HomeMy WebLinkAboutWater Line AnalysisREDMOND SHOPPING CENTER IN COLLEGE STATION WATER LINE ANALYSIS March 2013 PREPARED FOR: REDMOND SHOPPING CENTER IN COLLEGE STATION RICHARD RAINER, BKXL 6363 WOODWAY, SUITE 950 HOUSTON, TX 77055 Submitted to Cl� F COLLEGE STATION the heart ofthe Research Valley By M ITCH ELL MORGAN ENGINEERS $ CONSTRUCTORS 511 UNIVERSITY DRIVE, SUITE 204 COLLEGE STATION, TX 77840 OFFICE (979) 260-6963 FAx (979) 260-3564 CERTIFICATION This report for the water design for Redmond Shopping Center in College Station was prepared under my supervision in accordance with provisions of the Bryan/College Station Unified Design Guidelines for the owners of tbooMftdv. Veronica J.B. Morgan, P.E., C.F.I\ Registered Professional Engineer State of Texas No. 77689 Redmond Shopping Center in College Station Page 1 WATERLINE ANALYSIS REDMOND SHOPPING CENTER MARCH 2O13 INTRODUCTION Redmond Shopping Center (RSC) will be located in College Station, Texas, at the address 1530 Texas Ave. at the intersection of Texas Ave. and Redmond Dr., across Texas Avenue from the Central Station Shopping Center. The proposed development will be a single general commercial facility with multiple tenants. The overall site plan is provided in Exhibit 1. FIREFLOW DESIGN CRITERIA An updated City of College Station system MikeURBAN model was used. In order to determine if this model was calibrated two runs were performed. 1. Run 1 —Average Day Conditions without RSC's Development (Exhibit 6) 2. Run 2 —Average Day Conditions without RSC's Development and Fire Flow at Node 6000 (Exhibit 7) The results from these runs were compared to a fire flow pressure test performed by City of College Station Utilities (Exhibit 9). Based on the output it was determined that the model slightly underestimates pressures when compared to those measured in the field. As a result the model is considered to be conservative in predicting pressures within the water distribution system. A comparison of measured and modeled values can be found in Table 1. Table 1 - Calibration Results FLOW HYDRANT Measured Modeled Node Number 6000 Nozzle size 2.5 Pilot reading in PSI 72 81.8 Flow in G.P.M. 1435 STATIC HYDRANT Measured Modeled Node Number 490 Static PSI 104 97.8 Residual PSI 96 90.9 The demands utilized for this analysis were based upon the flow demands estimated by the MEP engineer using fixture units within the building. Table 2 illustrates how the water demands were calculated. 2edmond Shopping Center in College Station Page 2 Table 2 - Water Line Demand Data Avg Peak Use Area (SF) Demand Demand (gpm) (gpm) Commercial 9,181 28 110.0 This water demand was allocated to Node 'RedmondNode2' in the model, while Table 3 shows the water line information (size, length, connectivity) for the model. The corresponding MikeURBAN line and node identifiers are provided in Exhibit 2. Table 3 - Water Line Length Data Pipe From Node To Node Length (ft) Size (in) Number/Name RedmondSu 16 RedmondNode1 1 RedmondNode2 501 6 RedmondFire6 RedmondNode2 RedmondNode3 38.5 6 Redmond Shopping Center consists of an 8,640 SF structure and 541 SF outdoor patio equaling a total of 9181 SF. RSC will be constructed using Type 1113 construction and will contain a fire suppression system. Based upon Table B105.1 of the 2012 International Fire Code (Exhibit 8) the required fire flow for this facility is 2,000 gpm. This flow can be reduced by 50 percent due to of the presence of a fire suppression system. The minimum required fire flow of 1500 gpm was used when modeling the system. To simulate the fire flow for the building, we placed a 750 gpm fire flow at Node 'RedmondNode3' and another 750 gpm at Node'464'. Node'464' is an existing fire hydrant located on the south side of Redmond Dr. shown on Exhibit 2. The results from the run show that the current and proposed waterlines will sufficiently serve the fire flow needs of Redmond Shopping Center, keeping pressures in the proposed waterlines above 20 psi, and velocities at or below 12 fps. Redmond Shopping Center in College Station Page 3 ATTACHMENTS EXHIBIT 1: EXHIBIT 2: EXHIBIT 3A: EXHIBIT 3B: EXHIBIT 4A: EXHIBIT 4B: EXHIBIT 5A: EXHIBIT 5B: EXHIBIT 6: EXHIBIT 7: EXHIBIT 8: EXHIBIT 9: Overall Site Layout MikeURBAN Node and Link Identifier Map Proposed Average Day Conditions with RSC — Junction Results Proposed Average Day Conditions with RSC — Pipe Results Proposed Peak Day Conditions with RSC — Junction Results Proposed Peak Day Conditions with RSC — Pipe Results Proposed Peak Day and Fire Flow Conditions for RSC — Junction Results Proposed Peak Day and Fire Flow Conditions for RSC — Pipe Results Calibration Run — Static Results Calibration Run — Residual Results Table B105.1 of the 2012 International Fire Code College Station Hydrant Data Redmond Shopping Center in College Station Page 4 EXHIBIT 2 MikeURBAN Site Layout R.dmmdNod.3 monfflodO wL!kn-1 --J16dmondode' dmOn EXHIBIT 3A MikeURBAN Node Identifiers Description: Steady State Analysis Proposed Average Day Demand on System Node Results Name Demand (BPrn) Pressure (Psi) 388 0.00 95.87 390 2.58 95.75 393 0.00 96.00 397 0.00 95.92 401 0.74 96.51 412 0.00 96.07 413 0.00 96.07 428 11.67 96.07 447 0.03 97.62 452 0.21 96.97 463 0.27 99.55 464 0.01 98.17 465 0.00 99.55 471 2.31 97.59 472 1.89 97.68 473 0.20 97.80 490 11.99 97.80 491 0.10 98.69 510 0.21 97.32 515 0.00 97.42 516 4.86 98.34 517 0.00 96.96 527 0.00 97.21 531 0.00 96.97 535 0.00 96.40 536 0.00 96.19 540 0.06 97.03 542 0.00 96.64 550 0.10 94.11 552 0.00 93.21 553 0.00 96.84 Exhibit 3A Node Results Name Demand (gpm) Pressure (psi) 556 3.05 96.64 557 0.00 93.27 562 0.11 96.61 563 0.00 96.61 RedmondNodel 0.00 97.80 RedmondNode2 27.50 97.61 RedmondNode3 0.00 96.98 Exhibit 3A 2 EXHIBIT 3B MikeURBAN Link Identifiers Description: Steady State Analysis Proposed Average Day Demand on System Link Results' Name Velocity (ft/s) Headioss/1000 (ft) Roughness (millift) Friction Factor 112 0.62 0.13 120 0.03 117 0.75 0.79 100 0.05 160 0.27 0.07 135 0.03 166 0.03 0.00 125 0.04 218 0.58 0.08 130 0.02 2439 0.00 0.00 130 0.00 2440 0.24 0.02 120 0.03 2708 0.00 0.00 100 0.00 2788 0.16 0.04 90 0.07 2845 0.29 0.03 140 0.02 2846 0.60 0.09 130 0.02 3168 0.24 0.02 120 0.03 3173 0.73 0.17 110 0.03 3245 0.73 0.29 140 0.02 3252 0.18 0.01 140 0.03 3253 1.04 0.25 130 0.02 3255 0.96 0.21 130 0.02 3256 0.00 0.00 140 0.00 3296 0.24 0.02 120 0.03 3297 0.24 0.02 130 0.04 3298 0.96 0.21 130 0.02 3299 0.73 0.17 110 0.03 3315 0.00 0.00 130 0.00 3316 0.11 0.03 90 0.07 3318 0.19 0.05 120 0.04 3319 0.65 0.14 120 0.03 3320 0.63 0.13 120 0.03 3321 0.37 0.21 100 0.05 3323 0.17 0.05 100 0.06 3324 0.03 0.00 100 0.08 3325 0.03 0.00 140 0.00 IM.Jif[M Link Results Name Velocity (ft/s) Headloss/3000 (ft) Roughness (millift) Friction Factor 3326 0.36 0.05 140 0.02 3327 0.31 0.04 140 0.02 3328 0.21 0.04 140 0.03 3329 0.32 0.04 140 0.02 3331 0.76 0.16 130 0.02 3332 0.16 0.01 110 0.04 3333 0.21 0.09 90 0.07 3335 0.76 0.18 120 0.03 3482 0.90 0.19 130 0.02 3703 0.35 0.11 135 0.03 3713 0.74 0.18 110 0.03 3832 0.05 0.00 90 0.07 3834 0.11 0.01 130 0.02 696 0.06 0.00 135 0.04 734 0.36 0.08 140 0.03 740 0.37 0.08 140 0.03 878 0.24 0.12 90 0.06 897 0.75 0.53 125 0.03 RedmondFire6 0.00 0.00 150 0.00 RemondSupply6 0.31 0.07 150 0.02 wUnk 1 0.20 0.08 90 0.07 Exhibit 3B EXHIBIT 4A MikeURBAN Node Identifiers Description: Steady State Analysis Proposed Peak Day Demand on System Node Results Name Demand (gpm) Pressure (psi) 388 0.00 80.76 390 10.31 80.63 393 0.00 80.87 397 0.00 80.80 401 2.98 81.40 412 0.00 81.58 413 0.00 81.56 428 46.69 81.36 447 0.12 84.25 452 0.86 81.88 463 1.09 87.04 464 0.06 84.47 465 0.00 87.04 471 9.22 82.55 472 7.56 82.63 473 0.80 83.60 490 47.96 83.27 491 0.40 84.49 510 0.86 86.11 515 0.00 86.36 516 19.42 92.93 517 0.00 86.04 527 0.00 86.81 531 0.00 86.57 535 0.00 86.16 536 0.00 85.94 540 0.23 87.97 542 0.00 87.58 550 0.40 83.67 552 0.00 82.72 553 0.00 90.63 Exhibit 4A Node Results Name Demand (Bpm) Pressure (Psi) 556 12.20 91.24 557 0.00 82.78 562 0.46 91.22 563 0.00 91.21 RedmondNodel 0.00 83.52 RedmondNodel 110.00 83.31 RedmondNode3 0.00 82.68 Exhibit 4A EXHIBIT 4B MikeURBAN Link Identifiers Description: Steady State Analysis Proposed Peak Day Demand on System Link Results; Name Velocity (ft/s) Headloss/1000 (ft) Roughness (millift) Friction' Factor 112 0.73 0.17 120 0.03 117 1.01 1.23 100 0.04 160 0.85 0.57 135 0.03 166 0.12 0.01 125 0.04 218 12.04 22.96 130 0.02 2439 0.00 0.00 130 0.00 2440 3.43 2.60 120 0.02 2708 0.00 0.00 100 0.00 2788 2.61 6.88 90 0.04 2845 0.69 0.16 140 0.02 2846 11.48 21.04 130 0.02 3168 3.43 2.60 120 0.02 3173 11.18 27.26 110 0.02 3245 4.29 7.62 140 0.02 3252 2.58 1.86 140 0.02 3253 6.60 7.54 130 0.02 3255 7.75 10.15 130 0.02 3256 0.00 0.00 140 0.00 3296 3.43 2.60 120 0.02 3297 3.43 2.24 130 0.02 3298 7.75 10.15 130 0.02 3299 11.17 27.26 110 0.02 3315 0.00 0.00 130 0.22 3316 1.50 3.44 90 0.05 3318 1.74 2.66 120 0.03 3319 1.11 0.37 120 0.03 3320 0.86 0.23 120 0.03 3321 0.42 0.27 100 0.05 3323 1.35 2.33 100 0.04 3324 1.88 4.30 100 0.04 3325 1.88 2.31 140 0.02 Exhibit 4B Link Results'' Name Velocity (ft/s) Headloss/1000 (ft) Roughness (millift) Friction Factor 3326 5.37 7.20 140 0.02 3327 4.68 5.58 140 0.02 3328 2.76 4.71 140 0.02 3329 4.21 4.59 140 0.02 3331 1.23 0.39 130 0.02 3332 2.39 1.56 110 0.03 3333 2.76 10.67 90 0.05 3335 1.25 0.46 120 0.03 3482 5.75 5.85 130 0.02 3703 0.20 0.04 135 0.03 3713 3.37 2.95 110 0.03 3832 0.20 0.06 90 0.06 3834 2.81 4.00 130 0.02 696 0.96 0.71 135 0.02 734 2.10 2.02 140 0.02 740 2.19 2.19 140 0.02 878 0.95 1.49 90 0.05 897 1.01 0.82 125 0.03 RedmondFire6 0.00 0.00 150 0.00 RemondSupply6 1.25 0.95 150 0.02 wlink 1 2.74 10.57 90 0.05 [MSf M, .1 EXHIBIT 5A MikeURBAN Node Identifiers Description: Steady State Analysis Proposed Peak Day Demand on System with Fire Flows Placed on Nodes `RedmondNode3' and `464'. Node Results Flame Demand (gPm) Pressure' (psi) 388 0.00 77.88 390 10.31 77.72 393 0.00 77.96 397 0.00 77.89 401 2.98 78.49 412 0.00 78.55 413 0.00 78.53 428 46.69 78.36 447 0.12 81.01 452 0.86 78.97 463 1.09 84.70 464 750.06 73.91 465 0.00 84.69 471 9.22 79.04 472 7.56 79.31 473 0.80 71.31 490 47.96 72.16 491 0.40 72.20 510 0.86 84.27 515 0.00 84.55 516 19.42 92.12 517 0.00 84.26 527 0.00 85.17 531 0.00 84.93 535 0.00 84.55 536 0.00 84.33 540 0.23 86.56 542 0.00 86.17 550 0.40 82.06 552 0.00 81.11 Exhibit 5A Node Results Name Demand (Bpm) Pressure' (psi) 553 0.00 89.69 556 12.20 90.43 557 0.00 81.17 562 0.46 90.41 563 0.00 90.39 RedmondNodel 0.00 70.94 RedmondNode2 110.00 69.81 RedmondNode3 750.00 68.62 Exhibit 5A 2 EXHIBIT 5B MikeURBAN Link Identifiers Description: Steady State Analysis Proposed Peak Day Demand on System with Fire Flows Placed on Nodes `RedmondNode3' and `464'. Link Results Name Velocity W/O Headloss/1000 (it) Roughness (miliiit) Friction Factor 112 1.29 0.49 120 0.03 117 1.46 2.72 100 0.04 160 4.20 10.98 135 0.02 166 0.12 0.01 125 0.04 218 12.99 26.42 130 0.02 2439 0.00 0.00 130 0.00 2440 3.43 2.60 120 0.02 2708 0.00 0.00 100 0.00 2788 2.79 7.78 90 0.04 2845 0.58 0.12 140 0.02 2846 12.40 24.24 130 0.02 3168 3.43 2.60 120 0.02 3173 12.14 31.77 110 0.02 3245 4.52 8.39 140 0.02 3252 2.39 1.60 140 0.02 3253 7.65 9.92 130 0.02 3255 8.71 12.61 130 0.02 3256 0.00 0.00 140 0.00 3296 3.43 2.60 120 0.02 3297 3.43 2.24 130 0.02 3298 8.71 12.61 130 0.02 3299 12.14 31.77 110 0.02 3315 0.00 0.00 130 0.00 3316 3.55 17.05 90 0.04 3318 1.82 2.91 120 0.03 3319 1.11 0.37 120 0.03 3320 0.85 0.23 120 0.03 3321 0.69 0.67 100 0.05 3323 1.17 1.79 100 0.04 3324 1.70 3.58 100 0.04 Exhibit 513 Link Results Name Velocity NO Headloss/1000 (ft) Roughness (millift) Friction i Factor 3325 1.70 1.92 140 0.02 3326 7.89 14.68 140 0.02 3327 4.20 4.58 140 0.02 3328 14.73 104.85 140 0.02 3329 3.78 3.76 140 0.02 3331 1.30 0.43 130 0.02 3332 3.51 3.18 110 0.03 3333 6.22 48.14 90 0.04 3335 1.32 0.51 120 0.03 3482 6.76 7.88 130 0.02 3703 1.21 1.09 135 0.02 3713 3.25 2.77 110 0.03 3832 0.20 0.06 90 0.06 3834 2.99 4.48 130 0.02 696 3.08 6.18 135 0.02 734 2.21 2.23 140 0.02 740 2.30 2.41 140 0.02 878 4.10 22.20 90 0.04 897 1.46 1.80 125 0.03 RedmondFire6 8.51 33.40 150 0.01 RemondSupply6 9.76 43.03 150 0.01 wUnk 1 6.21 47.94 90 0.04 Exhibit 5B 2 EXHIBIT 6 MikeURBAN Node Identifiers Description: Steady State Analysis Current Demand on System Node Results Static Name Demand (gpm) Pressure (psi) 388 0.00 95.88 390 2.58 95.76 393 0.00 96.01 397 0.00 95.93 401 0.74 96.51 412 0.00 96.07 413 0.00 96.07 428 11.67 96.07 447 0.03 97.62 452 0.21 96.98 463 0.27 99.55 464 0.01 98.18 465 0.00 99.55 471 2.31 97.60 472 1.89 97.69 473 0.20 97.82 490 11.99 97.82 491 0.10 98.70 510 0.21 97.33 515 0.00 97.42 516 4.86 98.34 517 0.00 96.96 527 0.00 97.22 531 0.00 96.98 535 0.00 96.40 536 0.00 96.19 540 0.06 97.03 542 0.00 96.64 550 0.10 94.12 552 0.00 93.22 553 0.00 96.84 Exhibit 6 Node Results Static Name Demand (gpm) Pressure (psi) 556 3.05 96.65 557 0.00 93.27 562 0.11 96.61 563 0.00 96.61 6000 0.00 97.66 Exhibit 6 EXHIBIT 7 MikeURBAN Node Identifiers Description: Steady State Analysis Current Demand on System with 1435 gpm Fire Flow at Node 6000 Node Results Residual Name Demand (gpm) Pressure (psi) ; 388 0.00 95.03 390 2.58 94.90 393 0.00 95.15 397 0.00 95.07 401 0.74 95.66 412 0.00 95.28 413 0.00 95.28 428 11.67 95.26 447 0.03 96.93 452 0.21 96.08 463 0.27 99.09 464 0.01 96.22 465 0.00 99.09 471 2.31 93.40 472 1.89 94.59 473 0.20 94.02 490 11.99 90.88 491 0.10 94.91 510 0.21 97.01 515 0.00 97.11 516 4.86 98.22 517 0.00 96.67 527 0.00 96.95 531 0.00 96.71 535 0.00 96.15 536 0.00 95.94 540 0.06 96.81 542 0.00 96.42 550 0.10 93.86 552 0.00 92.96 Exhibit 7 Node Results Residual Name Demand (gpm) Pressure (psi) 553 0.00 96.70 556 3.05 96.52 557 0.00 93.02 562 0.11 96.49 563 0.00 1 96.49 6000 1435.00 11 81.87 Exhibit 7 2 APPENDIX TABLE BIOISA MINIMUM REQUIRED FIRE -FLOW AND FLOW DURATION FOR BUILDINGS FlR9-FLOW EabUl AREA (quan 1M) PRE -FLOW (patbna Par mi, rftr i FLOW DURATION (roara) Type IA W4 !' Type MA WA IRA' Type IV and V-A' Typo 0 wo M!' Tip v-r 0-22,7 0.12,700 0-8,200 0-5,900 0.3,600 1,500 22,701-30,200 12,701-17,000 8,201-10,900 5,901-7,900 3.6014,800 1,750 i 30,201-39,700 17,001-21,900 10,901-12,900 7,90I-9,11W 4.801.6,200 2,000 38,70148,300 21.801.24,200 12,901.17,400 9,801-12,600 6201-7.700 2.250 2 48,301-59,000 24.301.33,200 17,401-21.300 12.601-15.400 7,701.9,400 2-5W 59,001-70,900 33,201-39,700 21,301-25,500 15,401-18,400 9.401-11,300 2,750 i 70,901.93,700 39,70I47,100 25,501-30,100 18,401-21,800 11,301-)3,400 3,000 83,70147,700 47,101-34,900 30,101.35,200 21,901.25.900 13,401-15.600 3,250 97,701-1M700 54,901.63AM 35,201.40,600 25,901-29,300 1SA01-18,000 3,500 3 112,701-128,700 63.401-72400 460146,400 29,301-31LM 1901-20AM 3,750 128,701-145,9DO 77,401.82,100 46,401-32,500 33,501-37,"0 20,601-23,300 4,0D0 145,901-164,200 82,IOI.92,400 52,SOI-59.101) 37.90142,700 23,301-26,300 4,250 164,201-183,400 92,401-103,100 59,101-66A00 42,701-47,700 26,301-29,300 4,500 - 183,401-203,700 103.101-114,600 66,001.73,300 47.701-33,000 29.301-32,600 4.750 203.701-225.200 114,601.126,700 73,30141,100 53.001-50m 32,601-36,000 5,000 225,201-247,700 126,701-139.400 81,101-89,200 58,601.65,400 36.001-39,600 5,250 247,701-271,200 139,401-152.600 89,201-97,700 65,401-70,600 39,60143.400 5,500 271,201-29 152,60 1 - 166.5W 97,701-106,500 70,601-77,0D0 43,40147,400 5,750 295,901 166.501-Qe 106,501-115,800 77,001-83300 47,401-S1,500 6,000 4 — — 115,801.125,500 93.70 1 -90,60PO 51.301-55,700 6,250 — — 125,501-135,500 90,60147,900 55,701-60.2.00 6,500 — — 135XI-145,M10 97,901-i06,Mp 60,201b4,800 6,750 — — 145.801-156.700 106,801-I13,200 , 64,901-69.600 7,000 — — 156.701.167,900 113,201,121.300 69.601-74,600 7,250 — — 167,901.179,400 121,301-129A00 74,601-79,900 7,500 — — 179.401-191.400 129,601-136,2BD 79,iM4WIGO 71730 i — — 191,406Cm W 138,301-Greaser 95,101-Grater 8,000 For SI: I squm leaf - 0" m2, I Vilna pa miaule . 3385 Um, I pmw pa hquare 6rd + 6.M kPa. a. Types of wmblmtlodm bred W do lmsanrla,nl Bwidims Cods. b. Mavuml al 20 phi ro@ Wl Wam. EXHIBIT 8 2012 INTERNATIONAL FILE COW EXHIBIT 9 Description: Calibration data for Node 6000 from College Station Utilities (UfCollege Station Utilities Reliable, Affordable, Community Owned Date test completed Tuesday September 3. 2012 Time completed 10:30 A.M. Test completed by Vincent Rodriquez Witness Justin Tamplin FLOW HYDRANT Location 306 Redmond Nozzle size 2.5 Hydrant number J-074 Pitot reading in PSI 1435 Flow in G.P.M. 72 HYDRANT Location Hydrant number Static PSI Residual PSI Comments 306 Redmond J-076 104 Requested