HomeMy WebLinkAboutStaff CommentsSTAFF REVIEW COMMENTS NO. 1
Project: Genghis Grill Patio (Sp)—11-00500015
PLANNING
1) Please provide a key map of the project location.
2) Please include the following information in the title block:
a) Legal description of the property;
b) Name, address and telephone of the applicant;
c) Name, address, and telephone number of the property owner/developer;
d) An updated project submittal date on all sheets;
e) The total area of the project.
3) Please add,phase line around the project area. The phase line should be located 20' from
any new improvement. Without the phase line, the entire shopping center will need to come
into compliance with all applicable ordinances.
4) Please show the property line for this site.
5) Please provide ownership and zoning information for all abutting properties.
6) Please provide a note that identifies the FEMA panel that covers this property and was used
to determine no floodplain exists on the property.
7) Please the location of the existing FDC connection. If it is located within the patio area,
access through the patio fence will be required.
8) Provide a general note on the site plan that all roof and ground -mounted mechanical
equipment shall be screened from view or isolated so as not to be visible from any public
right-of-way or residential district within 150' of the subject lot, measured from a point five
feet above grade. Such screening shall be coordinated with the building architecture and
scale to maintain a unified appearance.
9) Provide a general note on the site plan that states the following: Exterior building and site
lighting will meet the standards of Section 7.10 of the Unified Development Ordinance. The
light source shall not project below an opaque housing and no fixture shall directly project
light horizontally. Fixtures will be mounted in such a manner that the projected cone of light
does not cross any property line.
10) Please note that any changes made to the plans, that have not been requested by the City
of College Station, must be explained in your next transmittal letter and "bubbled" on your
plans. Any additional changes on these plans that the City has not be made of aware of will
constitute a completely new review.
Reviewed by: Matthew Hilgemeier
LAN DSCAPING/STREETSCAPING/BUFFER
1. Planning has not landscape comments.
Reviewed by: Matthew Hilgemeier
Date: 4/1/2011
Date: 4/1 /2011
Page 2 of 3
ENGINEERING COMMENTS NO. 1
1. Please field verify the exact location of the water and sanitary sewer mains
located just adjacent to the proposed patio and identify these locations on the
site plan. The centerline of the utility pipe may not be any closer than 7.5 feet
away from the patio.
Reviewed by: Josh Norton
Date: March 31, 2011
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1. The scope of this project as shown does not require modification or additions to
existing CSU infrastructure. Electric for this project will be provided from the
customers internal service panel. If this is in error of if the scope of this project
changes to require additions or modifications to CSU infrastructure or additional
easements then all comments listed below will apply and easements will need to be
filed by separate instrument.
GENERAL ELECTRICAL COMMENTS
1. Developer installs conduit per CSU specs and design.
2. CSU will provide drawings for electrical installation.
3. Developer provides 30' of rigid or IMC conduit for riser poles. CSU installs riser.
4. Developer will intercept existing conduit at designated transformers or other existing
devices and extend as required.
5. If conduit does not exist at designated transformer or other existing devices,
developer will furnish and install conduit as shown on CSU electrical layout.
6. Developer pours electric device pads or footings (i.e. transformers, pull boxes etc)
per CSU specs and design.
7. Developer installs pull boxes and secondary pedestals per CSU specs and design
(pull boxes and secondary pedestals provided by CSU).
8. Developer provides digital AutoCAD 2000 or later version of plat and / or site plan.
Email to: gmartinez(cDcstx.gov.
9. Developer provides load data to CSU as soon as it is available to avoid construction
delays. Delivery time for transformers not in stock is approximately 40 weeks.
10. Final site plan must show all proposed electrical facilities necessary to provide
electrical service, i.e. transformer(s), pull box(es), switchgear(s), meter location and
conduit routing as designed by CSU.
11.To discuss any of the above electrical comments please contact Gilbert Martinez at
979.764.6255.
Reviewed by: Gilbert Martinez Date: 03.31.2011