Loading...
HomeMy WebLinkAboutWater and Wastewater Report~ James· F. Turner Engineers, l. P: . J FT E -----------··--. · -------.. ··-----~ Consulting Engineers Heights Venture Architects 1111 North Loop West Suite 800 Houston, TX 77008 Attn: Mike Kravetz Re: Water and Wastewater Demand Report Navarro West Center Wellbourn & Navarro Road College Station, TX Dear Mike, May 28, 2008 Thts .repprt is intended to meet the City of College Stahon design requirements for the proposed site improvements, abiding by the B/CS Unified Design Guideline Manual 2005, International Plumbing Code 2006, and the International Fire Code 2006. Water Design Report -Normal Flow Space 'A' fixture unit count 26.5 fixture units Space 'B' estimated fixture unit count 159 fixture units total fixture unit count 185.5 fixture units Total Demand 88 gpm Total demand in gallons per minute is based on the conversion of the fixture units on the system with flush valves. One such conversion table, as prepared by the "Plumbing Systems & Design" for continuing educatioo is attached. Reference Table 4. Domestic water service will be connected to an existing 8" diameter water line stubbed up at the property line along Navarro Drive. Water Design Report -Fire Flow Based on the International Fire Code 2006 Appendix B & C Three hour rated fire wall is between Tenant Space 'A' and Tenant Space 'B'. Space 'A' Building Category Type llB Area 11 ,990 sf Fire Flow 2,250 gpm from Table 8105.1 Fire Flow Duration 2 hrs from Table C105.1 DALLAS -8340Meadow Road -Suite 160 --Dallas, Texas 75231 --214-750-2900 --Fax 214-750-2902