Loading...
HomeMy WebLinkAboutFire Flow Test ReportEXHIBIT B SCHULTZ ENGINEERING, LLC FIRM #12327 WATER SYSTEM FIRE HYDRANT FLOW TEST REPORT 12-17-13 Date: Water System Owner: _Wellborn SUD Wellborn Business Park Development Project: Wellborn Business Park FH # 2 Flow Test Location: Nozzle size (in.): _2.5. 46 Pitot Reading (psi): _ 1140 Flowrate (gpm): _ Discharge Coeff: (c) = 0.90 Flowrate Formula: Q=29.84cd2p111 c = discharge coeff. d = orifice size (in) P = pitot pressure (psi) Wellborn Business Park FH #1 Pressure Gauge Location: 56 Static Pressure (psi): Residual Pressure (psi): 52_ 3734 Computed Discharge at 20 psi Residual Pressure: QR = 54 Discharge Formula: QR = QF X (hr 0.54 /hf 0.) Note: The flow test and report were prepared in accordance with NFPA 291, Joe Schultz Report Prepared by: Deven Doyen Others Present: Clenden Adams — Wellborn SUD Britt Curless I'Z't