MEMORANDUM
March 4, 2011 /
TO: James Harris via email jharris@briceco.net
FROM: Molly Hitchcock, AICP
Planning Administrator
SUBJECT: BRITT RICE ENTRY (SP)
Thank you for the submittal of your minor SITE PLAN - COMMERCIAL application. This project
and the NON-RESIDENTIAL ARCHITECTURAL STANDARDS application will be distributed to
staff next week for their review.
cc: Case file no. 11-00500041
Case file no. 11-00500028
�T1 1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
CITY or C01.GIGH STATION
Hwm, afYf ,A,+M Unw,,ty
MEMORANDUM
March 10, 2011 �. 1w l
TO: James Harris, via email: iharris(a)briceco.net/ oW
FROM: Matthew Hilgemeier, Staff Planner
SUBJECT: Britt Rice Entry (Sp)- Site Plan
Staff reviewed the above -mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments and
submit the following information by any Monday at 10:00 a.m. for further staff review:
City of College Station Transmittal Letter;
Memo providing written responses to all of staff's comments (identify the specific
page that each comment was addressed on or the reason for not addressing the
comment);
Seven (7) complete sets of site civil construction documents for the proposed
development with the revised site attached (one set will be returned to you,
please submit additional copies if you want more than one approved set)'
Four (4) revised site plans
Please note that this application will expire in 90 days from the date of this memo, if the
applicant has not provided written response comments and revised documents to the
Administrator that seek to address the staff review comments contained herein. If there are
comments that you are not addressing with the revised site plan, please attach a letter
explaining the details. If you have any questions or need additional information, please contact
Matthew Hilgemeier at 979.764.3570.
Attachments: Staff review comments
PC: Hawkins Architecture, via fax: 979.693.8370 V
Case file #11-00500041
STAFF REVIEW COMMENTS NO. 1
Project: Britt Rice Entry (Sp)—11-00500041
PLANNING
1. A six-inch monolithic curb is required along the all edges of the new porch and all parking
areas (except for ADA accessible ramps) that are affected by this site plan. Please show this
on the site plan and provide the standard curb detail found in the City of College Station
Sight Design Standards on the site plan.
2. Please provide the zoning classification for this site.
3. The masonry columns will conflict with the 2-foot overhang required of 18-foot parking
spaces. Please revise.
4. Please identify the location of the fire lane on this site and how it will be affected by the
proposed improvements.
5. Please identify the FEMA panel that covers this property and was used to determine no
floodplain exists.
6. Please note that any changes made to the plans, that have not been requested by the City
of College Station, must be explained in your next transmittal letter and "bubbled" on your
plans. Any additional changes on these plans that the City has not be made of aware of will
constitute a completely new review.
Reviewed by: Matthew Hilgemeier, Staff Planner Date: March 9, 2011
LAN DSCAPING/STREETSCAPING/BUFFER
1. Planning has no landscape comments.
Reviewed by: Matthew Hilgemeier, Staff Planner Date: March 9, 2011
ENGINEERING COMMENTS NO. 1
1. Will this expansion generate any additional water or sanitary sewer demand?
Please provide a table with the minimum, average, and maximum water and
sanitary sewer demands. If no additional domestic water or sanitary, sewer
demands are anticipated with this expansion, please provide a note indicating
such.
2. Please show any existing or proposed water, storm sewer, and sanitary sewer
service lines in the proposed area of work.
Reviewed by: Erika Bridges Date: 3/9/11