Loading...
HomeMy WebLinkAboutFire Hydrant Flow TestfmMCC'LURE & BROWNE, ENGINEERING/SURVEYING, INC. 1006 Woodereek Dr, Suite 103 -College Station, Tx. 77845 (979) 693-3636 Engineer Reg No, F-458 1314 loth Street, Who 210 , Huntsville, Tx 77320 - (036) 294,9149 Survoy Reg. NO 101033�00 December 20, 2013 Ms. Danielle Singh, PE City of College Station Post Office Box 9960 College Station, TX 77842 Re.: Fire Hydrant As Built Flow Test Great Oaks, Phase 13 and 14 MBESI No. 1028-0002 Dear Ms. Singh: I witnessed the Wellborn Water representatives perform a fire hydrant flow test on the new fire hydrants in Great Oaks Phase 13 and 14 yesterday. The following are the results of that test: STATIC HYDRANT LOCATION: Spanish Oak Court/Arboleda Drive intersection FLOW HYDRANT LOCATION: Mid block of Spanish Oak Court STATIC PRESSURE GAUGE: 67 psi RESIDUAL PRESSURE GAUGE: 43 psi NOZZLE SIZE: 2.5" DISCHARGE COEFFICIENT: 0.90 FLOWRATE FORMULA: Q=29.84cd2p0.5 C = discharge coef. D = orifice size (in) P = pilot pressure (psi) CALCULATED FLOWRATE: 1,100 gpm @ 43 psi Based on this information, the new water system meets the standards of College Station. Please let me know if you have any questions. Sincerely, *Jeffery L. Robertson, PE v