Loading...
HomeMy WebLinkAboutFire Flow Test ReportSCHULTZ ENGINEERING, LLC FIRM #12327 WATER SYSTEM FIRE HYDRANT FLOW TEST REPORT 9-19-2013 Date: Water System Owner: _Wellborn SUD Saddle Creek Subdivision Development Project: Flow Test Location: Lot 139/140 Vintage Oaks Court Nozzle size (in.): _2.5_ 50 Pitot Reading (psi): 1190 Flowrate (gpm): Discharge Coeff: (c) = 0.90 Flowrate Formula: Q=29.84cd2p1/2 c = discharge coeff. d = orifice size (in) P = pitot pressure (psi) Pressure Gauge Location: Lot 141/142 Vintage Oaks Court 80 Static Pressure (psi): Residual Pressure (psi): 45_ 1592 Computed Discharge at 20 psi Residual Pressure: OR = _ Discharge Formula: QR = QF X (hr 0.54 /hf 0.54) Note: The flow test and report were prepared in accordance with NFPA 291. Joe Schultz Report Prepared by: Ricky Flores w> PEE OF F F Others Present: Clenden Adams — Wellborn SUD Britt Curless ...... °°° q.i S-0 Wellborn Special Utility District September 18,;2013 Joe -Scl iltz Schultz Engineering, LLC 2730 Longmirer Suite A College Station,'I'esas 77845 Dear Mr, Schultz, Wellborn Special Utility District has inspected and approved thewater lines and facilities for Saddle Creek Development Phase 6. If you shontld need airy further information, please give me a call at 979-690 9799, Sincerely, Step Aen st Genet Manager P.O.Box 250 • 1118 Greens prairle Rd. #'Wellborn, TX 77881 4 979.690.9799 0 Fu 979.690.1260