HomeMy WebLinkAboutFire Flow Test ReportEXHIBIT B
SCHULTZ ENGINEERING, LLC
FIRM #12327
WATER SYSTEM FIRE HYDRANT FLOW TEST REPORT
12-17-13
Date:
Water System Owner: _Wellborn SUD
Wellborn Business Park
Development Project:
Wellborn Business Park FH # 2
Flow Test Location:
Nozzle size (in.): _2.5.
46
Pitot Reading (psi): _
1140
Flowrate (gpm): _
Discharge Coeff: (c) = 0.90
Flowrate Formula: Q=29.84cd2p111
c = discharge coeff.
d = orifice size (in)
P = pitot pressure (psi)
Wellborn Business Park FH #1
Pressure Gauge Location:
56
Static Pressure (psi):
Residual Pressure (psi): 52_
3734
Computed Discharge at 20 psi Residual Pressure: QR =
54
Discharge Formula: QR = QF X (hr 0.54 /hf 0.)
Note: The flow test and report were prepared in accordance with NFPA 291,
Joe Schultz
Report Prepared by:
Deven Doyen
Others Present: Clenden Adams — Wellborn SUD
Britt Curless