Hovde, Staff Planner Date: May 3, 2012
TxDOT Comments
1. The proposed access drives to FM 2154 and SH 40 will be required to meet TxDOT's current
"Regulations for Access Driveways to State Highways". Location must consider the posted
speed and the distance between existing, proposed and adjacent access points. Sufficient
information is not included denoting the access drives' location in relation to adjacent access
drives and roadway intersections. This information is necessary for further evaluation. No
access permit can be approved prior to receipt and approval by TxDOT of this information.
2. Proposed access drives should include right -turn deceleration lanes.
Reviewed by: Chad Bohne Date: April 26, 2012
ENGINEERING COMMENTS NO. 1
1. Please submit water and drainage reports, Letter of Acknowledgment, cost estimate, and
NOI.
2. Please submit construction plans for the proposed decel lanes.
3. Please add a note to the site plan addressing whether or not FEMA regulated floodplain
exists on the property.
4. Al — Please show and label all PUEs on -site and adjacent to the property.
5. The Landscape Plan by McClure & Browne is also labeled Site/Grading Plan. Please
clarify.
6. Al — Please show the driveway connection to W.D. Fitch Pkwy. on the site plan.
7. Al — Show and label the rights -of -way and property lines.
8. Al — Show and label all public and private water, sanitary sewer, electrical, and stormwater
infrastructure. Label size, pipe material, and slope (if applicable).
9. Al — Add a note or table with the minimum, average, and maximum water and sanitary
sewer demands.
10. Site/Grading Plan —All private utilities need to be removed from the PUE.
11. Site/Grading Plan — Please show and label all utilities.