RE: Culpepper Plaza Redevelopment Fireflow Report
Dear Josh:
November 10, 2006
Below is the water ana lysis for the Culpepper Plaza Redevelopment. The largest area between
firewall s will be Kohl 's department store, encompassing approximately 68, 77 5 square feet. Kohl's
will be equipped with an automatic sprinkler system and constructed of building type ll lB, requiring
a fireflow of 2750 gpm as required by the 2000 International Fire Code with a 50% sprinkler
reduction . An excerpt of the 2000 International Fire Code is provided as Exhibit 1.
The updated City of College Station water system MikeNET model was checked against hydrant
flow tests near Culpepper Plaza. Please see Exh ibit 2A for flow test results. At this time the exact
locations of the flow and static hydrants are not know, so a comparison was made between the
model results in the general vicinity and the flow tests. See Exhibit 2B for static conditions model
results and Exhibit 2C for residual conditions model results. It was found that model results were
similar to those found by flow test differential between static and residual conditions, but overall
the model showed pressures about 20 psi higher for both conditions. Because of this discrepancy
pressures under fireflow conditions will be assumed adequate over 40 psi .
Us ing the updated City of College Station water system MikeNET model, flows and pressures were
calculated in the adjacent li nes. Please see Exhibit 3 for model results. It was found that a new eight
inch (8") waterline and hydrant as well as the existing waterlines and hydrants in the area w ill
sufficiently serve the water needs of the Culpepper Plaza Redevelopment. Fireflow conditions
maintained velocities below 12 fps and pressure at or above 40 psi.
If you have any comments, or would like to discuss our f indings further, please feel free to contact
cc: Dan Muniza
S:\Proj\0553-Culpepper_Redevelopment\Docs\0553-fireflow-report-06111 O.doc
511 UNIVERSITY DRIVE EAST, SUITE 204 • COLLEGE STATIOf'J, TX 77840 • T 979.260.6963 • F 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • U11LITIES • STREETS • SITE PLANS • SUBDIVISIONS
mfo@mitchellandmorgan.com • www.mitchellandmorgan.com
7TMPBIDIXB i/ . FIR&R.OW REQtMBIENT8 FOR.._.... ! ! TABLE 8105. 1 c· lllNlllUll AEQW1ED FIRE A.OW ANO FLOW DURATION FOR llUl.D9GS . : -----•-------..____..... IAelld .. llAMllllA. Far SI: I ...-e foot• ().0929· ,1.2, I plloa per ... • 3.715 U.. I ,_..per .... i11c1a • 6M5 kPa.. L 'l)lpa al co•u1cdoa me llUed ~the lrtta11.,.,,,.,,, W1t1 Calk. II. .......... 20 psi. 351 PIREP\.OW 1.sOO PLOW DURA110H 2 3 • ~ '-"l .· ( -t 2000 INTERNA110 EXHIBIT 1
07/13/2006 15:33 FAX 979 764 3452 COLLEGE STATION PUB.UTL.
I# S( College Station Utilities ~ Reliable, Affordable, Community Owned
1601 GRAHAM ROAD
COLLEGE STATION TEXAS 77845
Date: 13 JULY 2006
Number pages including cover sheet -3
Fax number: 260-3564
Attention: BECKY
Company: MITCHELL AND MORGAN
From: Butch Willis Water Services Department
Phone: 979-764-3435 Fax: 979-764-3452
FLOW TEST REPORT
Nozzle size: 2.5 inch
Location: CULPEPPER PLAZA
Flow hydrant number: D-072
Pitot reading: 85
(GPM): 1550
Static hydrant number: D-177
Static PSI: 96
Residual PSI: 96
COMMENTS: HARVEY RD NEAR EXXON
~001
EXHIBIT 2A
07/13/2006 15:35 FAX 979 764 3452 COLLEGE STATION PUB.UTL.
/14( College Station Utilities ~ Re.Jiable, Affordable, Community Owned
1601 GRAHAM ROAD
COLLEGE STATION TEXAS 77845
Date: 13 JULY 2006
From: Butch Willis Water Services Department
Phone: 979-764-3435 Fax: 979-764-3452
FLOW TEST REPORT
Nozzle size: 2.5 inch
Location: CULPEPPER PLAZA
Flow hydrant number: D-069
Pitot reading: 70
(GPM): 1405
Static hydrant number: D-181
Static PSI: 94
Residual PSI: 92
COMMENTS: CLOSE TO BENNEGENS
!gj003
EXHIBIT 2A
07/13/2006 15:34 FAX 979 764 3452 COLLEGE STATION PUB.UTL.
II;(( College Station Utilities ~ Reliable, Affordable, Community Owned
1601 GRAHAM ROAD
COLLEGE STATION TEXAS 77845
Date: 13 JULY 2006
From: Butch Willis Water Services Department
Phone: 979-764-3435 Fax: 979-764-3452
FLOW TEST REPORT
Nozzle size: 2.5 inch
Location: CULPEPPER PLAZA
Flow hydrant number: D-070
Pitot reading: 83
(GPM): 1525
Static hydrant number: D-071
Static PSI: 94
Residual PSI: 92
COMMENTS: BACK OF COMPLEX WHERE FIRE SPRINKLERS
ARE TIED IN
~002
EXHIBIT 2A
EXHIBIT2B
Analysis Type: Steady State, Average day, no additional demand for Culpepper Plaza (static conditions) -flow test
comparison
EXHIBIT 28
Results -Junctions
Number of Junctions: I 7(Selection)
Junction ID Elevation Demand Grade Pressure
[ft] [gpm] [ft] [psi]
148 297.000 6.645 549.433 109.379
150 296.000 0.000 549.262 109.738
151 293.000 21 .045 549.187 111.006
153 286.000 19.167 549.260 114.071 J
154 286.000 2.658 549.267 114.073
580 286.000 14.056 549.313 114.093
,-
15.903 581 286.000 549.286 114.082
582 1285 .000-0.000 549.25 1 114.500
-.--
639 286.000 0.000 549.420 114.140
r---I 295.000 I 28.447
I
550.244 I 110.597 640
641 298.000 1 o.ooo 550.098 109.234
1284.000 I o.ooo I I
1218 549.249 114.933 J
2251 1290.500 1 o.ooo ~ 549.712 1 112.317 I
2252 I 291.500 I o.ooo 549.36 1 111.731
I 288.750 i 0.000
I
549.335 I 112.911 2253
,---
I o.ooo 2254 286.000 549.351 114.110
2255 1290.000 I o.ooo i 549.351 I 11 2.3n
EXHIBIT2B
Results -Pipes
Number of Pipes: 19(Se~n)
Roughness l Pipe ID Node 1 Node2 Diameter Length Flow Velocity Headloss
[in] [ft] [ millift] [gpm] [ft/s] [ft]
979 640 2251 12 .000 720.537 120.000 467.596 1.326 0.532
1085 151 582 6.000 819.825 110.000 -20.652 -0.234 0.064
r----
1166 148 641 8.000 746.175 110.000 -163.375 -1 .043 0.665
---r
1167 148 2252 8.000 884.531 110.000 45.233 0.289 0.072
1168 150 148 8.000 382.508 110.000 -111.497 -0 .712 0.172
,-
1169 151 150 8.000 663.430 110.000 -53.430 -0.341 0.075
1171 154 581 8.000 116.103 110.000 -62.155 -0.397 0.019 J ~ ,---
1172 154 153 8.000 369.776 110.000 19.167 0.122 0.006 I .---
1553 580 2254 18.000 259.169 130.000 -583.345 -0.735 0.038
I ss1
___, --
1554 580 18.000 123.451 130.000 -614.521 -0.775 0.027
,----
1555 582 1 ss1 18.000 1243.171 . 130.000 -546.463 -0.689 0.035 _J
1641 I 640 I 364.910 I 120.000 1594 12.000 -323 .802 -0.919 0.146
j 121s j 1s4 j s.ooo j 2s9.766
~ -r 10.<ITT _J 2255 110.000 -40.330 -0 .257
I 121 s
I I I 114.754 I 130.000
I I I 0.001 2258 582 12.000 -56.349 -0.160
2651 I 22s1 I 639 I 12.000 387.820 I 120.000 I 467.596 1 1.326 0.293 I
2654 I 22s2 2253 8.000 324.416 110.000 45 .233 0.289 0.026 J
2655 j 2253 I sso 8.000 I 268.988 110.000 45.233 0.289 I 0.022
2656 I 2254 1639 18 .000 499.971 130.000 -583.345 -0.735 0.069 I I 2254 2657 I 22ss 8.000 387.730 140.000 -0.000 -0.000 I o.ooo J
EXHIBIT 28
EXHIBIT2C
Analysis Type: Steady State, average day conditions, flow test comparison -residual
Horizontal Plan
EXHIBIT2C
NEAR EXXON
Results -Junctions
r-.--
Junction Elevation Demand Grade Pressure ID
[ft] [gpm] [ft] [psi]
---r
639 286.000 0.000 537.982 109.184
---, -,--
2256 286.000 1550.000 537.673 109.050
NEA R BENN/GAN'S
Results -Junctions
Junction Elevation I Grade Pressure I ID Demand
r--
[ft]l[psi] [ft] [gpm]
640 1295.000 128.447 I 539.202 I 105 .813
2257 292.750 1405 .000 538.870 106.644
BACK OF COMPLEX
Results -Junctions
Junction
ID
2258
2261
Elevation
[ft]
I 289.000
1287.250
Demand Grade Pressure
[gpm] [ft] [psi]
I o.ooo I 525.814 1 102 .612
i 1525.000 1525.814 1 103 .370 I
EXHIBIT2C
EXHIBIT3
Project Description: Steady State, firetl ow multiplier (x3 .69) on average day conditions, 5500 gpm firetlow split
between 2 hydrants
Horizontal Plan
/
.,,~<)"'
..::..::.;=------~o4.
EXHIBIT 3
Results -Junctions
Time Level: O; 0 day 0:00 hr
Number of Junctions: 19(Selection)
Junction ID I Elevation Demand Grade Pressure
[ft] [gpm] [ft] [psi]
...----·
148 297.000 24.520 435.572 60.043
150 296.000 0.000 434.832 T 60.156
151 293.000 77.656 434.742 . 61.4~
r--
153 286.000 70.726 440.3 14 66.864
154 286.000 9.808 440.385 66~
580 1286.000 51.867 441.5 12 67.383 I
581 I 286.000 21.782 440.808 67.078 I
582 285.000 0.000 439.902 67.119
639 I 286.000 I o.ooo 447.950 70.173
640 295 .000 104.969 449.466 66.930
641 298.000 0.000 447.169 64.635
I
642 300.000 0.000 446.699 63 .565
643 300.000 41.727 446.6 13 63.527
1218 284.000 0.000 439.897 67 .5 50
2251 290.500 0.000 448.488 68.456
2252 291.500 1375.000 429.557 59.820
2253 288.750 0.000 436.081 63.839
2254 286.000 0.000 443.121 68.081
2255 290.000 1375.000 431.986 61 .522
EXHIBIT 3
Results -Pipes
Number of Pipes: 21 (Selection)
r--,--I Velocity Pipe ID Node 1 Node2 Diameter Length Roughness Flow Headloss I
.----,-_J
[in] [ft] [millift] [gpm] [ ft/s] [ft]
979 640 22Sl 12.000 720.S37 120.000 649.090 l.S41 0.97S
JOSS l SI SS2 6.000 Sl9.S2S 110.000 -22 1.070 -2.S09 S.160
...------___J
1166 14S 641 S.000 746. I 7S 110.000 -762.114 -4.S64 I l .S97 J ---,.---
1167 14S 22S2 S.000 SS4.S3 I 110.000 492.SS6 13.146 6.0IS
__J
I 16S I 1so 14S S.000 I 3s2.sos ~.ooo I -244.73S I -l.S62 0.740
1169 IS 1 ISO S.000 663.430 110.000 1 -s9.13S 1-0.377 0.090
1171 IS4 SSl S.000 116.103 110.000 -323 .26S I -2.063 0.42~
r
I 1172 1S4 IS3 S.000 369.776 110.000 70.726 OAS I 0.071
I sso I 22S4 I 2s9.I69 1-4332.729
I
ISS3 1 1s.ooo 130.000 -S.463 1.609
1SS4 I ss1 \ sso G s.ooo 123.4Sl 130.000 -339S.71 S -4.2SS FoH I ss2 I ss1 I 1s.ooo 1243.171
I
1-30S3.667 1-3 .SSO lSSS 130.000 I
1S94 641 640 12.000 364.910 120.000 -1417.190 -4.020 2.297
1S9S 1642 1641 12.000 I 309.467 I 120.000 -6SS.076 -I.SSS 0.46~
IS96 1643 1642 12.000 124.649 I 120.000 1-6SS.076 I -I.SSS I o.os7
22SS 121S 1S4 S.000 2S9.766 110.000 -242.734 -1 .S49 0.4SS
22SS I 121s 12.000 l 14.7S4 130.000 -114.011 -0.323 O.OOS
26Sl 22Sl 639 12.000 3S7.S20 120.000 649.090 1.S41 O.S3S
26S4 22S2 22S3 S.000 324.416 110.000 -SS2.144 -S.631 6.S24
26SS 22S3 sso S.000 26S.9SS 110.000 -SS2 .144 -S .631 S.430
26S6 22S4 639 IS.000 499.971 130.000 -S707.729 -7.196 4.S29
26S7 I 22s4 I 22ss S.000 I 3s7.730 140.000 137S .OOO S.776 I I. I 3S
EXHIBIT 3