Loading...
HomeMy WebLinkAboutFire Flow CalculationNEW BUILDING FOR SEIDEL SCHROEDER AND COMP ANY CITY OF COLLEGE STATION JC JOB #C0007-005-00 FIRE FLOW CALCULATION CALCULATED FLOW Fire Flow at hydrant S09-0l 7: With 98-psi pressure at Static Hydrant G-097: Qr = 29.83cdD2.jP; Q, = (29.83)(0.9)(2.5)2.J70=1,404 gpm Qf = Qr (_P_s_-_2_0]0.54 Ps -Pr ( 98-20)0 ' 54 QI = (1,404) 98 _88 = 4,257 gpm Where: Q, = residual flow at the pitot pressure (gpm) Q 1 = Fire Flow (gpm) cd = friction loss (usually 0.9 for smooth opening) D = diameter of opening in inches (2.5 in most cases) PP = pitot pressure (psig) P, = residual pressure (psig) Ps = static pressure (psig) REOUIRED FLOW Building Type= VB (Section 602 and 1505 of 2000 Internationa 73uz Fire Area = 7,469 square feet (Section Bl04 of 2000 International Fire Code) Required Fire Flow= 2,250 gpm (Table B 105.1 of 2000 International Fire Code) Number of hydrants required= 2 (Table Cl05.l of 2000 International Fire Code) RESULTS 4,257 gpm available > 2,250 gpm required = OK 3 hydrants available > 2 hydrants required = OK