HomeMy WebLinkAboutFire Flow ReportMI ge Station Utilities
kellable, Affordable, +CoMMUnit} Owned
Date Tuesday January 10, 2012
Time 1:30 P.M.
Test
completed by Vincent Rodriquez and Gerald Borths
Witness Floyd Anderson
Location Townhomes of Marion Pugh
Nozzle size 2.5
Flow hydrant Hvd. #21 Hvd. #3
Pitot reading 60/65
G.P.M. 1300/1350
Static hydrant Hvd. #11
Static PSI 90
Residual PSI 82
Comments For Fireflow
college Station Utilities
Re/lalble, Affordable, Community Owned
Date Monday September 26, 2011
Time 10:15 A.M.
Test
completed by Justin Tamplin, Vincent Rodriquez
Witness Floyd Anderson
Location Townhomes of Marion Pugh
Nozzle size 2.5
Flow hydrant Hvd. #2l Hvd. #3
Pitot reading 70/63
G.P.M. 1440/1325
Static hydrant Hvd. #11
Static PSI 90
Residual PSI 83
Comments For Fireflow