May 7, 2012
TO: Travis Martinek, Clarke & Wyndham, Inc.; via email: travis(g), arkewyndham.com
FROM: Jason Schubert, AICP
Principal Planner
SUBJECT: FALCON POINT (PP)
Thank you for the submittal of your PRELIMINARY PLAN application. This project will be
distributed to staff this week for their review. /
V
cc: Paul Clarke, Clarke & Wyndham, Inc.; via email: piclndham.com
Kevin McClure, McClure & Browne Engineering/Surveying, Inc.; via email:
kevinm(a)mcclurebrowne.com /
Case file no. 12-00500100
1
CITY OF COLTEGF_ STATION -
Howe ofTexas AdMUniversity'
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM w
May 16, 2012
TO: Travis Martinek, Clarke & Wyndham, Inc.; via email: travis(5clarkewyndham.ComV
FROM: Teresa Rogers, Staff Planner
SUBJECT: FALCON POINT - Preliminary Plan
Staff reviewed the above -mentioned Preliminary Plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by any Monday at 10:00 a.m., your project
will be placed on the next available Planning and Zoning Commission meeting in the City Hall
Council Chambers, 1101 Texas Avenue.
One (1) 24" x 36" copy of the revised Preliminary Plan; and
Thirteen (13) 11" x 17" copies of the revised Preliminary Plan.
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that this application will
expire in 90 days from the date of this memo, if the applicant has not provided written response
comments and revised documents to the Administrator that seek to address the staff review
comments contained herein. If all comments have not been addressed, your project will be
pulled from the scheduled Planning & Zoning Commission agenda. Your project may be placed
on a future agenda once all the revisions have been made and the appropriate fees paid. Once
your item has been scheduled for the P&Z meeting, the agenda and staff report can be
accessed at the following web site on Monday the week of the P&Z meeting.
hftp://www.cstx.gov/pz
Please note that a Mylar original of the revised preliminary plan will be required after P&Z
approval and prior to processing subsequent final plats. If you have any questions or need
additional information, please call me at 979.764.3570.
Attachments: Staff review comments %
cc: Paul Clarke, Clarke & Wyndham, Inc.; via email: piclarke('Qclarkewyndham. com�/
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.1 of 4
Kevin McClure, McClure & Brow Engineering/Surveying, Inc.; via email:
kevi n m Coil m ccl u rebrown e. co m
Case file no. 12-00500100
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.2 of 4
STAFF REVIEW COMMENTS NO. 1
Project: FALCON POINT (PP) — (12-00500100)
PLANNING
V1. Revise the title block and label below the tract to state "Preliminary Plan".
2. Revise parcel labels so they are identified by legal description (subdivision, lot, and block)
instead of solely by owner.
3. Revise the plan to include contours at two foot intervals.
4. Residual tracts are not permitted. Please label the tracts currently reserved for future
development as Phase 2 and provide lot and block numbers. If a different configuration is
anticipated in the future for the "residual" tracts a new Preliminary Plan may be submitted for
that area.
-- 5. Show the limits of the Dartmouth Street and Holleman Drive right-of-ways (R.O.W.). It
appears to be 75 feet for both Dartmouth Street and Holleman Drive.
4 6. R.O.W. dedication of 8 feet for Holleman Drive and 18 feet for Dartmouth Street will be
required in order to meet sufficient widths required for the Thoroughfare Plan.
7. As advanced notice, please be aware that Parkland Dedication will be required for this
project.
,/8. Depict and label the joint access easement centered on the lot line adjoining the USDA
property.
9. Please note: Any changes made to the plans which have not been requested by the City of
College Station, much be explained in your next transmittal letter and "bubbled" on your
plans. Any additional changes on these plans that have not been pointed out to the City will
constitute a completely new review.
Reviewed by: Teresa Rogers
Date: May 15, 2012
ENGINEERING COMMENTS NO. 1
1. Label the volume and page number on all existing easements.
2. Each lot is required to have a 20-ft rear lot PUE which is contiguous with an existing PUE or
right-of-way.
3. Please show that the lot corners are tied to the City's horizontal control monuments.
4. Show and label the existing waterline and fire hydrant at the tract's southeastern corner.
5. Each lot is required to have access to public water and sanitary sewer mains, as well as
meet fire flow requirements per the BCS United Design Guidelines. Please show and label
infrastructure.
6. FYI — As this tract does not have direct access to Wolf Pen Creek, additional drainage
analysis will be required in order to evaluate the conveyance of storm water to the main
channel of Wolf Pen Creek, specifically the culvert beneath Holleman Drive.
7. Please label 10 foot electrical easement (v894, p656) along Dartmouth.
8. Please add a drainage easement along the watercourse crossing the property.
9. Please add a note and correspondence from the gas company specifying required
separation distances between the existing gas pipeline and structures.
Reviewed by: Erika Bridges Date: 5/14/12
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.3 of 4
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1. Developer provides temporary blanket easement for construction purposes and provides
descriptive easements for electric infrastructure as designed by CSU for electric lines (where
applicable, including street lights)
2. Developer may be responsible for locating easements on site to insure that electrical
infrastructure is installed within easement boundaries.
3. The following easements will be required:
10' PUE on each side of all Lot Lines (total 20' PUE) contained within the subject
property and that do not show existing or proposed PUE's along their length.
GENERAL ELECTRICAL COMMENTS
1. Developer installs conduit per CSU specs and design.
2. CSU will provide drawings for electrical installation.
3. Developer provides 30' of rigid or IMC conduit for riser poles. CSU installs riser.
4. Developer will intercept existing conduit at designated transformers or other existing devices
and extend as required.
5. If conduit does not exist at designated transformer or other existing devices, developer will
furnish and install conduit as shown on CSU electrical layout.
6. Developer pours electric device pads or footings (i.e. transformers, pull boxes etc) per CSU
specs and design.
7. Developer installs pull boxes and secondary pedestals per CSU specs and design (pull
boxes and secondary pedestals provided by CSU).
8. Developer provides digital AutoCAD 2000 or later version of plat and / or site plan. Email to:
gmartinez@cstx.gov.
9. Developer provides load data to CSU as soon as it is available to avoid construction delays.
Delivery time for transformers not in stock is approximately 26 weeks.
10. Final site plan must show all proposed electrical facilities necessary to provide electrical
service, i.e. transformer(s), pull box(es), switchgear(s), meter location and conduit routing as
designed by CSU.
11. To discuss any of the above electrical comments please contact Gilbert Martinez at
979.764.6255.
Reviewed by: Gilbert Martinez Date: 05.10.2012
SANITATION
1. Sanitation is ok with this project.
Reviewed by: Wally Urrutia Date: May 15, 2012
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.4 of 4
A
CITY OF C Ot r.r ci:; STMION
Horne of Texas A6'yW University'
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
July 31, 2012 � tW JI�� TO: Travis Martinek; via email: travis@clarkewyndham.com I I (2-
FROM: Teresa Rogers, Staff Planner
SUBJECT: FALCON POINT (PP) - Preliminary Plan
Staff reviewed the above -mentioned Preliminary Plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by any Monday at 10:00 a.m., your project
will be placed on the next available Planning and Zoning Commission meeting in the City Hall
Council Chambers. 1101 Texas Avenue.
One (1) 24" x 36" copy of the revised Preliminary Plan;
Thirteen (13) 11" x 17" copies of the revised Preliminary Plan.
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that this application will
expire in 90 days from the date of this memo, if the applicant has not provided written response
comments and revised documents to the Administrator that seek to address the staff review
comments contained herein. If all comments have not been addressed, your project will be
pulled from the scheduled Planning & Zoning Commission agenda. Your project may be placed
on a future agenda once all the revisions have been made and the appropriate fees paid. Once
your item has been scheduled for the P&Z meeting, the agenda and staff report can be
accessed at the following web site on Monday the week of the P&Z meeting.
httP://Www.Cstx.gov/Pz
If you have any questions or need additional information, please call me at 979.764.3570.
Attachments: Staff review comments
cc: Paul Clarke, Clarke & Wyndham, Inc.; via email: pjclarke@clarkewyndham.com
McClure & Browne Engineering/Surveying, Inc.; via email: kevinm@mcclurebrowne.com V
Case file #12-00500100
STAFF REVIEW COMMENTS NO. 2
Project: FALCON POINT (PP) - 12-00500100
PLANNING
V1. Please contact me at (979) 764-3570 to set up a facilitation meeting to quickly resolve
questions/comments.
Verify the limits of Dartmouth Street and Holleman Drive rights -of -way (R.O.W.). They are
't currently labeled as 80' but neither of the ROW widths are that size when scaled on the plan
or in GIS. The number appears to be closer to 75' maybe less in some places.
t 3. Because the subject tract will receive one access point from Dartmouth Street, the private
cross access easement should project to Phase 2 through Lot 1, Phase 1.
4R( Label the access easements as private access easements.
y,5: Provide the volume and page numbers for the Curtis Investments and Texas Huntington
Apartments tracts to show that these lots have been previously platted.
6. Revise the lot numbers for Phase Two to be Lots 5 and 6. While these lots are included in
V
different phases they are still within the same block and tract and should be numbered
differently. The repetition of the same lot numbers within a block may cause confusion for
future viewers of the plan.
V7:. Revise the plan to label contours at two foot intervals. Currently, the labels are depicted
less frequently which makes it difficult to differentiate between them.
y8.( Revise the title block number of lots to 6 lots for the 2436 submittal and update the date
given in the title block so the 2436 and the 11x17 copies match.
-9. Move the title block so that it is located in the bottom right corner of the plan.
-10. Remove Notes #4 and #5 from the Preliminary Plan, as they may be incorrect if a future
variance is granted by the Zoning Board of Adjustments.
V 11. As advanced notice, please be aware that Parkland Dedication will be required for this
project.
Reviewed by: Teresa Rogers
ENGINEERING
Date: July 25, 2012
1. (Repeat) Label the volume and page number on all existing easements. Please verify that
10-ft Sanitary Sewer Easement (V.335, P.452) is not located on the property.
2. (Repeat) Each lot is required to have a 20-ft rear lot PUE which is contiguous with an
existing PUE or right-of-way. Please show and label the rear lot PUE for Phase 2, Lot 1
and Lot 2.
3. (Repeat) Please show that the lot corners are tied to the City's horizontal control
monuments. Please show on plat.
4. (Repeat) Show and label the existing waterline and fire hydrant at the tract's southeastern
corner. Please show on plat.
5. (Repeat) Each lot is required to have access to public water and sanitary sewer mains, as
well as meet fire flow requirements per the BCS United Design Guidelines. Please show
and label infrastructure.
• Please show sewer line to Phase 2, Lot 1.
• The 8-inch waterline is required to be looped. Please connect to the existing 12-
inch waterline along Holleman Dr.
6. (Repeat) Please add a drainage easement along the watercourse crossing the property.
Please show and label the drainage easements as "proposed." FYI ... The width will
need to be determined with final plat in accordance with the B/CS Unified Stormwater
Design Guidelines.
(Repeat) Please add a note and correspondence from the gas company specifying required
separation distances between the existing gas pipeline and structures. Our system
indicates that this is a Lonestar Gas Pipeline. Please provide correspondence from
the gas company and revise note.
Reviewed by: Erika Bridges
Date: July 30, 2012
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1. SITE PLAN/PLAT: Developer will provide CSU with a digital, AutoCAD dwg format, version
of plat and / or site plan as soon as it is available. Email to: ehorton(a)cstx.gov.
2. LOAD DATA: The developer will provide load data to CSU as soon as it is available. This
information is critical for CSU to accurately determine the size and number of transformers,
and other equipment, required to provide service to the project. Failure to provide load data
will result in construction delays and, due to clearance requirements, could affect the final
building footprint. Delivery time for transformers and other equipment not in stock is
approximate 26 weeks.
3. EASEMENTS: Developer provides temporary blanket easement for construction purposes
and upon completion of project must provide descriptive easements for electric infrastructure
as designed by CSU.
4. Where possible electric facilities will be designed within existing easements.
5. If easements are existing, the developer will be responsible for locating easements on site to
insure that electrical infrastructure is installed within easement boundaries.
GENERAL ELECTRICAL
1. Developer installs conduit per CSU specs and design.
2. CSU will provide drawings for electrical installation.
3. Developer provides 30' of rigid or IMC conduit for each riser conduit. CSU installs riser.
4. Developer will intercept existing conduit at designated transformers or other existing devices
and extend as required.
5. If conduit does not exist at designated transformer or other existing devices, developer will
furnish and install conduit as shown on CSU electrical layout.
6. Developer pours electric device pads or footings, i.e. transformers, pull boxes, or other
device, per CSU specs and design.
7. Developer installs pull boxes and secondary pedestals per CSU specs and design, Pull
boxes and secondary pedestals provided by CSU.
8. Final site plan must show all proposed electrical facilities necessary to provide electrical
service, i.e. transformers, pull boxes, or switchgears, all meter locations, and conduit routing
as designed by CSU.
9. To discuss any of the above electrical comments please contact Gilbert Martinez at
979.764.6255, Sam Weido at 979,764,6314, Eric Horton at 979.764.6280, or Weldon Davis
at 979.764.5027.
Reviewed by: Eric Horton Date: July 31, 2012
/"r
CITY OF COLL GG STATION
Home of Texas A6M University'
1101 Texas Avenue
College Station, Texas 77840
Phone 979.743.3570 / Fax 979.764.3496
MEMORANDUM
August 21, 2012
TO: Travis Martinek; via email: travis@clarkewyndham.com "
FROM: Teresa Rogers, Staff Planner
SUBJECT: FALCON POINT (PP) — Preliminary Plan
Staff reviewed the above -mentioned Preliminary Plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information by any Monday at 10:00 a.m. to be placed on
the next available Planning and Zoning Commission meeting scheduled for 7:00 p.m. in the City
Hall Council Chambers, 1101 Texas Avenue.
One (1) 24" x 36" copy of the revised Preliminary Plan; and
Thirteen (13) 11" x 17" copies of the revised Preliminary Plan.
Please note that this application will expire in 90 days from the date of this memo, if the
applicant has not provided written response comments and revised documents to the
Administrator that seek to address the staff review comments contained herein. Once your item
has been scheduled for the P&Z meeting, the agenda and staff report can be accessed at the
following web site on Monday the week of the P&Z meeting.
http://www.cstx.gov/pz
If you have any questions or need additional information, please contact me at 979.764.3570.
Attachments: Staff Review Comments
cc: Paul Clarke, Clarke& Wyndham, Inc.; via email: pjclarke@clarkewyndham.com `_
McClure & Browne Engineering/Surveying, Inc.; via email: kevinm@mcclurebrowne.comv/�
Case file no. 12-00500100
STAFF REVIEW COMMENTS NO. 3
Project: FALCON POINT (PP) - 12-00500100
ENGINEERING
1. The 10-ft PUEs for the proposed water and sanitary sewer on Lots 2, 3, and 4 are
insufficient and need to be at least 15-ft wide.
2. Please show a 10-ft PUE along the NW side of Lots 4 & 6.
3. There's not enough room within the proposed right-of-way for the proposed water and
sanitary sewer along the side of Lot 1. A minimum 30-ft PUE with utility lines separated by 9
feet is needed if water and sewer are going to be located in the same trench.
Reviewed by: Erika Bridges
Date: August 16, 2012
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1. SITE PLAN/PLAT: Developer will provide CSU with a digital, AutoCAD dwg format, version
of plat and / or site plan as soon as it is available. Email to: ehorton cstx.gov
2. LOAD DATA: The developer will provide load data to CSU as soon as it is available. This
information is critical for CSU to accurately determine the size and number of transformers,
and other equipment, required to provide service to the project. Failure to provide load data
will result in construction delays and, due to clearance requirements, could affect the final
building footprint. Delivery time for transformers and other equipment not in stock is
approximate 26 weeks.
3. EASEMENTS: Developer provides temporary blanket easement for construction purposes
and upon completion of project must provide descriptive easements for electric infrastructure
as designed by CSU.
4. EASEMENTS: All easements on site are existing. Electric facilities will be designed within
existing easements.
GENERAL ELECTRICAL COMMENTS
1. Developer installs conduit per CSU specs and design.
2. CSU will provide drawings for electrical installation.
3. Developer provides 30' of rigid or IMC conduit for each riser conduit. CSU installs riser.
4. Developer will intercept existing conduit at designated transformers or other existing devices
and extend as required.
5. If conduit does not exist at designated transformer or other existing devices, developer will
furnish and install conduit as shown on CSU electrical layout.
6. Developer pours electric device pads or footings, i.e. transformers, pull boxes, or other
device, per CSU specs and design.
7. Developer installs pull boxes and secondary pedestals per CSU specs and design, Pull
boxes and secondary pedestals provided by CSU.
8. Final site plan must show all proposed electrical facilities necessary to provide electrical
service, i.e. transformers, pull boxes, or switchgears, all meter locations, and conduit routing
as designed by CSU.
9. To discuss any of the above electrical comments please contact Eric Horton at
979.764.6280.
Reviewed by: Eric Horton Date: August 20, 2012
FALCON POINT -PRELIMINARY PLAN
RESPONSE TO STAFF REVIEW COMMENTS NO. 2
PLANNING
1. No comment.
2. Resolved through discussions.
3. See attached revised Preliminary Plan.
4. See attached revised Preliminary Plan.
5. See attached revised Preliminary Plan.
6. See attached revised Preliminary Plan.
7. See attached revised Preliminary Plan.
8. See attached revised Preliminary Plan.
9. See attached revised Preliminary Plan.
10. See attached revised Preliminary Plan.
11. No comment.
ENGINEERING
1. After research, the easement you are describing is located on the South side of Holleman Drive.
2. See attached revised Preliminary Plan.
3. See attached revised Preliminary Plan.
4. See attached revised Preliminary Plan.
5. See attached revised Preliminary Plan.
6. See attached revised Preliminary Plan. Note 11 was reworded to better address the
establishment of the drainage easement.
7. Atmos Energy acquired the gas infrastructure in that easement from Lonestar Gas Pipeline.
Refer to attached email for more information.
ELECTRICAL
1. No comment.
2. No comment.
3. No comment.
4. No comment.
5. No comment.
ELECTRICAL (GENERAL)
1. No comment.
2. No comment.
3. No comment.
4. No comment.
5. No comment.
6. No comment.
7. No comment.
8. No comment.
9. No comment.
8/9/2012 Page 1 of 1
FALCON rJINT —PRELIMINARY PLAN
PLANNING
7.
ENGINEERING
See attached revised Preliminary Plan.
See Note 12.
3. See attached revised Preliminary Plan.
4. See attached revised Preliminary Plan.
5. See attached revised Preliminary Plan.
6. No comment.
7. See attached revised Preliminary Plan.
8. See Note 13.
9. See Note 14.
ELECTRICAL
1. No comment.
2. No comment.
3. See Note 12.
ELECTRICAL (GENERAL)
1.
No comment.
2.
No comment.
3.
No comment.
4.
No comment.
5.
No comment.
6.
No comment.
7.
No comment.
8.
No comment.
9.
No comment.
10.
No comment.
11.
No comment.
SANITATION
1. No comment.
RESPONSE TO STAFF REVIEW COMMENTS NO. 1
See attached revised Preliminary Plan. ^� i� (42 jylQ, i( )
See attached revised Preliminary Plan. riai«d pD� I�� 1 "IG1t II��
See attached revised Preliminary Plan. lo(/ S U.l L,
See attached revised Preliminary Plan.
See attached revised Preliminary Plan.T/WI
See attached r�ised Preliminary Plan. �o wow' tin
No comment. f
See attached revised Preliminary Plan<301 w)
No comment.
acceav : a(knv -+ - VriV&+b
6l uk to AA aarea - - MW 12I ,
0n9l0% .?
am* rid-oowlv�y an W) ?
VjjTrGUN _ LAKE F PEAO
00% not 40t'�2
date in Wit U000
v40 Pl l locaJf (it IZ 0ttj
V* remove notr2# 4F2
7/23/2012 Page 1 of 1
FALCON vOINT —PRELIMINARY PLAN
RESPONSE TO STAFF REVIEW COMMENTS NO. 3
ENGINEERING
1. See revised Preliminary Plan. The Property Owner will execute a 10-foot Public Utility Easement
by separate instrument along the future Phase 2, Lot 6 prior to filing the Final Plat for Phase 1.
2. See revised Preliminary Plan.
3. See revised Preliminary Plan. Phase 2, Lots 5 and 6 will take sewer service from a proposed
extension along the southern boundary of Phase 1, Lot 4.
ELECTRICAL
1. Property Owner will discuss this item with CSU during the completion of building construction
plans.
2. See Comment 1.
3. See Comment 1.
4. See Comment 1.
ELECTRICAL (GENERAL)
1. Property Owner will discuss this item with CSU during the completion of building construction
plans.
2. See Comment 1.
3. See Comment 1.
4. See Comment 1.
5. See Comment 1.
6. See Comment 1.
7. See Comment 1.
8. See Comment 1.
9. See Comment 1.
8/28/2012 Page 1 of 1