HomeMy WebLinkAboutWater ReportWATER REPORT
.;
GREAT OAKS
PHASES 13, & 14
College Station, Texas
JUNE 2013
MBESI# 1028-ooO2
pmMcCLURE & BROWNE, ENGINEERING/SURVEVING, INC.
1008 Woodcreek Dr, Suite 103 College Station, Tx. 77845 .(979) 693-3838 Engineer Reg. No. F-458
1314 10th Street, Suite 210 Huntsville, Tx. 77320 (936) 294-9749 Survey Reg. No. 101033-00
WATER SYSTEM ANALYSIS
FOR
GREAT OAKS SUBDIVISION, PHASE 13-14
General Information
Area encompassed by this phase: 124 acres
Anticipated land use: Single family residential (Great Oaks)
Anticipated number of lots: 24 lots
Notes on surrounding development: The subdivision is bounded by Great Oaks Phase 1
to the east and south, Quail Run Subdivision, and
property owned by the Kavanaugh Family to the
west.
Water System Analysis
Primary water supply line:
Existing 8" water line on Great Oaks Drive,
Arboleda Drive, and Walnut Road
Software model:
PIPE2012 (Kentucky Pipe Network Model)
Estimated peak domestic demand:
1.5 gpm per residential lot (per TCEQ
requirements)
Estimated fire demand:
1000 gpm
Pipe material:
PVC (C900)
Most Hydraulically Remote Point:
Node J-26 (See Exhibit A)
This is determined by calculating the lowest
pressure under static conditions.
Testing Method:
Wellborn S.U.D. performed the fire flow test on
May 13, 2013. A Pollard Hydrant Flow Gauge was
used to measure the flow at the existing fire hydrant
located at the intersection of Great Oaks Drive and
Arboleda Drive. The reading on the gauge was 70
psi which corresponds to a flow of 1450 gpm.
Water Model Parameters:
The model has been setup to analyze the "worst
case scenario'. We have assumed that Great Oaks
Phase 13/14 are fully developed and we only have
connections to the existing water system at Great
Oaks Drive. The model will work under these
conditions. However as the remainder of the Great
Oaks Subdivision is developed, additional
connections to the existing system will be made.
These connections will increase the pressures for
the entire system during fire flow conditions.
Great Oaks Phase 13/14
MBESI #1028-0002
Re elated Items Designed I Requirement I Notes
Min. Pressure (psi 68.4 _ 20 (min) ; Fire flow conditions (J-7)
Max. Velocity (fps) 6.50 12 (max) I Fire flow conditions (P-3)
Conclusion: The proposed water system exceeds the requirements of TCEQ
and the Cities of Bryan and College Station
Applicable Exhibits:
Exhibit A Schematic Water System Layout
Exhibit B PIPE2000 Model Output for Great Oaks, Phase 2 and Los Palomas
Subdivision (static)
Exhibit C PIPE2000 Model Output for Great Oaks, Phase 2 and Los Palomas
Subdivision (fire)
Y1
"y�,}1Ali r
Great Oaks Phase 13/14
MBESI 41028-0002
J8 Junction Location
p� Pressure Source Location
EXHIBIT A —HATER WATER MAP
® s� �,� a sae•
Exhibit B
Static Flow Conditions
* * * * * * * * * * K Y P I P E 5
* *
* Pipe Network Modeling Software
* *
* Copyrighted by KYPIPE LLC
* Version 5 - February 2010
* *
Date & Time: Fri Jun 28 10:36:05 2013
Master File : f:\1028 - caldwell companies\0002 - great oaks phases 13-
14\docs\gol314-stat.KYP\go1314-stat.P2K
S U M M A R Y O F O R I G I N A L D A T A
U N I T S S P E C I F I E D
FLOWRATE ............ = gallons/minute
HEAD (HGL) .......... = feet
PRESSURE ............ = psig
P I P E L I N E D A T A
STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE
P I P E
NODE
NAMES
LENGTH
N A M E
41
#2
(£t)
--------------------------------------------
P-1
VP-1
J-5
1660.00
P-2
J-2
J-1
1881.00
P-3
J-2
J-3
586.00
P-4
J-3
J-4
600.00
P-5
J-3
J-7
80.00
P-6
VP-1
J-2
578.00
P-7
J-5
J-1
558.00
P-8
J-7
J-8
800.00
P-9
J-8
J-6
351.13
P U M P/L 0 S S E L E M E N T D A T A
DIAMETER
ROUGHNESS
MINOR
(in)
COEFF.
LOSS COEFF.
-------------------------------
8.00
140.0000
0.00
4.00
140.0000
0.00
8.00
140.0000
0.00
8.00
140.0000
0.00
8.00
140.0000
0.00
8.00
140.0000
0.00
8.00
140.0000
0.00
6.00
140.0000
0.00
4.00
140.0000
0.00
THERE IS A DEVICE AT NODE
HEAD
FLOWRATE
(ft)
(gpm)
196.15
0.00
161.54
1500.00
71.19
3000.00
N 0 D E D A T A
VP-1 DESCRIBED BY THE FOLLOWING DATA: (ID= 1)
EFFICIENCY
M
75.00
75.00
75.00
NODE
NODE
EXTERNAL
JUNCTION
EXTERNAL
NAME
TITLE
DEMAND
ELEVATION
GRADE
--------------------------------------------------------------
(gpm)
(ft)
(ft)
J-1
10.50
291.00
J-2
10.50
316.00
J-3
0.00
314.00
J-4
7.50
323.00
J-5
10.50
295.00
J-6
3.50
301.00
J-7
4.50
314.00
J-8
3.25
307.00
VP-1
----
313.00
313.00
O U T P U T
O P T I O N
D A T A
OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE
TABULATED OUTPUT
MAXIMUM
AND MINIMUM
PRESSURES
= 4
MAXIMUM
AND MINIMUM
VELOCITIES
= 5
MAXIMUM
AND MINIMUM
HEAD LOSS/1000
= 5
S Y S T E M
C O N F I G U
R A T I O N
NUMBER OF
PIPES ...................(p)
= 9
NUMBER OF
END NODES ...............(j)
= 8
NUMBER OF
PRIMARY LOOPS
...........(1)
= 1
NUMBER OF
SUPPLY NODES
............(£)
= 1
NUMBER OF
SUPPLY ZONES
............(z)
= 1
Case: 0
RESULTS OBTAINED AFTER 8 TRIALS: ACCURACY = 0.00001
S I M U L A T I O N D E S C R I P T I O N (L A B E L)
P I P E L I N E R E S U L T S
STATUS CODE: XX -CLOSED PIPE
P I P E NODE NUMBERS
HL/
N A M E #1 #2
1000
(ft/ft)
0.01
0.00
0.01
0.00
0.00
0.03
0.00
0.01
0.01
P-1
P-2
P-3
P-4
P-5
P-6
P-7
P-8
P-9
--------------
VP-1
J-5
J-2
J-1
J-2
J-3
J-3
J-4
J-3
J-7
VP-1
J-2
J-5
J-1
J-7
J-8
J-8
J-6
CV -CHECK VALVE
FLOWRATE
(gpm)
19.53
1.47
18.75
7.50
11.25
30.72
9.03
6.75
3.50
P U M P/L 0 S S E L E M E N T R E S U L T S
HEAD
MINOR
LINE
HL+ML/
LOSS
LOSS
VELD.
1000
(ft)
---------------------------
(ft)
(ft/s)
(ft/ft)
0.02
0.00
0.12
0.01
0.00
0.00
0.04
0.00
0.01
0.00
0.12
0.01
0.00
0.00
0.05
0.00
0.00
0.00
0.07
0.00
0.01
0.00
0.20
0.03
0.00
0.00
0.06
0.00
0.00
0.00
0.08
0.01
0.00
0.00
0.09
0.01
INLET
OUTLET
PUMP
EFFIC-
USEFUL
INCREMTL
TOTAL
#PUMPS #PUMPS NPSH
NAME FLOWRATE
HEAD
HEAD
HEAD
ENCY
POWER
COST
COST
PARALLEL SERIES Avail.
(gpm)
(ft)
(ft)
(ft)
M
(Hp)
($)
($)
(ft)
-------------------------------------------------------------------------------
-------------------------
VP-1 50.25
0.00
196.09
196.1
75.00
0.
0.0
0.0
** ** 33.2
N 0 D E R E S U L T S
NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE
NAME
TITLE
DEMAND
GRADE
ELEVATION
HEAD
(gpm)
(ft)
(ft)
(£t)
---------------------------------------------------------------------
J-1
10.50
509.07
291.00
218.07
J-2
10.50
509.08
316.00
193.08
J-3
0.00
509.07
314.00
195.07
J-4
7.50
509.07
323.00
186.07
J-5
10.50
509.07
295.00
214.07
J-6
3.50
509.06
301.00
208.06
J-7
4.50
509.07
314.00
195.07
J-8
3.25
509.06
307.00
202.06
VP-1
----
509.09
313.00
196.09
M A X
I M
U M A
N
D M I N I
M U M
V A L U E S
P
R E
S S U R
E
S
JUNCTION
MAXIMUM
JUNCTION
MINIMUM
NUMBER
PRESSURES
NUMBER
PRESSURES
(psi)
(psi)
J-1
94.50
J-4
80.63
J-5
92.76
J-2
83.67
J-6
90.16
J-7
84.53
J-8
87.56
J-3
84.53
V
E L
O C I T
I
E S
PIPE
MAXIMUM
PIPE
MINIMUM
NUMBER
VELOCITY
NUMBER
VELOCITY
(ft/3)
--
-------
(ft/s)
----------
P-6
0.20
P-2
0.04
P-1
0.12
P-4
0.05
P-3
0.12
P-7
0.06
P-9
0.09
P-5
0.07
P-8
0.08
P-8
0.08
H
L+
M L /
1
0 0 0
PIPE
MAXIMUM
PIPE
MINIMUM
NUMBER
HL+ML/1000
NUMBER
HL+ML/1000
(ft/ft)
---------------------
(ft/ft)
---------------------
P-6
0.03
P-4
0.00
P-9
0.01
P-7
0.00
P-1
0.01
P-2
0.00
P-3
0.01
P-5
0.00
P-8
0.01
P-8
0.01
H
L /
1 0 0
0
PIPE
MAXIMUM
PIPE
MINIMUM
NUMBER
HL/1000
NUMBER
HL/1000
PRESSURE
(psi)
94.50
83.67
84.53
80.63
92.76
90.16
84.53
87.56
84.97
1
(ft/£t)
------------
0.03
0.01
0.01
0.01
0.01
S U M M A R Y O F I N F L O W S A N D
P-4
P-7
P-2
P-5
P-8
(+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES
(-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES
NODE
FLOWRATE NODE
NAME
(gpm) TITLE
----------------------------------
VP-1
50.25
NET SYSTEM INFLOW = 50.25
NET SYSTEM OUTFLOW = 0.00
NET SYSTEM DEMAND = 50.25
(ft/ft)
0.00
0.00
0.00
0.00
0.01
O U T F L O W S
***** HYDRAULIC ANALYSIS COMPLETED *****
Exhibit C
Fire Flow Conditions
* * * * * * * * * * K Y P I P E 5
*
* Pipe Network Modeling Software
* *
* Copyrighted by KYPIPE LLC
* Version 5 - February 2010
* *
Date & Time: Fri Jun 28 10:38:53 2013
Master File : f:\1028 - caldwell companies\0002 - great oaks phases 13-
14\docs\gol314-fire.KYP\gol314-fire.P2K
S U M M A R Y O F O R I G I N A L D A T A
U N I T S S P E C I F I E D
FLOWRATE ............ = gallons/minute
HEAD (HGL) .......... = feet
PRESSURE ............ = psig
P I
P
E L I N E
D A T A
STATUS CODE:
XX -CLOSED
PIPE
CV -CHECK
VALVE
P
I
P E
NODE
NAMES
LENGTH
DIAMETER
ROUGHNESS
MINOR
N
A
M E
#1
#2
(ft)
(in)
COEFF.
LOSS COEFF.
-------------------------------------------------------------------------------
P-1
VP-1
J-5
1660.00
8.00
140.0000
0.00
P-2
J-2
J-1
1881.00
4.00
140.0000
0.00
P-3
J-2
J-3
586.00
8.00
140.0000
0.00
P-4
J-3
J-4
600.00
8.00
140.0000
0.00
P-5
J-3
J-7
80.00
8.00
140.0000
0.00
P-6
VP-1
J-2
578.00
8.00
140.0000
0.00
P-7
J-5
J-1
558.00
8.00
140.0000
0.00
P-8
J-7
J-8
800.00
6.00
140.0000
0.00
P-9
J-8
J-6
351.13
4.00
140.0000
0.00
2 U
M
P/L 0 S S
E L E M E
N T D
A T A
1-6.4 :7al ai6W.1m7a0toow3rAB11
HEAD
FLOWRATE
(ft)
(gpm)
196.15
0.00
161.54
1500.00
71.19
3000.00
N 0 D E D A T A
VP-1 DESCRIBED BY THE FOLLOWING DATA: (ID= 1)
EFFICIENCY
M
75.00
75.00
75.00
NODE
NODE
EXTERNAL
JUNCTION
EXTERNAL
NAME
TITLE
DEMAND
ELEVATION
GRADE
(gpm)
(ft)
(ft)
--------------------------------------------------------------
J-1
10.50
291.00
J-2
10.50
316.00
J-3
0.00
314.00
J-4
7.50
323.00
J-5
10.50
295.00
J-6
3.50
301.00
J-7
1004.50
314.00
J-8
3.25
307.00
VP-1
----
313.00
313.00
O U T P U T
O P T I O N
D A T A
OUTPUT SELECTION: ALL RESULTS ARE INCLUDED
IN THE
TABULATED OUTPUT
MAXIMUM
AND MINIMUM
PRESSURES
= 4
MAXIMUM
AND MINIMUM
VELOCITIES
= 5
MAXIMUM
AND MINIMUM
HEAD LOSS/1000
= 5
S Y S T E M
C O N F I G U
R A T I O N
NUMBER OF
PIPES ...................(p)
= 9
NUMBER OF
END NODES ...............(j)
= 8
NUMBER OF
PRIMARY LOOPS
...........(1)
= 1
NUMBER OF
SUPPLY NODES
............(f)
= 1
NUMBER OF
SUPPLY ZONES
............(z)
= 1
Case: 0
RESULTS OBTAINED AFTER 6 TRIALS: ACCURACY = 0.00004
S I M U L A T I O N D E S C R I P T I O N (L A B E L)
P I P
E L I N E
R E S U L
T S
STATUS CODE:
XX -CLOSED
PIPE
CV -CHECK VALVE
P I
P E
NODE NUMBERS
FLOWRATE
HEAD
MINOR
LINE
HL+ML/
HL/
N A
M E
#1
#2
LOSS
LOSS
VELD.
1000
1000
(gpm)
(ft)
(ft)
(ft/s)
(ft/ft)
(ft/ft)
-------------------------------------------------------------------------------
P-1
VP-1
J-5
99.72
0.37
0.00
0.64
0.22
0.22
P-2
J-2
J-1
-78.72
7.91
0.00
2.01
4.20
4.20
P-3
J-2
J-3
1018.75
9.66
0.00
6.50
16.48
16.48
P-4
J-3
J-4
7.50
0.00
0.00
0.05
0.00
0.00
P-5
J-3
J-7
1011.25
1.30
0.00
6.45
16.26
16.26
P-6
VP-1
J-2
950.53
8.38
0.00
6.07
14.50
14.50
P-7
J-5
J-1
89.22
0.10
0.00
0.57
0.18
0.18
P-8
J-7
J-8
6.75
0.00
0.00
0.08
0.01
0.01
P-9
J-8
J-6
3.50
0.00
0.00
0.09
0.01
0.01
P U M P/L 0 S S E L E M E N T R E S U L T S
INLET
OUTLET
PUMP
EFFIC-
USEFUL
INCREMTL
TOTAL
*PUMPS #PUMPS NPSH
NAME FLOWRATE
HEAD
HEAD
HEAD
ENCY
POWER
COST
COST
PARALLEL SERIES Avail.
(gpm)
(ft)
(ft)
(ft)
M
(Hp)
($)
($)
(ft)
-------------------------------------------------------------------------------
-------------------------
VP-1 1050.25
0.00
178.27
178.3
75.00
0.
0.0
0.0
** ** 33.2
N 0 D E R E S U L T S
NODE
NODE
EXTERNAL
HYDRAULIC
NODE PRESSURE
NODE
NAME
TITLE
DEMAND
GRADE
ELEVATION
HEAD
PRESSURE
(gpm)
(ft)
(ft)
(ft)
(psi)
------------------------------------------------------------------------------
J-1
10.50
490.79
291.00
199.79
86.58
J-2
10.50
482.89
316.00
166.89
72.32
J-3
0.00
473.23
314.00
159.23
69.00
J-4
7.50
473.23
323.00
150.23
65.10
J-5
10.50
490.90
295.00
195.90
84.89
J-6
3.50
471.92
301.00
170.92
74.06
J-7
1004.50
471.93
314.00
157.93
68.43
J-8
3.25
471.92
307.00
164.92
71.47
VP-1
----
491.27
313.00
178.27
77.25
M A X
I M
U M A
N
D M I N
I M U M
V A L U E S
P
R E
S S U R
E
S
JUNCTION
MAXIMUM
JUNCTION
MINIMUM
NUMBER
PRESSURES
NUMBER
PRESSURES
(psi)
(psi)
J-1
86.58
J-4
65.10
J-5
84.89
J-7
68.43
VP-1
77.25
J-3
69.00
J-6
74.06
J-8
71.47
V
E L
O C I T
I
E S
PIPE
MAXIMUM
PIPE
MINIMUM
NUMBER
VELOCITY
NUMBER
VELOCITY
---------------------
(ft/s)
---------------------
(ft/s)
P-3
6.50
P-4
0.05
P-5
6.45
P-8
0.08
P-6
6.07
P-9
0.09
P-2
2.01
P-7
0.57
P-1
0.64
P-1
0.64
H
L+
M L /
1
0 0 0
PIPE
MAXIMUM
PIPE
MINIMUM
NUMBER
HL+ML/1000
NUMBER
HL+ML/1000
(ft/ft)
(ft/ft)
P-3
16.48
P-4
0.00
P-5
16.26
P-8
0.01
P-6
14.50
P-9
0.01
P-2
4.20
P-7
0.18
P-1
0.22
P-1
0.22
H
L /
1 0 0
0
PIPE
MAXIMUM
PIPE
MINIMUM
NUMBER
HL/1000
NUMBER
HL/1000
(ft/ft)
--------
(ft/ft)
----
-------------
P-3
16.48
P-40.00
P-5
16.26
P-8
0.01
P-6
14.50
P-9
0.01
2-2
4.20
P-7
0.18
P-1
0.22
P-1
0.22
S U
M M A R Y O
F I N F L O W
S A
N D O U
T F L O W S
(+)
INFLOWS INTO THE SYSTEM FROM
SUPPLY
NODES
(-)
OUTFLOWS FROM
THE SYSTEM INTO
SUPPLY
NODES
NODE
FLOWRATE
NODE
NAME
(gpm)
TITLE
--------------------------------------------
VP-1
1050.25
NET
SYSTEM INFLOW
= 1050.25
NET
SYSTEM OUTFLOW = 0.00
NET
SYSTEM DEMAND
= 1050.25