HomeMy WebLinkAboutWater Report'/:.?: C1VIL DEVELOPMENT, Lta.1:-?:
CIVIL ENGINEERING & DESIGN-BUILD SERVICES
P.O. Box 11929 · College Station, Texas 77842 · Phone: 979-764-7743 · Fax: 979-764-7759
October 3, 2008
Alan Gibbs, P.E.
City of College Station
P.O. Box 9960
College Station, TX 77842
RE: Water Analysis and Report
Oxford Court Office Building
Lot 4 Block 11 , Castlerock Subdivision, Ph 1 B
College Station, Texas
Dear Alan:
The Oxford Court Office Building is planned for Lot 4, Block 11 of the
Castlerock Subdivision, Ph 1 B. When that subdivision was developed, the water system
was analyzed to determine if sufficient water fiow and ressure was available for fire
demands on these commercial lots. co y of that water re ort is attach The fire flow
used in that analysis was 2500 gpm at the hydrant across the entry driveway from this lot.
The Oxford Court Office Building will lfave 4200 square feet of enclosed area.
We do not yet know the building type that would allow us to determine the actual fire
flow rate required by the International Fire Code. However, if we assume the most
conservative figure using a Building Type V-B1 a building of this size would require
1750 gpm and one hydrant (International Fire Code Tables Bl 05. I and Cl 05.1). Since
our system was analyzed using a fire flow rate of 2500 gpm, we conclude that the water
system is easily capable of serving this building. No additional water report will be
submitted for this development.
Sincerely Yours,
/~~
Kent Laza, P.E.
Project Manager
Bathroom Group
Bathroom Group
Bathtub
Bathtub
Bidet
Combination fixture
Dishwashing machine
Drinking fountain
Kitchen sink
Kitchen sink
Laundry trays (1 to 3)
Lavatory
Lavatory
Service sink
Shower head
Shower head
Urinal
Urinal
Urinal
Washing machine (8 lbs)
Washing machine (8 lbs)
Washing machine (15 lbs)
Water closet
Water closet
Water closet
Water closet
Water closet
Oxford Court Office Building
Summary of Fixture Unit Computations
Total Load per
Fixture Type (from Plumbing Code) fixture
(wsfu)
Private Flush tank 3.60
Private Flush valve 8.00
Private Faucet 1.40
Public Faucet 4.00
Private Faucet 2.00
Private Faucet 3.00
Private Automatic 1.40
Offices, etc. 3/8" valve 0.25
Private Faucet 1.40
Hotel, restaurant Faucet 4.00
Private Faucet 1.40
Private Faucet 0.70
Public Faucet 2.00
Offices, etc. Faucet 3.00
Public Mixing valve 4.00
Private Mixing valve 1.40
Public I" flush valve 10.00
Public 3/4" flush valve 5.00
Public Flush tank 3.00
Private Automatic l.40
Public Automatic 3.00
Public Automatic 4.00
Private Flush valve 6.00
Private Flush tank 2.20
Public Flush valve 10.00
Public Flush tank 5.00
Public or private Flushometer tank 2.00
Fixture Fixture Total
Count -1st Count-Total Fixture
Fir 2nd Fir Count Units
2 2 7.2
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
I 1 0.3
I I l.4
0 0.0
0 0.0
0 0.0
0 0.0
I I 3.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
0 0.0
TOT AL FIXTURE COUNT = 11.85
Flowrate (from Plumbing Code -Table E102) =
Recommended Meter Size =
16 gpm
3/4"