Loading...
HomeMy WebLinkAboutFire Hydrant Flow ReportExhibit B SCHULTZ ENGINEERING, LLC FIRM #12327 WATER SYSTEM FIRE HYDRANT FLOW TEST REPORT Date: 10/12/2012 Water System Owner: Wellborn SUD Development Project: South Brazos County Fire Station Flow Test Location: Hydrant installed for the South Brazos County Fire Station Nozzle size (in.): 2.5" Pitot Reading (psi): 70 Flowrate (gpm): 1404 Discharge Coeff: (c) = 0.90 Flowrate Formula: Q=29.84c&pv2 c = discharge coeff. d = orifice size (in) P = pitot pressure (psi) Pressure Gauge Location: Across parking lot from worship center. Static Pressure (psi): 82 Residual Pressure (psi): 65 Computed Discharge at 20 psi Residual Pressure: QR = 2824 gpm Discharge Formula: QR = OF X (hr0.54/hf .54) --------------------------------------------------------------------------------------------- Note: The flow test and report were prepared in accordance with NFPA 291. Report Prepared by: Ricky Flores Others Present: Clenden Adams F-12327 SCHULTZ ENGINEERING. LLC. ,S./ Z