December 3, 2007
Mr. Josh Norton
City of College Station
P.O. Box 9960
College Station, Texas 77842
Re: Stormwater Detention
Aggieland Dental
JC Job No. C0019-001 -00
Dear Mr. Norton,
700 University Dr. East, Suite 11 OC
College Station, Texas 77840-1848
AUSTIN
HOUSTON
SAN ANTONIO
COLLEGE STATION
TEL 979 731 8000
FAX 979 846 2893
DALLAS
BRENHAM
ROSENBERG
THE WOODLANDS
The development of Block 1, Lot 3 of the Graham Comer Plaza plat does not require storm
water detention. When the land included in the Graham Comer Plaza subdivision was
platted, a portion was given to the City as part of a greenway dedication in exchange for a
waiver of the storm water detention requirements. The plat is attached for reference.
Sincerely,
Steve E. Duncan, P .E.
Vice President
SED/cls
cc: Dr. Spence
-''''"""' ---~~OF Tc..t ''t .: t:.;,~.·· .. •••• -1,s-•• ,,: .·· * ·.. ,, ~·: ·.• ~ "'•: ·.•'I. ,. •••••••••••••••••••••••••• 'I.
I. STEVE E. DUNCAN I. 'I.· ••••••••••••••••••••••••• oil ~ ••• 83252 ... ~ I~• ....<'> :15,, Ila O~·. (.ICENS'v.·~(()',,: '. ~s.s. ...... ~di: .: l\\\ it>NAL t-•-_--
'""'''''
Smart Engineering. Smart Solutions™ www.jonescarter.com
AGGIELAND DENTAL
CITY OF COLLEGE STATION
PK&JC JOB #C0019-001-00
FIRE FLOW CALCULATION
CALCULATED FLOW
Fire Flow at hydrant Q-122:
With 20-psi pressure at Static Hydrant Q-121:
Q, = 29.83cdD2 jP;
Q, = (29.83)(0.9)(2.5)2.JSO = 1,500 gpm
(
PS -20J0.54
Qf = Qr
Ps -Pr
Q =(1500)(104 -20 )
0
.
54
=6237 m I ' 104-98 ' gp
Where:
Q, = residual flow at the pitot pressure (gpm)
Q1 = Fire Flow (gpm)
j
cd = friction loss (usually 0.9 for smooth 2.5-in opening)
D = diameter of opening in inches (2.5 in most cases)
PP = pitot pressure (psig)
P, = residual pressure (psig)
Ps = static pressure (psig)
REQUIRED FLOW
Building Type = VB (Section 602 and 1505 of 2000 International Building Code)
Fire Area = 4,560 square feet (Section BI 04 of 2000 International Fire Code)
Required Fire Flow = 1,750gpm (Table BIOS .I of 2000 International Fire Code)
Number of hydrants required = I (Table Cl 05.1 of 2000 International Fire Code)
RESULTS
6,237 gpm available > 1,750 gpm required = OK
I hydrants avai lable = I hydrant required = OK