HomeMy WebLinkAboutWater & Sewer System AnalysisWATER & SEWER SYSTEM
ANALYSIS
RB
11 11
FOR
CARTER'S CROSSING,
PHASES 1 thru 4
COLLEGE STATION, TEXAS
JUNE2007
MBESI# 1015-0006
SUBMITIED BY:
McCLURE & BROWNE ENGINEERING/SURVEYING, INC.
l008 Woodcreek Drive, Suite l03 •College Station, Texas 77845
(979) 693-3838 • Fax: (979) 693-2554 •Email: McCJureBrowne@Verizon.net
WATER AND SEWER SYSTEM ANALYSIS
FOR
CARTER'S CROSSING, PHASES 1 - 4
General Information
Area encompassed by this phase: 47 .7 acres
Anticipated land use:
Anticipated number of lots:
Single family residential
140 lots
Notes on surrounding development: The site is bordered to the north by Raintree
Subdivision, to the south by Emerald Forest
Subdivision, and the east and west by undeveloped
land.
Water System Analysis
Primary water supply line: Existing 8" line on North Forest Parkway
& Existing 8" line on Raintree Drive
PIPE2000 (Kentucky Pipe Network Model)
267 gpd (0.185 gpm) per residential lot
Software model:
Average daily flow:
Peaking factor: 4.0
Estimated peak domestic demand: 1.5 gpm per lot (per TCEQ requirements)
1000 gpm Estimated fire demand:
Pipe material: PVC (C909)
Most Hydraulically Remote Point: Node J-16 (See Exhibit A)
Conclusion:
Applicable Exhibits:
Exhibit A
Exhibit B
Exhibit C
ExhibitD
Exhibit E
This is determined by calculating the lowest
pressure under static conditions.
20 (min Fire flow conditions
12 (max) Fire fl.ow conditions
The proposed water system exceeds the requirements of TCEQ
and the City of College Station
Schematic Water System Layout
City of College Station Fire Flow Test Report 1
City of College Station Fire Flow Test Report 2
Static Flow Model Output for Carter's Crossing, Phases 1 - 4
Fire Flow Model Output for Carter's Crossing, Phases 1 - 4
CARTER'S CROSSING, PHASES 1 -4
MBESI # 10150006
Primary outfall line:
Software model:
Average daily flow:
Peaking factor:
P;pe Material:
Manning's N value:
Spreadsheet Notes:
Conclusion:
Applicable Exhibits:
Exhibit F
Exhibit G
Exhibit H
Sewer System Analysis
8" Line in Emerald Forest Subdivision
Microsoft EXCEL Spreadsheet based on Manning's Equation
267 gpd per residential lot
4.0
PVC (D3034 and D2241)
0.013
The spreadsheet in Exhibit G analyzes the entire system for
Carter's Crossing, Phases I - 4. It computes the anticipated
flowrates from each area and the minimum slopes of the lines that
serve those areas. It compares the computed slope with either the
required minimum slope or the design slope from the plans. If the
computed slope is less than the minimum or the design slope, the
spreadsheet indicates the line is "OK".
All of the lines in the spreadsheet on Exhibit H indicate they
are OK and thus meet the design guidelines of the City of
College Station. Therefore, we conclude that the lines are
adequately sized and will easily carry the sewage flows that are
expected to pass through them.
Schematic Sewer System Layout
Sewer Model Spreadsheet
Copy of Letter to TCEQ
CARTER'S CROSSING, PHASES 1 -4
MBESI #10150006
Exhibit B
(Hydrant Flow Test)
College Station Utilities
Re/fable, Aff ordab/e, Communil ;r o ,vned
1601 GRAHAM ROAD
COLLEGE STATION TEXAS 77845
Date: 10 JANUARY 2006
From: Butch Willis Water Wastewater Division
Phone: 979-764-3435 Fax: 979-764-3452
FLOW TEST REPORT
Nozzle size: 2.5 inch
Location: APPOMATTOX AT WALNUT GROVE
Flow hydrant number: 1-052
Pitot reading: 78
(GPM): 1475
Static hydrant number: 1-050
Static PSI: 116
Residual PSI: 88
Exhibit B
Existing Hydrant Flow Test Data
Carter's Crossing, Phases 1 & 2
Exhibit C
(Hydrant Flow Test)
Co' lege Station Utilities
Reliable~ AtYordab/e,. Communit y Owned
1601 GRAHAM ROAD
COLLEGE STATION TEXAS 77845
Date: 10 JANUARY 2006
From: Butch Willis Water Wastewater Division
Phone: 979-764-3435 Fax: 979-764-3452
FLOW TEST REPORT
Nozzle size: 2.5 inch
Location: RAINTREE AT SUMTER
Flow hydrant number: H-022
Pitot reading: 85
(GPM): 1550
Static hydrant number: H-020
Static PSI: 116
Residual PSI: 96
Exhibit C
Hydrant Flow Test Data
Carter's Crossing, Phases 1 & 2
EXHIBIT D
STATIC FLOW ANALYSIS
KYPIPE4
University of Kentucky Network Modeling Software
Copyrighted by KYPIPE LLC
Version 3 -11/01/2005
Date & Time : Wed May 23 10:06:32 2007
INPUT DATA FILENAME --------------F: \1015-S-l \0006-C-l\Docs\Repor ts\WATERS-l \10150006.DT2
TABULATED OUTPUT FILENAME --------F: \1015-S-l \0006-C-l \Docs\Reports\WATERS-1 \10150006.0TZ
POSTPROCESSOR RESULTS FILENAME ---F: \1015-S-l \0006-C-l \Docs\Reports\WATERS-1 \10150006. RS2
S U M M A R Y 0 F 0 R I G I N A L D A T A
U N I T S S P E C I F I E D
FLOWRATE . • • • . • . . . • • • = gallons/minute
HEAD (HGL) .•...••..• = feet
PRESSURE • • • • • • • • • • • • • psi g
P I P E L I N E D A T A
STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE
NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR P I P E
N A M E #1 #2 (ft) (in) COEFF. LOSS COEFF .
P-1 FH-1 J-1 234. 20 1. 05 119.4518
P-2 J-1 J-4 234. 61 1.05 119.4518
P-3 J-3 J-2 50. 71 8. 00 120. 0000
P-4 J-4 J-3 132. 95 8. 00 120.0000
P-5 J-3 J -5 209. 98 3.00 120. 0000
P-6 J-2 J-6 394. 35 3.00 120. 0000
P-7 J-4 J-7 703. 83 8. 00 120. 0000
P-8 J-7 J -8 181. Bl 8. 00 120. 0000
P-9 J-8 J-10 584. 30 6.00 120 .0000
P-10 J-10 J-9 525.35 6.00 120. 0000
P-11 J -9 J-8 428.74 8. 07 119.4518
P-12 J-9 J-11 113. 05 8. 00 120. 0000
P-13 J-11 FH-2 213.05 8. 00 120. 0000
P-14 J-7 J-21 128. 51 8. 00 120. 0000
P-15 J -13 J-18 758. 77 8. 00 120. 0000
P-16 J-12 J-15 740.46 8. 00 120.0000
P-17 J-12 J-15 675. 55 6.00 120. 0000
P-18 J -4 J-13 252. 34 8. DO 120. 0000
P-19 J -15 J-13 268. 38 8. DO 120. 0000
P-20 J-14 J-12 272. 76 8. 00 120. 0000
P-21 J-14 J-16 206 .19 8. OD 120.0000
P-22 J -7 J-17 190. 02 3.00 120. 0000
P-23 J-18 J -14 344. 02 8. OD 120. 0000
P U M P/L 0 S S E L E M E N T DAT A
THERE IS A DEVICE AT NODE
HEAD FLOWRATE
(ft) (gpm)
267.69 0. 00
203 . 08 1475. 00
34 . 43 2950.00
THERE IS A DEVICE AT NODE
HEAD FLOWRATE
(ft) (gpm)
267. 69 0. 00
221. 54 1550.00
101. 08 3100. 00
E N D N 0 D E DAT A
Carter's Crossing, Phases 1-4
Static Flow Analysis
FH-1 DESCRIBED BY THE FOLLOWING DATA:
EFFICIENCY
(%)
75. OD
75. 00
75. 00
FH-2 DESCRIBED BY THE FOLLOWING DATA:
EFFICIENCY
(%)
75. 00
75. 00
75. 00
1. 67
4. 67
0.00
3. 74
1.17
1.17
3. 34
3.17
1.65
0.92
3.17
3.17
1.67 o.oo
0.00
O. DD
O. OD
5. 24
0. DO o. 00
0.00
0.00
0. 00
(ID= 1)
(IO-2)
Page 1 of3
NODE
NAME
FH-1
FH-2
J-1
J-2
J-3
J-4
J-5
J-6
J-7
J-8
J-9
J -10
J-11
J-12
J -13
J-14
J-15
J-16
J-17
J-18
J-21
NODE
TITLE
EXTERNAL
DEMAND
lgpm)
0. 00
0. 00
1.50
0. 00
3.00
9.75
1. 50
9. 00
1. 50
6. 00 o. 00
9.00
17.25
15. 75
18. 75
0. 00
3.75 o. 00
0. 00
0 U T P U T 0 P T I 0 N D A T A
JUNCTION
ELEVATION
(ft)
256. 00
260. 00
256. 00
255. 00
256.00
256.00
253.00
250.00
258. 00
256.00
255. 00
253.00
258. 00
261. 00
258. 00
263.00
261. 00
264. 00
260.00
260.00
262. 00
EXTERNAL
GRADE
(ft)
256.00
260. 00
OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE TABULATED OUTPUT
Y S T E M C 0 N F I G U R A T I 0 N
NUMBER OF PIPES ...••...........••• (p) = 23
NUMBER OF END NODES .•...........•• ( j) • 19
NUMBER OF PRIMARY LOOPS •••••..•••. ( l) = 3
NUMBER OF SUPPLY NODES .•••••••.•.• (f) = 2
NUMBER OF SUPPLY ZONES •.•......••. (z) = l
Case:
RESULTS OBTAINED AFTER 9 TRIALS: ACCURACY = 0. 00001
S I M U L A T I 0 N D E S C R I P T I 0 N (L A B E L)
I P E L I N E RESULTS
STATUS CODE: xx -CLOSED PIPE CV -CHECK VALVE
P I P E NODE NUMBERS FLOWRATE HEAD MINOR LINE
NAM E #1 #2 LOSS LOSS VELO.
(gpm) (ft) (ft) (ft /s)
HL+ML/ HL/
1000 1000
(ft/ft) (ft/ft) -----------------------------------------------------------------------------------------
P-l FH-1 J -l
-. P-2 J-l J-4
P-3 J-3 J-2
P-4 J-4 J-3
P-5 J-3 J-5
P-6 J-2 J-6
P-7 J-7 J-4
P-8 J-8 J-7
P-9 J-10 J-8
P-10 J-9 J-10
P-11 J-9 J-8
P-12 J-11 J-9
P-13 FH-2 J-11
P-14 J-7 J -21
P-15 J-13 J-18
-P-16 J-15 J -12
P-17 J-15 J-12
P-18 J-4 J-13
-P-19 J-13 J-15
P-20 J-12 J-14
P-21 J-14 J -16
P-22 J-7 J-17
P-23 J-18 J-14
P U M P/L 0 S S ELEMENT
Carter's Crossing, Phases 1-4
Static Flow Analysis
0.00 0. 00 0. 00 0.00 0. 00 0. 00
0.00 0. 00 0. 00 0.00 0. 00 o. 00
9. 75 0.00 0. 00 0.06 0.00 0. 00
14. 25 0.00 0.00 0.09 0. 01 o. 01
3.00 0. 01 0. 00 0.14 0.06 0.05
9. 75 0 .19 0. 00 0. 44 0. 48 0. 47
75.00 0 .12 0. 01 0. 48 0.19 0.17
80. 25 o. 04 0. 01 0. 51 0.27 0.20
17. 87 0. 03 0. 00 0. 20 0.05 0.05
23.87 0 . 04 0. 00 0.27 0. 09 0. 09
71. 38 0.07 0. 01 0. 45 0.18 0.15
96. 75 0. 03 0.02 0. 62 0. 45 0.28
96.75 0.06 0. 01 0. 62 0. 33 0.28
0.00 0 . 00 0. 00 0.00 0. 00 o. 00
14. 73 0. 01 0. 00 0.09 0. 01 0. 01
6. 71 0. 00 0. 00 0. 04 0.00 0. 00
3. 31 0. 00 0. 00 0. 04 0.00 0. 00
60. 75 0. 03 0. 01 0. 39 0.17 0 .12
28. 77 0. 01 0. 00 0.18 0. 03 0. 03
l. 02 0. 00 0.00 0.01 0. 00 0. 00
0.00 0.00 0. 00 0. 00 0. 00 0.00
3. 75 0. 02 0. 00 0.17 0. 08 0. 08
14. 73 0.00 0. 00 0. 09 0.01 0.01
RESULTS
Page 2 of 3
f ~
EXHIBIT E
FIRE FLOW ANALYSIS
K Y P I P E 4
University of Kentucky Network Modeling Software
Copyrighted by KYPIPE LLC
Version 3 -11/01/2005
Date & Time: Wed May 23 09:34:30 2007
INPUT DATA FILENAME --------------F: \ 1015-S•l \ 0006-C•l \Docs\Reports\WATERS•l \ 10150006. DT2
TABULATED OUTPUT FILENAME --------F: \ 1015-S•l \ 0006-C•l \Docs\Reports\WATERS•l \ 10150006 .OT2
POSTPROCESSOR RESULTS FILENAME ---F: \1015-S•l \ 0006-C·l \Docs\Reports\WATERS•l \ 10150006. RS2
S U M M A R Y 0 F 0 R I G I N A L D A T A
U N I T S S P E C I F I E D
FLOWRATE •••••••••••• • gallons/minute
HEAD (HGL) • • • • • • • • . • = feet
PRESSURE •••••••••••• • psig
P I P E L I N E D A T A
STATUS CODE : XX -CLOSED PIPE CV -CHECK VALVE
P I P E
NAME
NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR
#1 #2 (ft) (in) COEFF. LOSS COEFF .
P-1 FH-1 J-l 234.20 l.05 119.4518 l.67
P-2 J-l J-4 234. 61 l.05 119.4518 4.67
P-3 J -3 J-2 50. 71 8. 00 120. 0000 o. 00
P-4 J-4 J-3 132. 95 8. 00 120. 0000 3. 74
P-5 J-3 J -5 209.98 3.00 120.0000 1.17
P-6 J-2 J-6 394. 35 3.00 120. 0000 l.17
~,..,, P-7 J-4 J-7 703.83 8.00 120. 0000 3.34
P-8 J-7 J-8 181. Bl 8. 00 120. 0000 3.17
P-9 J-8 J-10 584.30 6.00 120.0000 l.65
f ''
P-10 J-10 J-9 525. 35 6.00 120. 0000 0.92
P-11 J-9 J-8 428.74 8. 07 119.4518 3.17
P-12 J-9 J-11 113. 05
P-13 J-11 FH-2 213. 05
P-14 J-7 J-21 128. 51
P-15 J-13 J-18 758. 77
P-16 J-12 J-15 740.46
P-17 J-12 J-15 675. 55
P-18 J-4 J-13 252.34
P-19 J-15 J-13 268. 38
P-20 J-14 J-12 272. 76
P-21 J-H J-16 206.19
P-22 J-7 J-17 190. 02
P-23 J-18 J-14 344. 02
P U M P/L 0 S S E L E M E N T D A T A
THERE IS A DEVICE AT NODE
HEAD FLOWRATE
(ft) (gpm)
267. 69 0.00
203.08 1475. 00
34. 43 2950.00
THERE IS A DEVICE AT NODE
HEAD FLOWRATE
(ft) (gpm)
267. 69 0. 00
221. 54 1550.00
101.08 3100.00
E N D N 0 D E D A T A
Carter's Crossing, Phases 1-4
Fire Flow Anajysis
FH-1 DESCRIBED BY
EFFICIENCY
(l)
75. 00
75. 00
75.00
FH-2 DESCRIBED BY
EFFICIENCY
(%)
75.00
75. 00
75. 00
8. 00 120.0000 3.17
8.00 120. 0000 l.67
8. 00 120. 0000 o. 00
8.00 120. 0000 0. 00
8.00 120. 0000 o. 00
6. 00 120.0000 0. 00
8.00 120. 0000 5 .24
8.00 120. 0000 o. 00
8.00 120. 0000 0. 00
8. 00 120. 0000 0.00
3.00 120. 0000 0. 00
8.00 120. 0000 0. 00
THE FOLLOWING DATA: (ID= l )
THE FOLLOWING DATA: (ID= 2)
Page 1of3
NODE NODE EXTERNAL JUNCTION EXTERNAL
NAME TITLE DEMA!lll ELEVATION GRADE
(gpml (ft) (ft)
--------------------------------------------------------------
FH-1 256. 00 256. 00
FH-2 260. 00 260. 00
J-1 0. 00 256.00
J-2 0. 00 255. 00
J-3 1.50 256. 00
J-4 0. 00 256. 00
J -5 3. 00 253. 00
J-6 9. 75 250. 00
J-7 1.50 258. 00
J-8 9. 00 256.00
J-9 1. 50 255. 00
J-10 6.00 253. 00
J-11 0. 00 258.00
J-12 9. 00 261. 00
J-13 17. 25 258. 00
J-14 15. 75 263.00
J-15 1018. 75 261. 00
J-16 0. 00 264.00
J-17 3. 75 260.00
J-18 0. 00 260.00
J-21 0. 00 262. 00
0 U T P U T 0 P T I 0 N D A T A
OUTPUT SELECTION: ALL RESULTS ARE INCWDED IN THE TABULATED OUTPUT
S Y S T E M C 0 N F I G U R A T I 0 N
NUMBER OF PIPES ••...••..•...•....• (p) • 23
NUMBER OF END NODES .••..•...•....• I j I -19
NUMBER OF PRIMARY LOOPS •.••••••.•• (1) • 3
NUMBER OF SUPPLY NODES •.•...•••.•• If) • 2
NUMBER OF SUPPLY ZONES .•••••••.•.• I z) •
Case:
RESULTS OBTAINED AFTER 5 TRIALS: ACCURACY = 0. 00020
S I M U L A T I 0 N D E S C R I P T I 0 N IL A B E LI
P I P E L I N E R E S U L T S
STATUS CODE: XX -CLOSED PIPE
P I P E
N AM E
P-1
-P-2
P-3
P-4
P-5
P-6
P-7
P-8
P-9
P-10
P-11
P-12
P-13
P-14
• P-15
' P-16
P-17
P-18
'P-19
P-20
P-21
P-22
P-23
P U M P/L 0 S S
NODE NUMBERS
ill #2
FH-1 J-1
J-l J-4
J-3 J-2
J-4 J-3
J-3 J-5
J-2 J-6
J-7 J-4
J-8 J-7
J-10 J-8
J-9 J-10
J-9 J-8
J-11 J-9
FH-2 J-11
J-7 J-21
J-13 J-18
J-12 J-15
J-12 J-15
J-4 J-13
J-13 J-15
J-14 J-12
J-14 J-16
J-7 J-17
J-18 J-14
ELEMENT
Carter's Crossing, Phases 1-4
Fire Flow Analysis
CV -CHECK VALVE
FLOWRATE HEAD MINOR
LOSS LOSS
(gpm) (ft) (ft)
12.85 31.18 0.59
12.85 31.23 1. 65
9. 75 0. 00 0.00
14.25 0. 00 0.00
3.00 0. 01 0.00
9. 75 0.19 0.00
1062.15 16. 67 2.38
1067.40 4.35 2.28
245.69 3. 73 0.20
251. 69 3.51 0.12
830. 71 6. 22 1. 34
1083.90 2 .78 2. 36
1083.90 5.24 1. 24
0.00 o. 00 0.00
284. 90 1.57 0.00
174.23 o. 62 0. 00
85. 92 0.62 0.00
1060.75 5.96 3. 73
758.60 3. 41 0.00
269. 15 0. 51 0.00
0.00 0. 00 0.00
3. 75 o. 02 0. 00
284.90 o. 71 o. 00
RESULTS
LINE HL+ML/
VELO. 1000
(ft/s) (ft/ft)
4. 77 135. 65
4. 77 140.16
0. 06 0. 00
0.09 0. 01
0.14 0.06
0. 44 0. 48
6. 78 27. 08
6. 81 36. 47
2. 79 6. 73
2.86 6. 90
5. 21 17. 63
6. 92 45. 43
6.92 30. 42
0. 00 0. 00
1. 82 2. 07
1.11 0. 83
0.97 0. 91
6. 77 38.41
4. 84 12.70
1. 72 1. 86
0. 00 0.00
0.17 0. 08
l. 82 2. 07
HL/
1000
(ft/ft)
133 .13
133 .13 o. 00
0. 01
0. 05
0.47
23.69
23.91
6.39
6.68
14. 52
24.60
24.60
0. 00
2. 07
0. 83
0. 91
23.63
12.70
1. 86 o.oo
0. 08
2. 07
Page 2 of3
E N
NAME
-1
-2
FLOWRATE
(gpm)
12.85
1083.90
D N 0 D E R E S U
NODE NODE
NAME TITLE
FH-1
FH-2
J-l
J-2
J-3
J-4
J-5
J-6
J-7
J-8
J-9
J-10
J-11
J-12
J-13
J-14
J-15
J-16
J-17
J-18
J-21
INLET
HEAD
(ft)
0.00
0.00
OUTLET
HEAD
(ft)
267. 68
243.90
L T S
EXTERNAL
DEMAND
(gpm)
0. 00 o. 00
1.50
0.00
3.00
9. 75
1.50
9.00
1.50
6. 00
0.00
9. 00
17.25
15.75
1018.75
0. 00
3.75
0. 00
0. 00
PUMP
HEAD
(ft)
267 .7
243. 9
HYDRAULIC
GRADE
(ft)
523.68
503. 90
491.91
4 59. 03
4 59. 03
4 59. 03
459. 02
4 58. 64
476.09
484. 72
492.26
466.65
497.41
446.55
449. 34
4 4 7. 05
445. 93
44 7. 05
476. 07
447.77
476.09
SUMMARY 0 F INFLOW'S A N D 0 u
(+) INFLOW'S INTO THE SYSTEM FROM SUPPLY NODES
(-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES
NODE FLOW'RATE NODE
NAME (gpm) TITLE --------------------------------------------FH-1 12.85
FH-2 1063.90
NET SYSTEM INFLOW a 1096. 75
NET SYSTEM OUTFLOW • 0. 00
NET SYSTEM DEMAND a 1096. 75
..... HYDRAULIC ANALYSIS COMPLETED +++••
Carter's Crossing, Phases 1-4
Fire Flow Analysis
EFFIC-USEFUL INCREMTL TOTAL #PUMPS #PUMPS NPSH
ENCY POWER COST COST PARALLEL SERIES Avail.
(\) (Hp) ($) ($) (ft)
33.2
33.2
NODE PRESSURE NODE
ELEVATION HEAD PRESSURE
(ft) (ft) (psi)
256.00 267. 68 116. 00
260.00 243. 90 105. 69
256. 00 235.91 102.23
255. 00 204. 03 66.41
256.00 203.03 67 .98
256. 00 203. 03 67. 98
253. 00 206. 02 69. 27
250. 00 208. 84 90. 50
256.00 220. 09 95 . 37
256.00 228. 72 99 .11
255. 00 237. 28 102. 82
253. 00 235. 65 102 .12
256. 00 239. 41 103. 75
261. 00 185.55 80 .40
256. 00 191. 34 82 . 91
263. 00 184. 05 79.76
261. 00 184. 93 60.14
264 . 00 183. 05 79.32
260. 00 21 B. 07 94.50
260. 00 187. 77 Bl. 37
262.00 216.09 93. 64
TFLOW'S
Page 3 of3
Line Area of Contributing Lond Uses "' "' M s d -a >->->-'8 !>: z . ., ]U ]u ]u ll ii !'! 8 8 ~ '8 From To "' "'!'! "'!'! 18 ~ ii "':::> ":::> ":::> 0 ~z "Q ]'Q ]'Q ·13 0. <>! ]' ~ ":::> VJ VJ 8 !i VJ !>: otl 267 401 534 801 50 35 GPDper GPDper GPDper GPDper GPDper GPDper MH# MH# Lot Acre Acre Acre Person Person GPD Car1ers Crossing Sewer Lines I 5 36 0 0 0 0 0 9,612 -2 4 23 0 0 0 0 0 6,141 -3 4 14 0 0 0 0 0 3,738 ... 4 5 8 0 0 0 0 0 2,136 9,879 •lo 5 7 3 0 0 0 0 0 801 21,627 6 7 5 0 0 0 0 0 1,335 --~ 7 13 6 0 0 0 0 0 1,602 23,763 8 12 13 0 0 0 0 0 3,471 9 11 7 0 0 0 0 0 1,869 10 II 8 0 0 0 0 0 2,136 II 12 6 0 0 0 0 0 1,602 4,005 12 13 3 0 0 0 0 0 801 9,078 ExhibitG Carters Crossing Phases 1-4 Sanitary Sewer Analysis Flow Calculations '~ Average Daily Flows Infiltration Peaking Peak Inside Size Material (ADF) (IOo/oADF) Factor Flows Diameter GPD CFS CFS CFS (m.) Inches 9,612 0.0149 0.0015 4.00 0.06 8 03034 7.754 6,141 0.0095 0.0010 4.00 0.04 8 03034 7.754 3,738 0.0058 0.0006 4.00 O.Q2 6 03034 5.793 12,015 0.0186 0.0019 4.00 0.08 8 03034 7.754 22,428 0.0347 0.0035 4.00 0.14 8 03034 7.754 1,335 0.0021 0.0002 4.00 0.01 8 03034 7.754 25,365 0.0392 0.0039 4.00 0.16 8 03034 7.754 3,471 0.0054 0.0005 4.00 0.02 8 03034 7.754 1,869 0.0029 0.0003 4.00 0.01 8 03034 7.754 2,136 0.0033 0.0003 4.00 0.01 8 03034 7.754 5,607 0.0087 0.0009 4.00 0.04 8 03034 7.754 9,879 0.0153 0.0015 4.00 0.06 8 03034 7.754 Manning Min. Friction Design Slope Slope ADF ADF % % 0.0009 0.40 0.0004 0.40 0.0006 0.80 0.0013 0.40 0.0047 0.40 0.0000 0.40 0.0060 0.40 0.0001 0.40 0.0000 0.40 0.0000 0.40 0.0003 0.40 0.0009 0.40 PipeC culations ,,_, Manning Min. Ave. Daily Ave. Daily Friction Design Flow Flow Slope Slope Velocity Depth Peak Peak Flows Flows Ii>• Inches % % 0.85 0.39 0.0030 0.40 0.74 0.00 0.0012 0.40 0.86 0.00 0.0021 0.80 0.91 0.78 0.0047 0.40 1.12 1.16 0.0163 0.40 0.45 0.00 0.0001 0.40 1.18 1.16 0.0208 0.40 0.63 0.00 0.0004 0.40 0.45 0.00 0.0001 0.40 0.56 0.00 0.0001 0.40 0.74 0.00 0.0010 0.40 0.85 0.39 0.0032 0.40 Actual Slope for Pipe Existing Slope or Check Designed Systems % 0.40 OK 0.40 OK 0.80 OK 0.40 OK 0.40 OK 0.40 OK 0.40 OK 0.40 OK 0.40 OK 0.40 OK 0.40 OK 0.40 OK Peak Peak Flow Flow Velocity Depth fps 1.28 1.15 1.30 1.37 1.68 0.69 1.72 0.96 0.78 0.82 1.12 1.28 inches 1.16 1.16 0.87 1.55 2.33 0.00 2.33 0.78 0.39 0.39 1.16 1.16 6/812007 Exhibit F
!VicCLURE & RROV\TNE ENGINEERL 1G /SURVEYING~ INC,
1008 \Voockreek D1i1·e, Suite 103 •College Station, Texas 7784;
(979) 693-3838 •Fax (979) 693-2554-•Erna.ii :mcclurebrmrne@rnizon.net
June 18, 2007
Mr. Louis C. Herrin, III, P .E .
TCEQ-MC 148
P. 0 . Box 13087
Austin, TX 78711-3087
Re: Chapter 317 Summary Transmittal Letter
Permittee: City of College Station
Permit Number: TPDES WQOO 10024006
Project Name: Carter's Crossing Subdivision, Phases 1 - 4
County: Brazos County
MBESI #1015-0006
Dear Mr. Herrin:
The purpose of this letter is to provide the TCEQ with the information necessary to comply with the
requirements of §317.1 (a)(3)(D) of the TCEQ' s rules titled, Design Criteria for Sewerage Systems.
The necessary information includes:
1. Engineering Firm: McClure & Browne Engineering/Surveying, Inc.
1008 Woodcreek Drive, Suite 103
College Station, Texas 77845
2. Design Engineer: Jeffery L. Robertson, P.E. No. 94745
3. Facility Owner: City of College Station, Brazos County, Texas
4. The plans and specifications which describe the project identified in this letter are in
substantial compliance with all requirements of Chapter 317.
5. Project Description: The wastewater improvements that are detailed within this project are
located within the City of College Station in Brazos County, Texas,
and are designed to connect to the existing wastewater collection
system. The project involves the extension of an existing sewer line
into a new subdivision located near the intersection of Appomattox
Drive and North Forest Parkway. The project consists of eight new
gravity wastewater lines and their associated appurtenances.
Wastewater from this subdivision will flow to the Carters Creek
Wastewater Treatment Plant. The following is a general description
of the new collection system:
· .. Mr. Louis C. Herrin, III, P .E.
June 19, 2006
Page 2
Gravity Wastewater Lines:
Number of Lots: Residential: 140
Amount/Type of Wastewater Pipe to be Installed:
Pipe Size
(in.) Material
8 ASTM D3034, SDR 26 PVC
8 ASTM D224 l, SDR 26 PVC
8 CL 350 DJP
6 ASTM D3034, SDR 26 PVC
6 ASTM D2241 , SDR 26 PVC
Number of Manholes: 29
Linear
Feet
5218
140
955
157
20
Distance between manholes range from 49 LF to 449 LF.
Grade(%)
Min. Max.
0.40 0.40
0.40 0.40
0.40 0.40
0.80 0.80
0.80 0.80
The plans will be reviewed by the City of College Station and they will also provide construction
inspection. If you have any questions regarding this project, please contact me at (979) 693-3838.
Very truly yours,
j{i~~t~ .............. "' ............ \."" .... \.,~
__ ...-..:~ ~ OF r~''i't\1 -;(~ ......... ~ ... 1. : e;,' ...-~·· .. -~IS' 'I ;' * ..... ·· ... 1C ,, ~ * .... b/1~ 26o"7\ * ~ ~ ....................................... /. ~ JEFFERY L. ROBERTSON ~ ~·····:···························: .. ···~ ~ -0\ 94745 /$ ~ 11i··.. /~;' 11t ~··/1CENS~~.·;...ff ;-lil\~'5'sio'N·~·"·" ~~~ \\\.-.,'\: pl,·