HomeMy WebLinkAboutWater ReportNB 111 I McCLURE & BROWNE ENGINEERING/SURVEYING, INC. 1008 Woodcreek Drive, Suite 103 •College Station, Texas 77845 (979) 693-3838 •Fax (979) 693-2554 •Email: mcclurebrowne@verizon.net December 8, 2005 Mr. Josh Norton CITY OF COLLEGE STATION Post Office Box 9960 College Station, Texas 77842 RE: Popeye's Restaurant, Graham Road Letter Report for the Water System and Required Fire Flows Dear Josh: According to the architect, the new Popeye's Restaurant being proposed on Graham Road will have a total interior floor space of 2,100 s.f., and it will be constructed using Type III construction. The International Fire Code has two categories for Type III construction (Illa and Illb). Fire flow requirements for the two types are as follows: Construction Type ma Illb Building Size (sf) 0-12,700 0-5,900 Required Fire Flow (gpm) 1,500 1,500 While it is not clear which construction type is used for the Popeye's Restaurant, the required flow for a 2,100 sf building is 1,500 gpm under either scenario. Accompanying this letter are two Flow Test Reports prepared by the City of College Station's Public Utilities Department. These two tests were taken on the hydrants closest to the proposed location of the restaurant. Both hydrants are capable of flowing 1,525 gpm while maintaining a residual system pressure in excess of 100 psi. We therefore conclude that the existing water system is easily capable of providing the required fire flow for this building. As always, if you have any questions regarding our conclusions, please contact me at your convenience. Very jz:;;_ i Kent Laza, P.E. 0 Project Administrator attachments College a ion Utilities Re.Jiable, Affordable, Communit Owned 1601 GRAHAM ROAD COLLEGE STATION TEXAS 77845 From: Butch Willis Water Wastewater Division Phone: 979-764-3435 Fax: 979-764-3452 FLOW TEST REPORT Nozzle size: 2.5 inch Location: GRAHAM AT HWY SIX Flow hydrant number: Q-151 Pitot reading: 82 (GPM): 1525 Static hydrant number: Q-121 Static PSI: 104 Residual PSI: 104 . ) College S ation U ilities Reliable, Affordabl , Communit Owned 1601 GRAHAM ROAD COLLEGE STATION TEXAS 77845 From: Butch Willis Water Wastewater Division Phone: 979-764-3435 Fax: 979-764-3452 FLOW TEST REPORT Nozzle size: 2.5 inch Location: GRAHAM AT HWY SIX Flow hydrant number: Q-121 Pitot reading: 82 (GPM): 1525 Static hydrant number: Q-151 Static PSI: 104 Residual PSI: 104