HomeMy WebLinkAboutWater System AnalysisMcCI,URE & BROWNE, ENGINEERING/SURVEYING, INC. 1003 Woodcreek Dr., Suite 103 - College Station, Tx. 77845 (979) 693-3838 Engineer Reg. No. F-458 1314 10th Street, Suite 210 -Huntsville, Tx. 77320 . (936) 294-9749 Survey Reg. No. 101033-00 June 9, 2014 Erika Bridges Graduate Engineer - City of College Station P.O. Box 9960 College Station, Texas 77842 Re.: Revised Water System Analysis of Bridgewood Subdivision and College Station I.S.D. School Site #9 MBESI No. 10530014 Dear Erika, As per your requested and comments, this letter shall serve as the revised water system analysis for the entire Bridgewood Subdivision and College Station I.S.D. School Site #9. Figure "A" shows the proposed Bridgewood Subdivision water system and water model nodes and pipes. The water system -- piping was analyzed based on the following three cases and assumptions: Case 1: Water model analyzed at 1.5 g.p.m./connection. Case 2: Water model analyzed with 2,625 g.p.m. fire flow at the proposed school site and a 0.75 g.p.m./connection peak demand. Case 3: Water mode analyzed with 1,000 g.p.m. fire flow within the development and a 0.75 g.p.m./connection peak demand. Assumptions: Based on fire flow data from the City's water department (refer to Attachment "A") and the proposed layout of Phase 1, the water model was analyzed with only pressure source which is shown as Pressure Node R-1 (Elevation: 336.0) at 76 p.s.i. ® Elevation data was based on field survey and City of College Station aerial data. Peak Demand of 0.75 g.p.m./connection (2.67 persons/unit x 100 g.p.m./person/1440 min/day x 4) Fire flow required for the school site is based on 64,697 SF area of Type II-B construction which will have a sprinkler system. Therefore, the fire flow required is 2,625 g.p.m. and is split equally between Junction Nodes J-27, J-28 and J-32 in accordance with the City Fire Code. Fire flow required for the residential area is 1,000 g.p.m. as per the BCS Unified Design Guidelines and was placed on the node that created the least favorable demand on the system, which was Junction Node J-14. Hazen Williams Friction Coefficient for PVC Pipe: 140 Attachment "B" shows the water model input data based a water system consisting of 10", 8", 6" and 4" water lines within the proposed development. F91053 -Randy French10014 - Bddgewood Phase 1\DomXDes1gnMater SystemlWaler System Report-2014-0rr09.od1 Erika Bridges June 9, 2014 Page 2 Analysis Results (refer to Attachment "C"): Case 1 — The lowest pressure within the model occurs at Junction Node J-18 with a pressure of 75.9 p.s.i. The highest velocity occurs in Pipe P-15 at 1.3 f.p.s. Case 2 — The lowest pressure within the proposed development will be at Junction Node J-30 at a pressure of 65.3 p.s.i. The highest velocity occurs in Pipe P-16 at 8.8 £p.s. Case 3 —The lowest pressure within the proposed development will be at Junction Node J-18 at a pressure of 72.7 p.s.i. The highest velocity occurs in Pipe P-15 at 7.6 £p.s. Based on the above results, the proposed water system which consists of 4", 6", 8" and 10" water lines is more than capable of meeting all of the requirements of the BCS Unified Design Guidelines. As requested by the City, the water line along W. S. Phillips Parkway will be up sized to a 12" water line. Attachment "D" shows the water system input data based on this layout. Analysis Results with 12" along W. S. Phillips Parkway (refer to Attachment "E"): Case 1 — The lowest pressure within the model occurs at Junction Node J-18 with a pressure of 75.9 p.s.i. The highest velocity occurs in Pipes P-15 1.3 fp.s. Case 2 — The lowest pressure within the proposed development will be at Junction Node J-30 at a pressure of 69.1 p.s.i. The highest velocity occurs in Pipes P-16 at 8.8 ip.s. Case 3 — The lowest pressure within the proposed development will be at Junction Node J-18 at a pressure of 72.7 p.s.i. The highest velocity occurs in Pipe P-15 at 7.6 fp.s. As can be seen from the above information, the water system with the 12" water line along W. S. _ Phillips Parkway will also be more than capable of meeting all of the requirements of the BCS Unified Design Guidelines. Let me know if you have any questions or need any additional information regarding this matter. _ Sincerely, J. Dale Browne, Jr., P.E. FM President e *, ° J. DALE BROWNE, JR. �.................. -o_: 81890 F11053 - Randy FrenchM14 - Bridgewood Phase W)ocs\DesignlWater System\Water System Report-2014-OB-09.odt c A � � 7 --- BARRON ROAD/ f} \ / -- 2 \� Jill � m m §2 > m% M m%mm ch §Mk )§)m k m, ■ c %k( z m R,2 » lz S w m�s \� m r ATTACHMENT JJNT"A1�" 1 YLFiire Flow Data Provided by City of College Station M ry� Lr N 111 P P11 O 5 � � h M Cry1 M w Q w %PARKWAY o i q ariN34 V co bl$fD1 o �+ m 0 ry9' WK V cy �f Gryi 0 4Y .� O N a N Y O Ky 'd` R O 4 O � W N C5 r e Station Utilities Affordable,t Date test completed Friday February 7, 2014 Time completed 2:00 P.M. Test completed by Howard Mitchell Witness Eugene Marshall and Justin Tamplin M nw uvnPAKIT Location 4209 Belsay Nozzle size 2.5 Hydrant number V-054 - Pitot reading in PSI 80 Flow in G.P.M. 1500 STATIC HYDRANT Location W.D. Fitch and Victoria Hydrant number V-055 Static PSI 104 Residual PSI 102 Comments Requested � n � w w m� r m N � 3 w �n g�a � o � O 6 N ry 4 o O ry O P � C aw�t Ni w u] Itl N O N o M1 § G_ m n oa v 4 r 6} P M G F[i go Station Utilities Refilble, Affordable, Community Owned Date test completed Wednesday July 24, 2013 Time completed 9:00 A.M. Test completed by Justin Tamplin Witness Howard Mitchell, Jeff Boriski FLOW HYDRANT Location Castleuate Ph. 2 Sec 100 Nozzle size 2.5 Hydrant number V-100 Pitot reading in PSI 57 Flow in G.P.M. 1275 STATIC HYDRANT Location Castlegate Ph. 2 Sec 100 Hydrant number V-099 Static PSI 80 Residual PSI 76 Comments For Initial ATTACHMENT "B" Water Model with 8" & 10" Water Line along W. S. Phillips Parkway Water Model Input Data K Y P I P E 5 x x x x x x s x x x x Pipe Network Modeling Software z x s Copyrighted by KYPIPE LLC " x Version 5 - February 2010 x Date L Time: Mon Jun 09 19:50:38 2014 Master File : £:\1053 - randy french\0014 - bridgewood phase 1\docs\design\water system\water system 8 in.KYP\water system 8 in.P2K SUMMARY OF ORIGINAL DATA xsxzxxxxxzzzxzxxzxxxxxxxxxxxxzxxxxxxz�zzxxxxxxxz U N I T S S P E C I F I E➢ FLONRATE .... _._... = gallons/minute _. HEAD (HGL) .......... = feet PRESSURE ............ = psig P I P E L I N E D A T A STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P I P E NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR N A M E Al 02 (ft) (in) COEFF. LOSS COEFF. ___________________________________ P-1-XX R-2 J-3 1377.97 7.68 __-_---__--------__-_ 140.0000 0.00 -..• P-2 J-3 J-5 185.69 7.68 140.0000 0.00 P-3 J-4 J-2 81.13 5.96 140.0000 0.00 P-4 1-5 J-22 224.11 7.68 140.0000 0.00 P-5 J-5 J-6 77.16 7.68 140.0000 0.00 P-6 J-5 J-7 313.95 4.07 140.0000 0.00 P-7 J-5 J-9 380.72 5-86 140.0000 0.00 P-8 J-9 J-24 299,62 5.86 140.0000 0.00 P-9 J-8 J-10 226.02 5.66 140.0000 0.00 '_- P-10 5-10 J-4 250.31 5.86 140.0000 0.00 P-11 J-2 J-11 317.65 7.68 140.0000 0.00 P-12 J-8 J-11 294.16 5.86 140.0000 0.00 P-13 J-11 J-12 332.90 7.66 140.0000 0.00 P-14 J-12 J-16 202.46 7.68 140.0000 0.00 -- P-15 J-13 J-15 169.95 7.68 140A000 0.00 P-16 J-15 J-26 526.09 11.20 140.0000 0.00 P-17 J-13 J-14 75.20 7.68 140.0000 0.00 P-18 J-14 J-16 380.60 4.07 14C.0000 0.00 P-19 J-12 J-25 85.72 4.01 14C.0000 0.00 -- P-20 J-11 J-17 60.03 7.68 140.0000 0.00 P-21 J-17 J-20 176.52 4.01 140.0000 0.00 P-22 J-2 J-21 164.91 4.01 140.0000 0.00 P-23 J-22 J-4 193.48 7.68 140.0000 0.00 P-24 J-22 J-23 207.43 4.07 140.0000 0.00 _._ P-25 J-24 J-8 317.93 5.86 14C.0000 0.00 2-26 J-25 J-19 230.79 4.07 140.0000 0.00 P-27 J-26 R-1 116.57 11.20 140.0000 0.00 P-28 J-15 J-29 413.05 9.42 140.000D 0.00 P-29 J-16 J-13 122.32 7.68 140.0000 0.00 _.. P-30 J-1 9-28 411.32 7.68 140.0000 0.00 P-31 J-29 J-1 305.72 7.68 140.0000 0.00 P-32 J-27 J-16 215.44 7.69 140.0000 0.00 '' P-33 17-1 J-30 1606.57 7.68 140.0000 0.00 acid4emood T. J 3 0.00 313.00 J 4 5.00 323..00 J-5 6.00 318.00 J-6 5.00 318.00 J-7 11.00 312.00 J-8 9.00 320.00 ' J-9 14.00 320.00 J-10 7.00 322.00 J-11 3.00 325.00 J-1Z 0.00 339.00 J-13 0.00 329.00 --- J-14 5.00 332.00 ' J-15 0.00 330.00 5-16 0.00 330.00 J-17 2.00 326.00 5-18 13.00 335.00 --. J-19 10.00 331.00 J-20 5.00 327.80 J-21 6.00 326.00 " J-22 0.00 321.00 J-23 8.00 320.00 _.. J-24 10.00 316.00 J-25 2.00 332.03 J-26 0.00 336.00 J-27 0.00 318.00 J-28 1.00 314.00 J-29 0.00 321.00 J-30 0.00 335.00 5-32 0.00 315.00 -- R-1 ---- 336.00 511.38 R-2 ---- 300.00 530.77 --- O U T P UT O P T I ON DA TA OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE TAEUL.ATED OUTPUT MAXIMUM AND MINIMUM PRESSURES = 5 MAXIMUM AND MINIMUM VELOCITIES = 5 .-,. MAXIMUM AND MINI HEAD LOSS/1000 = 5 S Y S T E M C O N F I G U R A T I O N NUMBER OF PIPES ................ - (P) = 34 NUMBER OF END NODES ...............(j) = 31 "- NUMBER OF PRII Y LOOPS ......... - (1) = 2 NUMBER OF SUPPLY NODES .... ........ (£) = 2 NUMBER OF SUPPLY ZONES ... ......... (Z) = 1 ATTACHMENT 66C99 Water Model with 8" & 10" Water Line along W. S. Phillips Parkway Case 1 Results Case 2 Results Case 3 Results CASE 1 1.5 gpm/connection Demand _._ ------- _-_ Br?dgewood Water System C H A N G E S F O R N E X T S I M U L A T I 0 N (Change Number = 1) JUNCTION DEMANDS CHANGED - PLEASE SEE RESULTS TABLE RESULTS OBTAINED I AFTER 3 TRIALS: ACCURACY = 0.00000 P I P E L I N E R E S U L T S STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE ". P I P E NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ N A M E #1 #2 LOSS LOSS VELO. 1000 1000 ----- (gpm) (ft) (ft) ----- (ft/s) (ft/ft) ----- (ft/ft) --- ----- P-1-XX R-2 J-3 P-2 J-3 J-5 0.00 0.00 0.00 0.00 0.00 0.00 "- P-3 J-4 J-2 -62.49 0.03 0.00 0.74 0.43 0.43 P-4 J-5 J-22 -41.67 0.01 0.00 0.29 0.05 0.05 -- P-5 J-5 J-6 24.00 0.00 0.00 0.17 0.02 0.02 P-6 J-6 J-7 16.50 0.07 0.00 0.41 0.21 0.21 P-7 J-5 J-9 8.67 0.00 0.00 0.10 0.01 0.01 P-8 J-9 J-24 -12.33 0.01 0.00 0.15 0.02 0.02 P-9 J-8 J-10 9.18 0.00 0.00 0.11 0.01 0.01 -- P-10 J-10 J-4 -1.32 0.00 0.00 0.02 0.00 0.00 P-11 J-2 J-11 -71.49 0.05 0.00 0.50 0.15 0.15 -" P-12 J-8 J-11 -48.51 0.08 0.00 0.58 0.27 0.27 P-13 J-11 J-12 -135.00 0.16 0.00 0.93 0.48 0.48 P-14 J-12 J-16 -153.00 0.12 0.00 1.06 0.60 0.60 P-15 J-13 J-15 -160.00 0.14 0.00 1.25 0.81 0.81 P-16 J-15 J-26 -181.50 0.07 0.00 0.59 0.13 0.13 P-17 J-13 J-14 27.00 0.00 0.00 0.19 0.02 0.02 P-18 J-14 J-16 19.50 0.11 0.00 0.48 0.29 0.29 - P-19 J-12 J-25 18.00 0.02 0.00 0.44 0.25 0.25 P-20 J-11 J-17 10.50 0.00 0.00 0.07 0.00 0.00 P-21 J-17 J-20 7.50 0.01 0.00 0.18 0.05 0.05 P-22 J-2 J-21 9.00 0.01 0.00 0.22 0.07 0.07 P-23 J-22 J-4 -53.67 0.02 0.00 0.37 0.09 0.09 _.._. P-24 J-22 J-23 12.00 0.02 0.00 0.30 0.12 0.12 P-25 J-24 J-8 -27.33 0.03 0.00 0.33 0.09 0.09 --- P-26 J-25 J-19 15.00 0.04 0.00 0.37 0.18 0.18 P-27 J-26 R-1 -181.50 0.02 0.00 0.59 0.13 0.13 `" P-28 J-15 J-29 1.50 0.00 0.00 0.01 0.00 0.00 I(� Bridgewood Water System N O D E R E S U L T S NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE _..� ,._ (gpm) (ft) (ft) (ft) (psi) -- ----------------------------------------------------------------------- J-1 0.00 511.30 314.00 197.30 85.50 J-2 0.00 510.76 324.00 186.76 80.93 ` J-3 0.00 510.70 313.00 197.70 85.67 J-4 7.50(1.50) 510.73 323.00 187.73 81.35 J-5 9.00(1.50) 510.70 318.00 192.70 83.50 J-6 7.50(1.50) 510.70 318.00 192.70 83.50 J-7 16.50(1.50) 510.63 312.00 198.63 86.07 -I J-8 12.00(1.50) 510.73 320.00 190.73 82.65 J-9 21.00(1.50) 510.70 320.00 190.70 82.63 --'I J-10 10.50(1.50) 510.73 322.00 188.73 81.78 J-11 4.50(1.50) 510.81 325.00 165.81 80.52 J-12 0.00 510.97 330.00 180.97 78.42 J-13 0.00 511.16 329.00 182.16 78.94 J-14 7.50(1.50) 511.16 332.00 179.16 77.64 -- J-15 0.00 511.30 330.00 181.30 78.56 J-16 0.00 511.09 330.00 181.09 78.47 --- J-17 3.00(1.50) 510.81 326.00 184.81 80.08 J-18 19.50(1.50) 511.05 336.00 175.05 75.86 j J-19 15.00(1.50) 510.91 331.00 179.91 77.96 J-20 7.50(1.50) 510.80 327.00 183.80 79.65 _...� J-21 9.00(1.50) 510.75 326.00 184.75 80.06 _.. J-22 0.00 510.71 321.00 189.71 82.21 ( J-23 12.00(1.50) 510.69 320.00 190.69 82.63 J-24 15.00(1.50) 510.70 316.00 194.70 84.37 J-25 3.00(1.50) 510.95 332.00 178.95 77.54 J-26 0.00 511.37 336.00 175.37 75.99 J-27 0.00 511.09 318.00 193.09 83.67 J-2B 1.50(1.50) 511.30 314.00 197.30 85.50 J-29 0.00 511.30 321.00 190.30 82.46 J-30 0.00 511.30 335.00 176.30 76.40 J-32 0.00 511.30 318.00 193.30 83.76 R-1 ---- 511.38 336.00 175.38 76.00 R-2 ---- 530.77 300.00 230.77 100.00 M A X I M U M A N D M I N I M U M V A L U E S P R E S S U R E S `` JUNCTION MAXIMUM JUNCTION MINIMUM V E L O C I T I E S PIPE MAXIMUM PIPE MINIMUM NUMBER VELOCITY NUMBER VELOCITY (ft/s) (ft/s) --------------------- P-15 1.25 --------------------- P-28 0.01 P-14 1.06 P-30 0.01 P-29 1.06 P-31 0.01 P-13 0.93 P-10 0.02 P-3 0.74 P-20 0.07 H L+ M L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL+ML/1000 NUMBER HL+ML/1000 (ft/ft) (ft/ft) --------------------- P-15 0.81 --------------------- P-28 0.00 P-29 0.60 P-30 0.00 P-14 0.60 P-31 0.00 P-13 0.48 P-10 0.00 P-3 0.43 P-20 0.00 H L J 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL/1000 NUMBER HL/1000 (ft/ft) (ft/ft) --------------------- P-15 0.81 --------------------- P-28 0.00 P-29 0.60 P-30 0.00 P-14 0.60 P-31 0.00 P-13 0.48 P-10 0.00 P-3 0.43 P-20 0.00 S U M M A R Y O F I N F L O W S A N D O U T F L O W S (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE -------------------------------------------- R-1 181.50 R-2 0.00 CASE 2 2,625 gpm Fire Demand at School Site with 0.75 gpm/connection Peak Demand Bridgewood Water System C H A N G E S F O R N E X T S I M U L A T I 0 N (Change Number = 2) i JUNCTION DEMANDS CHANGED - PLEASE SEE RESULTS TABLE - RESULTS OBTAINED AFTER 3 TRIALS: ACCURACY = 0.00000 P I P E L I N E R E S U L T S STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P I P E NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ ---- N A M E #1 #2 LOSS LOSS VELD. 1000 1000 ---------------------------------------------------------------------------------------- (gpm) (ft) (ft) (ft/s) (ft/ft) (ft/ft) _.. P-1-XX R-2 J-3 P-2 J-3 J-5 0.00 0.00 0.00 0.00 0.00 0.00 -_ P-3 J-4 J-2 -31.25 0.01 0.00 0.37 0.12 0.12 P-4 J-5 J-22 -20.84 0.00 0.00 0.14 0.01 0.01 _-- P-5 J-5 J-6 12.00 0.00 0.00 0.08 0.01 0.01 P-6 J-6 J-7 8.25 0.02 0.00 0.20 0.06 0.06 P-7 J-5 J-9 4.34 0.00 0.00 0.05 0.00 0.00 _.. P-8 J-9 J-24 -6.16 0.00 0.00 0.07 0.01 0.01 P-9 J-8 J-10 4.59 0.00 0.00 0.05 0.00 0.00 --_� P-10 J-10 J-4 -0.66 0.00 0.00 0.01 0.00 0.00 P-11 J-2 J-11 -35.75 0.01 0.00 0.25 0.04 0.04 1 P-12 J-8 J-11 -24.25 0.02 0.00 0.29 0.07 0.07 P-13 J-11 J-12 -67.50 0.04 0.00 0.47 0.13 0.13 P-14 J-12 J-16 -76.50 0.03 0.00 0.53 0.17 0.17 P-15 J-13 J-15 -965.00 3.07 0.00 6.68 18.19 18.19 P-16 J-15 J-26 -2715.00 10.35 0.00 8.84 19.67 19.67 ._. P-17 J-13 J-14 13.50 0.00 0.00 0.09 0.01 0.01 P-18 J-14 J-18 9.75 0.03 0.00 0.24 0.08 0.08 P-19 J-12 J-25 9.00 0.01 0.00 0.22 0.07 0.07 P-20 J-11 J-17 5.25 0.00 0.00 0.04 0.00 0.00 P-21 J-17 J-20 3.75 0.00 0.00 0.09 0.01 0.01 P-22 J-2 J-21 4.50 0.00 0.00 0.11 0.02 0.02 P-23 J-22 J-4 -26.84 0.00 0.00 0.19 0.02 0.02 ,_. P-24 J-22 J-23 6.00 0.01 0.00 0.15 0.03 0.03 P-25 J-24 J-8 -13.66 0.01 0.00 0.16 0.03 0.03 -- P-26 J-25 J-19 7.50 0.01 0.00 0.18 0.05 0.05 P-27 J-26 R-1 -2715.00 2.29 0.00 8.84 19.67 19.67 P-28 J-15 J-29 1750.00 6.37 0.00 8.06 20.26 20.26 N 0 D E R E S U L T S NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE (gpm) (ft) (ft) (ft) (psi) -- ------------------------------------------------------------------------------ J-1 0.00 485.74 314.00 171.74 74.42 J-2 0.00 493.41 324.00 169.41 73.41 J-3 0.00 493.40 313.00 180.40 78.17 J-4 3.75(0.75) 493.40 323.00 170.40 73.84 --- J-5 4.50(0.75) 493.40 318.00 175.40 76.00 " J-6 3.75(0.75) 493.40 318.00 175.40 76.00 J-7 8.25(0.75) 493.38 312.00 181.38 78.60 -- J-8 6.00(0.75) 493.40 320.00 173.40 75.14 J-9 10.50(0.75) 493.39 320.00 173.39 75.14 --' J-10 5.25(0.75) 493.40 322.00 171.40 74.27 J-11 2.25(0.75) 493.43 325.00 168.43 72.98 J-12 0.00 493.47 330.00 163.47 70.84 J-13 0.00 495.67 329.00 166.67 72.22 J-14 3.75(0.75) 495.67 332.00 163.67 70.92 J-15 0.00 498.74 330.00 168.74 73.12 J-16 0.00 493.50 330.00 163.50 70.85 J-17 1.50(0.75) 493.43 326.00 167.43 72.55 J-18 9.75(0.75) 495.64 336.00 159.64 69.18 J-19 7.50(0.75) 493.45 331.00 162.45 70.40 J-20 3.75(0.75) 493.42 327.00 166.42 72.12 J-21 4.50(0.75) 493.41 326.00 167.41 72.54 -- J-22 0.00 493.40 321.00 172.40 74.71 J-23 6.00(0.75) 493.39 320.00 173.39 75.14 -- J-24 7.50(0.75) 493.40 316.00 177.40 76.87 J-25 1.50(0.75) 493.46 332.00 161.46 69.97 J-26 0.00 509.09 336.00 173.09 75.01 J-27 875.00 490.24 318.00 172.24 74.64 " J-28 875.00( ** ) 479.50 314.00 165.50 71.72 J-29 0.00 490.38 321.00 169.38 73.40 J-30 0.00 485.74 335.00 150.74 65.32 ._-. J-32 875.00 487.21 318.00 169.21 73.32 R-1 ---- 511.38 336.00 175.38 76.00 R-2 ---- 530.77 300.00 230.77 100.00 M A X I M U M A N D M I N I M U M V A L U E S P R E S S U R E S JUNCTION MAXIMUM JUNCTION MINIMUM Bridgewood Water System V E L O C I T I E S PIPE MAXIMUM PIPE MINIMUM NUMBER VELOCITY NUMBER VELOCITY _. (ft/s) (ft/s) " --------------------- P-16 8.84 --------------------- P-10 0.01 P-27 8.84 P-20 0.04 P-28 8.06 P-7 0.05 P-15 6.68 P-9 0.05 P-29 6.59 P-8 0.07 " H L+ML / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL+ML/1000 NUMBER HL+ML/1000 (ft/ft) (ft/ft) --------------------- P-28 20.26 --------------------- P-10 0.00 P-16 19.67 P-20 0.00 - P-27 19.67 P-7 0.00 P-15 18.19 P-9 0.00 P-29 17.72 P-5 0.01 H L / 1 0 0 0 ..... PIPE MAXIMUM PIPE MINIMUM --- NUMBER HL/1000 NUMBER HL/1000 (ft/ft) (ft/ft) --------------------- P-28 20.26 ------- P-10 0.00 P-16 19.67 P-20 0.00 P-27 19.67 P-7 0.00 P-15 18.19 P-9 0.00 P-29 17.72 P-5 0.01 S U M M A R Y O F I N F L O W S A N D O U T F L O W S (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES "-- NODE FLOWRATE NODE NAME (gpm) TITLE -------------------------------------------- R-1 2715.00 " R-2 0.00 CASE 3 1,000 gpm Fire Demand within the Developmnet with 0.75 gpm/connection Peak Demand C H A N G E S F O R N E X T S I M U L A T I O N (Change Number = 3) JUNCTION DEMANDS CHANGED - PLEASE SEE RESULTS TABLE RESULTS OBTAINED AFTER 3 TRIALS: ACCURACY = 0.00000 P I P E L I N E R E S U L T S STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P I P E NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ N A M E #1 #2 LOSS LOSS VELO. 1000 1000 (gpm) (ft) (ft) (ft/s) (ft/ft) (ft/ft) P-1-XX R-2 J-3 P-2 J-3 J-5 0.00 0.00 0.00 0.00 0.00 0.00 P-3 J-4 J-2 -31.25 0.01 0.00 0.37 0.12 0.12 P-4 J-5 J-22 -20.84 0.00 0.00 0.14 0.01 0.01 P-5 J-5 J-6 12.00 0.00 0.00 0.08 0.01 0.01 P-6 J-6 J-7 8.25 0.02 0.00 0.20 0.06 0.06 P-7 J-5 J-9 4.34 0.00 0.00 0.05 0.00 0.00 P-8 J-9 J-24 -6.16 0.00 0.00 0.07 0.01 0.01 P-9 J-8 J-10 4.59 0.00 0.00 0.05 0.00 0.00 P-10 J-10 J-4 -0.66 0.00 0.00 0.01 0.00 0.00 P-11 J-2 J-11 -35.75 0.01 0.00 0.25 0.04 0.04 P-12 J-8 J-11 -24.25 0.02 0.00 0.29 0.07 0.07 P-13 J-11 J-12 -67.50 0.04 0.00 0.47 0.13 0.13 P-14 J-12 J-16 -76.50 0.03 0.00 0.53 0.17 0.17 P-15 J-13 J-15 -1091.25 3.86 0.00 7.56 22.84 22.84 P-16 J-15 J-26 -1091.25 1.91 0.00 3.55 3.64 3.64 P-17 J-13 J-14 1014.75 1.50 0.00 7.03 19.96 19.96 P-18 J-14 J-18 9.75 0.03 0.00 0.24 0.08 0.08 P-19 J-12 J-25 9.00 0.01 0.00 0.22 0.07 0.07 P-20 J-11 J-17 5.25 0.00 0.00 0.04 0.00 0.00 P-21 J-17 J-20 3.75 0.00 0.00 0.09 0.01 0.01 P-22 J-2 J-21 4.50 0.00 0.00 0.11 0.02 0.02 P-23 J-22 J-4 -26.84 0.00 0.00 0-19 0.02 0.02 P-24 J-22 J-23 6.00 0.01 0.00 0.15 0.03 0.03 P-25 J-24 J-8 -13.66 0.01 0.00 0.16 0.03 0.03 P-26 J-25 J-19 7.50 0.01 0.00 0.18 0.05 0.05 P-27 J-26 R-1 -1091.25 0.42 0.00 3.55 3.64 3.64 P-28 J-15 J-29 0.00 0.00 0.00 0.00 0.00 0.00 Bridgewood Water System N 0 D E R E S U L T S NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE ------------------------------------------------------------------------------ (gpm) (ft) (ft) (ft) (psi) _.. J-1 0.00 509.05 314.00 195.05 84.52 J-2 0.00 505.08 324.00 181.08 78.47 J-3 0.00 505.06 313.00 192.06 83.23 J-4 3.75(0.75) 505.07 323.00 182.07 78.90 ' J-5 4.50(0.75) 505.06 318.00 187.06 81.06 J-6 3.75(0.75) 505.06 318.00 187.06 81.06 J-7 8.25(0.75) 505.04 312.00 193.04 83.65 __. J-8 6.00(0.75) 505.07 320.00 185.07 80.20 J-9 10.50(0.75) 505.06 320.00 185.06 80.19 J-10 5.25(0.75) 505.07 322.00 183.07 79.33 J-11 2.25(0.75) 505.09 325.00 180.09 78.04 J-12 0.00 505.14 330.00 175.14 75.89 J-13 0.00 505.19 329.00 176.19 76.35 J-14 1005.00( ** ) 503.69 332.00 171.69 74.40 __. J-15 0.00 509.05 330.00 179.05 77.59 J-16 0.00 505.17 330.00 175.17 75.91 ..-. J-17 1.50(0.75) 505.09 326.00 179.09 77.61 J-18 9.75(0.75) 503.66 336.00 167.66 72.65 J-19 7.50(0.75) 505.12 331.00 174.12 75.45 J-20 3.75(0.75) 505.09 327.00 178.09 77.17 J-21 4.50(0.75) 505.08 326.00 179.08 77.60 J-22 0.00 505.06 321.00 184.06 79.76 J-23 6.00(0.75) 505.06 320.00 185.06 80.19 ..-. J-24 7.50(0.75) 505.06 316.00 189.06 81.93 J-25 1.50(0.75) 505.13 332.00 173.13 75.02 -- J-26 0.00 510.96 336.00 174.96 75.82 J-27 0.00 505.17 318.00 187.17 81.11 J-28 0.00 (0.00) 509.05 314.00 195.05 84.52 J-29 0.00 509.05 321.00 188.05 81.49 J-30 0.00 509.05 335.00 174.05 75.42 J-32 0.00 509.05 318.00 191.05 82.79 R-1 ---- 511.38 336.00 175.38 76.00 R-2 ---- 530.77 300.00 230.77 100.00 M A X I M U M A N D M I N I M U M V A L U E S P R E S S U R E S JUNCTION MAXIMUM JUNCTION MINIMUM V E L O C I T I E S PIPE MAXIMUM PIPE MINIMUM NUMBER VELOCITY NUMBER VELOCITY (ft/s) (ft/s) --------------------- P-15 7.56 --------------------- P-10 0.01 P-17 7.03 P-20 0.04 P-16 3.55 P-7 0.05 P-27 3.55 P-9 0.05 P-14 0.53 P-8 0.07 H L+ M L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL+ML/1000 NUMBER HL+ML/1000 (ft/ft) (ft/ft) --------------------- P-15 22.84 --------------------- P-10 0.00 P-17 19.96 P-20 0.00 P-16 3.64 P-7 0.00 P-27 3.64 P-9 0.00 P-14 0.17 P-5 0.01 H L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL/1000 NUMBER HL/1000 (ft/ft) (ft/ft) --------------------- P-15 22.84 --------------------- P-10 0.00 P-17 19.96 P-20 0.00 P-16 3.64 P-7 0.00 P-27 3.64 P-9 0.00 P-14 0.17 P-5 0.01 S U M M A R Y O F I N F L O W S A N D O U T F L O W S (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE -------------------------------------------- R-1 1091.25 R-2 0.00 ATTACHMENT ('D" Water Model with 12" Water Line along W. S. Phillips Parkway Water Model Input Data s s x x x x x z x* K Y P I P E 5 x Pipe Network Modeling Software x h * Copyrighted by KYPIPE III * Version 5 - February 2010 x x z s z x x z z z x z x x x z s z x s s z x x x a x z x Date 5 Time: Mon Jun 09 19:27:00 2014 Master File : f:\1053 - randy french\0014 - bridgewood phase 1\docs\design\water system\water system 12 in.KYP\water system 12 in.P2K xxxzxzzxxxzxxzxxxxxxxxxxsxxxxxxxxxzxzzxzzzzxxssx SUMMARY OF ORIGINAL DATA z zxxxxzzxzx zxxxxxxxxxxxzss:xxxxsszszssszzzzxxxxx UNITS SPECIFIED FLONRATE ............ = gallons/minute HEAD (HGL) .......... = feet PRESSURE ............ = psig P I P E L I N E D A T A STATUS CODE: X -CLOSED PIPE CV -CHECK VALUE P I P E NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR N A M E #1 02 (£t) (in) COEFF. LOSS COEFF. -------------------------------------------------------------- P-1-XK R-2 J-3 1245.52 7-68 140.0000 0.00 P-2 J-3 J-5 183.89 7.68 140.0000 0.00 P-3 J-4 J-2 81.68 5.86 140.0000 0.00 P-4 J-5 J-22 276.79 7.68 140.0000 0.00 P-5 J-5 J-6 85.05 7.68 140.0000 0.00 P-6 J-6 J-7 215.33 4.07 140.0000 0.00 P-7 J-5 J-9 513.53 5.86 140.0000 0.00 P-8 J-9 J-24 306-28 5.86 140.0000 0-00 P-9 J-8 J-10 214.32 5.86 140.0000 0.00 P-10 J-10 3-4 261.24 5.86 140.0000 0.00 P-11 J-2 J-11 323.71 7.68 140.0000 B.00 P-12 J-8 J-11 292.B2 5.B6 140.0000 0.00 P-13 J-11 J-12 332.07 7.63 140.0000 0.00 P-14 J-12 J-16 202.46 7.68 140.0000 0.00 P-15 J-13 J-15 169.95 7.69 140.0000 0.00 P-16 J-15 J-26 526.09 11.20 140.0000 0.00 P-17 J-13 J-14 57.97 7.68 140.0000 0.00 P-18 J-14 J-18 412.51 4.07 140.0000 0.00 P-19 J-12 J-25 61.43 4.07 140.0000 0.00 P-20 J-11 J-17 75.05 7.68 140.0000 0.00 P-21 J-17 J-20 192.67 4.07 140.0000 0.00 P-22 J-2 J-21 183.74 4.07 140.0000 0.00 P-23 J-22 J-4 214.81 7.69 140-0000 0.00 P-24 J-22 J-23 141.99 4.07 140.0000 0.00 P-25 J-24 J-G 316.52 5-86 140.0000 0.00 P-26 J-25 J-19 253.95 4.07 140.0000 0.00 P-27 J-26 R-1 116.57 11.20 140.0000 0.00 P-28 J-15 J-29 413.05 11.20 140.0080 0.00 P-29 J-16 J-13 122.32 7.68 140.0000 0.00 2-30 J-1 J-28 411.32 7.68 140.0000 0.00 P-31 J-29 J-1 3B5.72 11.20 140.0000 0.00 P-32 J-27 J-16 215.44 7.60 140.0000 0.00 P-33 J-1 J-30 1606.57 11-20 140.0000 0.00 J-4 5.00 323.00 J-5 6.00 318.00 _.: J-6 5.00 313.00 J-7 11.00 312.00 J-8 8.00 320.00 J-9 14.00 320.00 J-10 7.00 322.00 .. J-11 3.00 325.00 J-12 0.00 330.00 J-13 0.00 329.00 J-14 5.00 332.00 J-15 0.00 330.90 J-16 0.00 330.00 J-17 2.00 326.00 J-18 13.00 336.00 --- J-19 10.00 331.00 J-20 5.00 327.00 J-21 6.00 326.00 J-22 0.00 321.00 J-23 8.00 320.00 J-24 10.00 316.00 J-25 2.00 332.00 J-26 0.00 336.00 J-27 0.00 318.00 J-28 1.00 314.00 -- J-29 0.00 321.00 J-30 0.00 335.00 J-32 0_00 318.00 R-1 336.00 511.38 R-2 ---- 300.00 530.77 --" O U T P U T O P T I O N D A T A OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE TABULATED OUTPUT MAXIMUM AND MINIMUM PRESSURES 5 I IMUM AND MINIMUM VELOCITIES = 5 ---' MAXIMUM AND MINIMUM HEAD LOSS/1000 = 5 S Y S T E M C O N F I G U R A T I O N NUMBER OF PIPES ..... .............. (P) = 34 NU[O3ER OF END NODES ...............(j) = 31 NUMBER OF PRIMARY LOOPS ...........(1) = 2 NUMBER OF SUPPLY NODES ............(£) = 2 NUMBER OF SUPPLY ZONES ............(2) = 1 ATTACHMENT 66 T99 Waters Model with 12'"Water Line along W. S. Phillips Parkway Case 1 Results Case 2 Results Case 3 Results CASE 1 1.5 gpm/connection Demand C H A N G E S F O R N E X T S I M U L A T I 0 N (Change Number = 1) JUNCTION DEMANDS CHANGED - PLEASE SEE RESULTS TABLE RESULTS OBTAINED AFTER 3 TRIALS: ACCURACY = 0.00000 P I P E L I N E STATUS CODE: P I P E N A M E R E S U L T S XX -CLOSED PIPE NODE NUMBERS #1 #2 CV -CHECK VALVE FLOWRATE (gPm) HEAD MINOR LINE HL+ML/ HL/ LOSS LOSS VELO. 1000 1000 (ft) (ft) (ft/s) (ft/ft) (ft/ft) P-1-XX R-2 J-3 P-2 J-3 J-5 0.00 0.00 0.00 0.00 0.00 0.00 P-3 J-4 J-2 -62.10 0.03 0.00 0.74 0.42 0.42 P-4 J-5 J-22 -40.65 0.01 0.00 0.28 0.05 0.05 P-5 J-5 J-6 24.00 0.00 0.00 0.17 0.02 0.02 P-6 J-6 J-7 16.50 0.05 0.00 0.41 0.21 0.21 P-7 J-5 J-9 7.65 0.00 0.00 0.09 0.01 0.01 P-8 J-9 J-24 -13.35 0.01 0.00 0.16 0.02 0.02 P-9 J-8 J-10 8.55 0.00 0.00 0.10 0.01 0.01 P-10 J-10 J-4 -1.95 0.00 0.00 0.02 0.00 0.00 P-11 J-2 J-11 -71.10 0.05 0.00 0.49 0.15 0.15 P-12 J-8 J-11 -48.90 0.08 0.00 0.58 0.27 0.27 P-13 J-11 J-12 -135.00 0.16 0.00 0.93 0.48 0.48 P-14 J-12 J-16 -153.00 0.12 0.00 1.06 0.60 0.60 P-15 J-13 J-15 -180.00 0.14 0.00 1.25 0.81 0.81 P-16 J-15 J-26 -181.50 0.07 0.00 0.59 0.13 0.13 P-17 J-13 J-14 27.00 0.00 0.00 0.19 0.02 0.02 P-18 J-14 J-18 19.50 0.12 0.00 0.48 0.29 0.29 P-19 J-12 J-25 18.00 0.02 0.00 0.44 0.25 0.25 P-20 J-11 J-17 10.50 0.00 0.00 0.07 0.00 0.00 P-21 J-17 J-20 7.50 0.01 0.00 0.18 0.05 0.05 P-22 J-2 J-21 9.00 0.01 0.00 0.22 0.07 0.07 P-23 J-22 J-4 -52.65 0.02 0.00 0.36 0.08 0.08 P-24 J-22 J-23 12.00 0.02 0.00 0.30 0.12 0.12 P-25 J-24 J-8 -28.35 0.03 0.00 0.34 0.10 0.10 P-26 J-25 J-19 15.00 0.05 0.00 0.37 0.18 0.18 P-27 J-26 R-1 -181.50 0.02 0.00 0.59 0.13 0.13 P-28 J-15 J-29 1.50 0.00 0.00 0.00 0.00 0.00 N 0 D E R E S U L T S NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE ------------------------------------------------------------------------------ (gpm) (ft) (ft) (ft) (psi) J-1 0.00 511.30 314.00 197.30 85.50 J-2 0.00 510.76 324.00 186.76 80.93 J-3 0.00 510.70 313.00 197.70 85.67 J-4 7.50(1.50) 510.73 323.00 187.73 81.35 J-5 9.00(1.50) 510.70 318.00 192.70 83.50 J-6 7.50(1.50) 510.69 318.00 192.69 83.50 J-7 16.50(1.50) 510.65 312.00 198.65 86.08 J-8 12.00(1.50) 510.73 320.00 190.73 82.65 J-9 21.00(1.50) 510.69 320.00 190.69 82.63 J-10 10.50(1.50) 510.73 322.00 188.73 61.78 J-11 4.50(1.50) 510.81 325.00 185.81 80.52 J-12 0.00 510.97 330.00 180.97 78.42 J-13 0.00 511.16 329.00 182.16 78.94 J-14 7.50(1.50) 511.16 332.00 179.16 77.64 J-15 0.00 511.30 330.00 181.30 78.56 J-16 0.00 511.09 330.00 181.09 78.47 J-17 3.00(1.50) 510.81 326.00 184.81 80.08 J-18 19.50(1.50) 511.04 336.00 175.04 75.85 J-19 15.00(1.50) 510.91 331.00 179.91 77.96 J-20 7.50(1.50) 510.80 327.00 183.80 79.65 J-21 9.00(1.50) 510.75 326.00 184.75 80.06 J-22 0.00 510.71 321.00 189.71 82.21 J-23 12.00(1.50) 510.69 320.00 190.69 82.63 J-24 15.00(1.50) 510.70 316.00 194.70 84.37 J-25 3.00(1.50) 510.95 332.00 178.95 77.55 J-26 0.00 511.37 336.00 175.37 75.99 J-27 0.00 511.09 318.00 193.09 83.67 J-28 1.50(1.50) 511.30 314.00 197.30 85.50 J-29 0.00 511.30 321.00 190.30 82.46 J-30 0.00 511.30 335.00 176.30 76.40 J-32 0.00 511.30 318.00 193.30 83.76 R-1 ---- 511.38 336.00 175.38 76.00 R-2 ---- 530.77 300.00 230.77 100.00 M A X I M U M A N D M I N I M U M V A L U E S P R E S S U R E S JUNCTION MAXIMUM JUNCTION MINIMUM V E L O C I T I E S PIPE MAXIMUM PIPE MINIMUM NUMBER VELOCITY NUMBER VELOCITY (ft/s) (ft/s) P-15 1.25 P-28 0.00 P-14 1.06 P-31 0.00 P-29 1.06 P-30 0.01 P-13 0.93 P-10 0.02 P-3 0.74 P-20 0.07 H L+ M L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL+ML/1000 NUMBER HL+ML/1000 (ft/ft) (ft/ft) --------------------- P-15 0.81 --------------------- P-28 0.00 P-29 0.60 P-31 0.00 P-14 0.60 P-30 0.00 P-13 0.48 P-10 0.00 P-3 0.42 P-20 0.00 H L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL/1000 NUMBER HL/1000 (ft/ft) (ft/ft) --- P-15 0.81 P-28 0.00 P-29 0.60 P-31 0.00 P-14 0.60 P-30 0.00 P-13 0.48 P-10 0.00 P-3 0.42 P-20 0.00 S U M M A R Y O F I N F L O W S A N D O U T F L O W S (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE -------------------------------------------- R-1 181.50 P-9 n_nn CASE 2 2,625 gpm Fire Demand at School Site with 0.75 gpm/connection Peak Demand C H A N G E S F O R N E X T S I M U L A T I O N (Change Number = 2) JUNCTION DEMANDS CHANGED - PLEASE SEE RESULTS TABLE RESULTS OBTAINED AFTER 3 TRIALS: ACCURACY = 0.00000 P I P E L I N E R E S U L T S STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P I P E NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ N A M E #1 #2 LOSS LOSS VELD. 1000 1000 (gpm) (ft) (ft) (ft/s) (ft/ft) (ft/ft) P-1-XX R-2 J-3 P-2 J-3 J-5 0.00 0.00 0.00 0.00 0.00 0.00 P-3 J-4 J-2 -31.05 0.01 0.00 0.37 0.12 0.12 P-4 J-5 J-22 -20.32 0.00 0.00 0.14 0.01 0.01 P-5 J-5 J-6 12.00 0.00 0.00 0.08 0.01 0.01 P-6 J-6 J-7 8.25 0.01 0.00 0.20 0.06 0.06 P-7 J-5 J-9 3.82 0.00 0.00 0.05 0.00 0.00 P-8 J-9 J-24 -6.68 0.00 0.00 0.08 0.01 0.01 P-9 J-8 J-10 4.27 0.00 0.00 0.05 0.00 0.00 P-10 J-10 J-4 -0.98 0.00 0.00 0.01 0.00 0.00 P-11 J-2 J-11 -35.55 0.01 0.00 0.25 0.04 0.04 P-12 J-8 J-11 -24.45 0.02 0.00 0.29 0.08 0.08 P-13 J-11 J-12 -67.50 0.04 0.00 0.47 0.13 0.13 P-14 J-12 J-16 -76.50 0.03 0.00 0.53 0.17 0.17 P-15 J-13 J-15 -965.00 3.07 0.00 6.68 18.19 18.19 P-16 J-15 J-26 -2715.00 10.35 0.00 8.84 19.67 19.67 P-17 J-13 J-14 13.50 0.00 0.00 0.09 0.01 0.01 P-18 J-14 J-18 9.75 0.03 0.00 0.24 0.08 0.08 P-19 J-12 J-25 9.00 0.00 0.00 0.22 0.07 0.07 P-20 J-11 J-17 5.25 0.00 0.00 0.04 0.00 0.00 P-21 J-17 J-20 3.75 0.00 0.00 0.09 0.01 0.01 P-22 J-2 J-21 4.50 0.00 0.00 0.11 0.02 0.02 P-23 J-22 J-4 -26.32 0.00 0.00 0.18 0.02 0.02 P-24 J-22 J-23 6.00 0.00 0.00 0.15 0.03 0.03 P-25 J-24 J-8 -14.18 0.01 0.00 0.17 0.03 0.03 P-26 J-25 J-19 7.50 0.01 0.00 0.18 0.05 0.05 P-27 J-26 R-1 -2715.00 2.29 0.00 8.84 19.67 19.67 P-28 J-15 J-29 1750.00 3.60 0.00 5.70 8.72 8.72 I Bridgewood Water System N 0 D E R E S U L T S NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE (gpm) (ft) (ft) (ft) (psi) --- ------------------------------------------------------------------------------ J-1 0.00 494.40 314.00 180.40 78.17 J-2 0.00 493.41 324.00 169.41 73.41 -- J-3 0.00 493.39 313.00 180.39 78.17 J-4 3.75(0.75) 493.40 323.00 170.40 73.84 J-5 4.50(0.75) 493.39 318.00 175.39 76.00 J-6 3.75(0.75) 493.39 318.00 175.39 76.00 J-7 8.25(0.75) 493.38 312.00 181.38 78.60 J-8 6.00(0.75) 493.40 320.00 173.40 75.14 J-9 10.50(0.75) 493.39 320.00 173.39 75.14 -- J-10 5.25(0.75) 493.40 322.00 171.40 74.27 J-11 2.25(0.75) 493.43 325.00 168.43 72.98 J-12 0.00 493.47 330.00 163.47 70.84 J-13 0.00 495.67 329.00 166.67 72.22 J-14 3.75(0.75) 495.67 332.00 163.67 70.92 -... J-15 0.00 498.74 330.00 168.74 73.12 J-16 0.00 493.50 330.00 163.50 70.85 --- J-17 1.50(0.75) 493.43 326.00 167.43 72.55 J-18 9.75(0.75) 495.64 336.00 159.64 69.18 J-19 7.50(0.75) 493.45 331.00 162.45 70.40 J-20 3.75(0.75) 493.42 327.00 166.42 72.12 J-21 4.50(0.75) 493.41 326.00 167.41 72.54 J-22 0.00 493.40 321.00 172.40 74.71 J-23 6.00(0.75) 493.39 320.00 173.39 75.14 -- J-24 7.50(0.75) 493.40 316.00 177.40 76.87 J-25 1.50(0.75) 493.47 332.00 161.47 69.97 J-26 0.00 509.09 336.00 173.09 75.01 J-27 875.00 490.24 318.00 172.24 74.64 J-28 875.00( ** ) 488.16 314.00 174.16 75.47 J-29 0.00 495.14 321.00 174.14 75.46 J-30 0.00 494.40 335.00 159.40 69.07 J-32 875.00 491.97 318.00 173.97 75.39 R-1 ---- 511.38 336.00 175.38 76.00 R-2 ---- 530.77 300.00 230.77 100.00 M A X I M U M A N D M I N I M U M V A L U E S -- P R E S S U R E S JUNCTION MAXIMUM JUNCTION MINIMUM Water S,,>stem V E L O C I T I E S PIPE MAXIMUM PIPE MINIMUM NUMBER VELOCITY NUMBER VELOCITY (ft/s) (ft/s) P-16 8.84 P-10 0.01 P-27 8.84 P-20 0.04 P-15 6.68 P-7 0.05 P-29 6.59 P-9 0.05 P-30 6.06 2-8 0.08 H L+ M L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL+ML/1000 NUMBER HL+ML/1000 (ft/ft) (ft/ft) P-16 19.67 P-10 0.00 P-27 19.67 P-20 0.00 P-15 18.19 P-7 0.00 P-29 17.72 P-9 0.00 P-30 15.17 P-5 0.01 H L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL/1000 NUMBER HL/1000 (ft/ft) (ft/ft) P-16 19.67 P-10 0.00 P-27 19.67 P-20 0.00 P-15 18.19 P-7 0.00 P-29 17.72 P-9 0.00 P-30 15.17 P-5 0.01 S U M M A R Y O F I N F L O W S A N D O U T F L O W S (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE -------------------------------------------- R-1 2715.00 R-2 0.00 CASE 3 1,000 gpm Fire Demand within the Developmnet with 0.75 gpm/connection Peak Demand Bridgewood Water System _.... C H A N G E S F O R N E X T S I M U L A T I 0 N (Change Number = 3) JUNCTION DEMANDS I CHANGED - PLEASE SEE RESULTS TABLE ..'.i RESULTS OBTAINED AFTER 3 TRIALS: ACCURACY = 0.00000 P I P E L I N E R E S U L T S STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P I P E NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ ,i N A M E #1 #2 LOSS LOSS VELO. 1000 1000 ---------------------------------------------------------------------------------------- (gpm) (ft) (ft) (ft/5) (ft/ft) (ft/ft) -- P-1-XX R-2 J-3 P-2 J-3 J-5 0.00 0.00 0.00 0.00 0.00 0.00 -• P-3 J-4 J-2 -31.05 0.01 0.00 0.37 0.12 0.12 P-4 J-5 J-22 -20.32 0.00 0.00 0.14 0.01 0.01 - P-5 J-5 J-6 12.00 0.00 0.00 0.08 0.01 0.01 P-6 J-6 J-7 8.25 0.01 0.00 0.20 0.06 0.06 P-7 J-5 J-9 3.82 0.00 0.00 0.05 0.00 0.00 -- P-8 J-9 J-24 -6.68 0.00 0.00 0.08 0.01 0.01 P-9 J-8 J-10 4.27 0.00 0.00 0.05 0.00 0.00 -- P-10 J-10 J-4 -0.98 0.00 0.00 0.01 0.00 0.00 P-11 J-2 J-11 -35.55 0.01 0.00 0.25 0.04 0.04 P-12 J-8 J-11 -24.45 0.02 0.00 0.29 0.08 0.08 P-13 J-11 J-12 -67.50 0.04 0.00 0.47 0.13 0.13 _ P-14 J-12 J-16 -76.50 0.03 0.00 0.53 0.17 0.17 P-15 J-13 J-15 -1091.25 3.86 0.00 7.56 22.84 22.84 P-16 J-15 J-26 -1091.25 1.91 0.00 3.55 3.64 3.64 P-17 J-13 J-14 1014.75 1.16 0.00 7.03 19.96 19.96 P-18 J-14 J-18 9.75 0.03 0.00 0.24 0.08 0.08 P-19 J-12 J-25 9.00 0.00 0.00 0.22 0.07 0.07 P-20 J-11 J-17 5.25 0.00 0.00 0.04 0.00 0.00 P-21 J-17 J-20 3.75 0.00 0.00 0.09 0.01 0.01 P-22 J-2 J-21 4.50 0.00 0.00 0.11 0.02 0.02 P-23 J-22 J-4 -26.32 0.00 0.00 0.18 0.02 0.02 _-... P-24 J-22 J-23 6.00 0.00 0.00 0.15 0.03 0.03 P-25 J-24 J-8 -14.18 0.01 0.00 0.17 0.03 0.03 P-26 J-25 J-19 7.50 0.01 0.00 0.18 0.05 0.05 P-27 J-26 R-1 -1091.25 0.42 0.00 3.55 3.64 3.64 I P-28 J-15 J-29 0.00 0.00 0.00 0.00 0.00 0.00 N 0 D E R E S U L T S NODE NODE NAME TITLE J-1 J-2 J-3 J-4 J-5 J-6 J-7 J-8 J-9 J-10 J-11 J-12 J-13 J-14 J-15 J-16 J-17 J-18 J-19 J-20 J-21 J-22 J-23 J-24 J-25 J-26 J-27 J-28 J-29 J-30 J-32 R-1 R-2 water EXTERNAL HYDRAULIC NODE PRESSURE NODE DEMAND GRADE ELEVATION HEAD PRESSURE (gpm) ------------------------------------------------ (ft) (ft) (ft) (psi) 0.00 509.05 314.00 195.05 34.52 0.00 505.08 324.00 181.08 78.47 0.00 505.06 313.00 192.06 83.23 3.75(0.75) 505.07 323.00 182.07 78.90 4.50(0.75) 505.06 318.00 187.06 81.06 3.75(0.75) 505.06 318.00 187.06 81.06 8.25(0.75) 505.05 312.00 193.05 83.65 6.00(0.75) 505.07 320.00 185.07 80.20 10.50(0.75) 505.06 320.00 185.06 80.19 5.25(0.75) 505.07 322.00 183.07 79.33 2.25(0.75) 505.09 325.00 180.09 78.04 0.00 505.14 330.00 175.14 75.89 0.00 505.19 329.00 176.19 76.35 1005.00( ** } 504.03 332.00 172.03 74.55 0.00 509.05 330.00 179.05 77.59 0.00 505.17 330.00 175.17 75.91 1.50(0.75) 505.09 326.00 179.09 77.61 9.75(0.75) 504.00 336.00 168.00 72.80 7.50(0.75) 505.12 331.00 174.12 75.45 3.75(0.75) 505.09 327.00 178.09 77.17 4.50(0.75) 505.07 326.00 179.07 77.60 0.00 505.06 321.00 184.06 79.76 6.00(0.75) 505.06 320.00 185.06 80.19 7.50(0.75) 505.06 316.00 189.06 81.93 1.50(0.75) 505.13 332.00 173.13 75.02 0.00 510.96 336.00 174.96 75.82 0.00 505.17 316.00 187.17 81.11 0_00(0.00) 509.05 314.00 195.05 84.52 0.00 509.05 321.00 188.05 81.49 0.00 509.05 335.00 174.05 75.42 0.00 509.05 318.00 191.05 82.79 ---- 511.38 336.00 175.38 76.00 ---- 530.77 300.00 230.77 100.00 M A X I M U M A N D M I N I M U M V A L U E S P R E S S U R E S JUNCTION MAXIMUM JUNCTION MINIMUM Water System V E L O C I T I E S PIPE MAXIMUM PIPE MINIMUM NUMBER VELOCITY NUMBER VELOCITY (ft/s) (ft/s) P-15 7.56 P-10 0.01 P-17 7.03 P-20 0.04 P-16 3.55 P-7 0.05 P-27 3.55 P-9 0.05 P-14 0.53 P-8 0.08 H L+ M L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL+ML/1000 NUMBER HL+ML/1000 (ft/ft) (ft/ft) P-15 22.84 P-10 0.00 P-17 19.96 P-20 0.00 P-16 3.64 P-7 0.00 P-27 3.64 P-9 0.00 P-14 0.17 P-5 0.01 H L / 1 0 0 0 PIPE MAXIMUM PIPE MINIMUM NUMBER HL/1000 NUMBER HL/1000 (ft/ft) (ft/ft) P-15 22.84 P-10 0.00 P-17 19.96 P-20 0.00 P-16 3.64 P-7 0.00 P-27 3.64 P-9 0.00 P-14 0.17 P-5 0.01 S U M M A R Y O F I N F L O W S A N D O U T F L O W S (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE -------------------------------------------- R-1 1091.25 R-2 0.00