HomeMy WebLinkAboutFire Flow AnalysisM��IT�/C�,H ELL IY�►i/1 MORGAN April 30, 2012 Carol Cotter, PE City of College Station Planning & Development Services P.O. Box 9960 College Station, TX 77840 RE: Copper Falls Executive Suites - Fire Flow Analysis Dear Carol: Below is the fire flow analysis for the new Mitchell & Morgan, LLP Office Building to be located along SH 6 West Frontage Road between Mile Drive and Texas Avenue. The development will contain two structures, both 2,876 square feet and will be classified as Type III-B construction with no sprinkler installation. A domestic flow of 2.35 gpm was calculated by using Method 2 from the Bryan/College Station Unified Design Guidelines. A population factor of 30 persons per acre was used for commercial land use. The fire code requires a 1500 gpm fire flow as calculated using the Fire Flow Requirements as shown on page 10 of the May 2006 City of College Station Site Design Standards (Exhibit 1). The site will be served by 1 hydrant as shown on Exhibit 2. The updated City of College Station water system InfoWater model, compiled by Nick Dons at Freese & Nichols in January 2008, was checked against a flow test performed on Texas Avenue and Deacon Exit off SH 6 West Frontage Road. It was found that model results (average day conditions) were reasonably close to those found by flow tests under both static and residual conditions. Please see Exhibit 3 for the hydrant flow test report and Exhibit 4 for a map showing the tested hydrants. Flow Test and InfoWater Comparison Method Static Residual IDemand Flow Test 100.00 psi 96.00 psi 1500 gpm InfoWater 108.93 psi 100.91 psi 1500 gpm 511 UNIVERSITY DRIVE EAST, SUITE 204 • COLLEGE STATION, TX 77840 • I 979.260.6963 • 979.260.3564 CIVIL ENGINEERING HYDRAULICS HYDROLOGY UTILITIES STREETS SITE PLANS SUBDIVISIONS 'info@mhchellandmorgan.com • www, mi[chellandmorgan.com The City of College Station water system InfoWater model was updated with the proposed waterlines and then used to model fire flow conditions. The proposed waterlines will connect to an existing eight (8") inch waterline. Eight (8") inch waterlines will serve the site as shown in Exhibit 2. The 1500 gpm fire flow was assigned to the proposed hydrant and the InfoWater model was analyzed. The results, found in Exhibit 5, show that velocities do not exceed maximum velocity allowed and all pressures meet minimum requirements given the required fire flow. If you have any comments, or would like to discuss our findings further, please feel free toxontact me. Veronica J."o(g PE, CFM Managing Partne :rvzk4F- )44t) Cc: File limited to banquet halls night clubs, restaurants, taverns, and bars that exceed 5,000 square feet in area shA require an automatic sprinkler system. A Fire Department Connection (FDC) is required for all buildings utilizing an automatic sprinkler system. The FDC must be located within 150 feet of a fire hydrant. Fire Flow Requirements In general, the calculation area for fire flow requirements is based on the total gross area of the structure, including any area under the horizontal projections of the roof of the structure. Portions of the building that are separated by fire walls without openings and constructed in accordance with the International Building Code, may be considered as separate areas for the purposes of fire flow calculations. For type IA and type IB construction, the calculation shall be based on the area of the three largest successive floors. A@W UN REWIRED FIRE FLOW AND FLOW DURATION FOR SUIIDWOS• PM941 WCALCUTAVgNARY I" FLOW m9iw FLOW DURATION Awdeb rNONA&WSO No~ NY wM No 706 W 0• 700 042,700 0-8200 0-590D 036DO I500 22 701.30 200 1 701.17 000 8 201.10,900 3 901.7 900 3 6014 900 1750 30.20138700 17,001.21A00 10,901.12,900 7901.9,800 4.801-6200 2ODD 38,70148.300 2101-24,200 12901.17,400 9801.12600 6201.7,70D 2.250 2 301.39000 24201.33 17401.21 12601-15400 7.701-9AOD 2500 59 1- 900 3320I.39.700 21 1.25500 13401.18 9401-11300 2750 70,90143 700 39.70147.100 25,501 I00 1 I8 1.21 11M 11 301.13 310D0 $3701.97700 47101-34900 3%I01-332DO 21801.25900 13401-1S600 3250 97701-112700 3490WAM 3320140600 25901-29 00 15601.1300D 3,500 ) 112701.128700 63401.72.400 40,60146,400 29301.33 18001.10600 3750 128,701.145.900 7 401.82.100 46.401.32,500 33.501.37900. 20,601 33W 4000 145901.1 8 101.92,400 52 1-59100 3790142700 23,301-26.3W 4250 160 201-193,400 401.103 100 59 101 000 42,70147,700 26 301.29 300 4.500 163 1.203 700 103 101-114 600 001.73 300 47 701.53 000 29 30132 . 4,750 203 701-225 114 601.126.11M 73 301.81 100 53 I-58 600 32,601-36AW 5AW 225201.247700 I 701.139400. 91,10149200 58.601.6.3400 3001-39,6w S250 247701.271 139401.152A00 $9201-97700 65401770600 3960143400 55W 271201.205900 152601.166 701-106500 70.601.77000 43,4014740D 5750 295901-Orewr 166 143rawr 106501.115800 77001.8370D 47.401.51 OD 600D 4 115801.123 00 83701.90.600 511.55700 6250 12S 1.133 90.001-97900 55.701-60.200 6 135 1.143,8DO 97,901-106,800 60201.64800 6.730 143 801.156700 106.901.113200 64 801.69 600 7 000 156701.167900 113201-IV M 69601.14600 7.250 167 901.179 40D 121.301.129 600 74 601.79 800 7.500 174401-191400 129601.138300 79801.85100 7750 19I401.Omma 138 01.Oraar $5101-0rewr 11,: For 51: 1 aluue faX • 0.0929 mr, 1 plbn W+mhwle • 3.785 Um, 1 pwnd pw spwrc IaA • 6.895 kn. I AThe Wal mm mgaW Arc Rlow dn11 be permlped M be M6JeW by 25 pemem for Omop R. A 7yp& dmn Jlm we bwed m Nw 101~i& W $WU19 Cods. r. Mnw W a 20 psi. 10- EXHIBIT 1 P9aCer DoBeliv M: ewne. er Cea"ele dwrew", .' ]auwvslOzmff.if" oev= mn.A BATENSLOT PERMEABLE CONCRETE PAVEMENT SYSTEM STORAGE& DETENTION WITH CURB 6' In<k Cearad P of r/ 6' 1nIIX [enable Pov<menl x/ of Bon O Is of .0 . Blow R<Inlw<emenl oo i. r 4 fi 1Mek Il 51 N end b11ed Pembor O 5 F W. t n.,..,n. a Be Floc¢ xN J. Heber of 5 6. nNED meSm Milei6 RCP"'IDs) WROPP. IN OEOIEI(BIL SLOPED TO DRVN A LtlMFR Rem." '. doe s IN ONNERT NABD E0 YHO. 6' Thek Ceovele Pmmnl eer/ /4 Max O Ior OCEW of I. Took Ume SLablaeE "u 'Ue E'Pomlon Jolnle O 60 0 C, onI Ce-d-ru.n Je n4 O 30 O C. OEOIIXIXL .1 Re l red, exb wle eM bared, to Om n Ol RS The forms sno0 he placed of 5 as .an ...h way and .... red u n DI... bit" dowels. The forms must be se ed both horizontally and _d"lly Tne aawele as ed to e the farms must be rem used after a they nave served their pumas¢ FORMWORKFOR SLOTS ` ry wr< fibsB'N.C.to rn 'b aof lumber omburdened coorto, I"r6' Pine Lumber a ambled to prwiae Lr'x4' Slal 1n ConcretesPoaemenl. Lumber shall be coal.' with bond breaker and Proused man me .anar<t. is -L 4' Thick Concrete Sidewalk .y w/ NJ Oere 0 12' OC.EW. n On Thick Lima stonleee Shegrade XXXX \ X X >� o� X � X 6' Thick Concrete Pavement w/ X X X fiber Re nlorce 0 and,E k 4 X X X Raml. Pollem®R OFat W. X X ')� x Re EVE vi lh {'5 Reber of 5 oc.EW ipaa tomss the slots. Zi X ">< Be C. on J.i nts 060 oc om Na COnlmct on Jo nis. 6' PERFORATED 03034 SIR � ^{ zfi PVC PIPE(S) SLOPED TO / DRAIN PPRTIAuv EMBEDDED IN CEMENT STABILIZED SAND. 3/6 3/4' River brovel with 6eoteane Eabrc Above and Coax 36' depth 23' W'lh (entire drive I.le) 6' Thick Concrete Pavement W/ #4 Bars 015'OCEW n 6- Thck Lime Stabilized Suhgraae. Erpaneo. JOnle ® 6U NO, oad cerebration J.Irta ® 20 oC Vegetated Slope (4a Max) :C I i \ we PROPOSE[ BUILDING 2876BLDG HT SF 2E FF=102.30 I we f/ 90.99 2876 SF FF=105.30he Omj I I 1 ` ` / ] 0'%141 Owe E/L 99,45 V MJ Bentlan U'lia _ �E/Le9B.issl6o 1. leEditor e —�<ss 9I0' PVE l T1 Ea slled'ne 'n9 Wo Erulin_to Curb Inlet Section ad g9C nn TeP .1 WATER LINE 8" PVC (AWWA C900—CL 200) SEE DETAIL SHEET FOR EMBEDMENT lU I'D I OB ___ •__. _. I __I-. If •__ __. __ 108 06 106 04 104 102 V u xly wm<ane 0 5DF 00 _ 1 __. I _._ __-__. _. _. _. 100 98 __. ___. _- •__. __.__ __als 11.11.___-• ___-_. 95 Sla, Few I'Marm a Sta Oi]O50 le ='ovu weler ter 0... IAJ Bentl ___ NJ teen 96 — .._._.__ ..evokes r/un., F/is .6'n9O 9D<0 4J. Bend 94 94 n+nn 1+00 9+0n F.979.260.3564 own.—anpN.OID¢ si>9 UP EXHIBIT 2 College Station Utilities Reliable, Affordable, Community Owned Date Friday, May 30, 2008 Time 10:12AM Test completed by Matthew Matcek Witness Aaron Matthews Location 3101 Texas Nozzle size 2.5 Flow hydrant F-091 Pitot reading 80 G.P.M. 1600 Static hydrant F-090 Static PSI 100 Residual PSI 96 Comments EXHIBIT 3 �# � » � �~ ly C ` 0 $ J� ~ *¥ k£CD0o =Rg$E »#0 CD *;AK§E AA4P })k\\C e■A�e, _.RUDDER FWY. / E'D EECD (E220 CD §ƒ 0 E; Ko ���.eE �4,. % % Rmml! EXIUBIT 5 FIRE FLOW ANALYSIS Analysis Type: Water Quality Project Description: Copper Falls Executive Suites Horizontal Plan rResults - Junctions Time Level: 0; 0 day 0:00 hr Number of Junctions: 6(Selection) Junction ID Description Elevation Demand Grade Pressure IN [gpm] [ft] [psi] 1249 WPIPEFIT 277.349 10.256 485.808 90.325 1404 WPIPEFIT 274.409 90.696 482.222 90.045 59289 275.879 0.000 472.723 85.293 59290 276.000 8.672 472.359 85.082 59291 277.00 0.000 471.234 84.162 59292 hydrant 275.750 1500.00 469.162 83.805 Results - Pipes Time Level: 0; 0 day 0:00 hr Number of Pipes: 5(Selection) Pipe ID Description Node 1 Node 2 Dia. Length Roughness Flow Velocity Headloss Headlos s/1000 [in] [ftl [millift] [gpm] [ft/s] [ft] [ft] 53 WMAIN 1404 1249 8 1346.3 120 -381.33 -2.434 4.783 3.553 55 WMAIN 1249 59289 8 830.93 125 1034.88 6.605 17.391 20.93 3981 WMAIN 59289 1404 8 1168 125 -621.18 -3.97 9.499 8.113 3982 59289 59290 8 9.30 130 1508.67 9.63 0.364 39.112 3983 59290 59291 8 29.06 130 1500 9.574 1.125 38.705 3984 59291 59292 1 8 53.55 130 1500 9.574 2.073 38.705 0 1 a N O —h CD rr A ®i [llOJ'SLL`LLS2�IEI'MMMI I ISIOZ'40'EO ZOSLL X.L`NVXUEE Ii£i-Z96 (£IL) xiS EOZaLIns �' j• ZIO-51 #90f SI922IJ,I9.LL vD OOSb I q 99£E-M-WO JNSIWJC)'IgAgQ SIJnI2Ig sl-orw sKolsl�n3aayrs-au 9,iv z 0 U U r _._.-._._._.-----._._._.__ b1. a �I ILI iw I I i im I I i J p vP -II W N ¢w I i arc I � rn ,EE'921 M ,Li,64.Zt, rn w F- Q w w Z JO Q m Z w w ttl