Loading...
HomeMy WebLinkAboutFire Flow LetterRB 111 McCLURE & BROWNE ENGINEERING/SURVEYING, INC. July 14, 2008 Erika Bridges Graduate Engineer City of College Station P.O. Box 9960 1008 Woodcreek Drive, Suite 103 •College Station, Texas 77845 (979) 693-3838 • Fax: (979) 693-2554 • Email: McClureBrowne@Verizon.net College Station, Texas 77842 Re.: Fire Flow Letter Adamson Lagoon Building MBESI No. 10140005 Dear Erika: This letter shall serve as our fire flow analysis of the proposed improvements for the above referenced project. This project consists of the replacement of the existing ±2,300 s.f. pool building with a new 3,958 s.f. pool building. The proposed building will be Type 1118 construction and will not be sprinklered. Based on Table 8105.1 of the International Fire Code, the minimum fire flow requirements for this building will be 1,500 g.p.m. Therefore, a new fire hydrant will be installed approximately 62' northeast of the proposed building to meet the fire flow requirements. If you have any questions or need any additional information, please do not hesitate to call. Sincerely, !!: J. Dale Browne, Jr, P.E • l .. FIRE-FLOW REQUIREMENTS FOR BUILDINGS TABLE B105.1 I I MINIMUM REQUIRED FIRE FLOW AND FLOW DURATION FOR BUILDINGS8 FIRE-FLOW CALCULATION AREA (square feet) FIRE FLOW FLOW Type IA and IBb Type llA and lllAb Type IV and V-Ab Type 118 and lllBb Type V-Bb (gallons per minute)< DURATION (hours) 0-22,700 0-12,700 0-8,200 0-5,900 0-3,600 1,500 22,701-30,200 12,701-17,000 8,201-10,900 5,901-7,900 3,601-4,800 1,750 30,201-38,700 17,001-21,800 10,901-12,900 7,901-9,800 4,801-6,200 2,000 2 38,701-48,300 21,801-24,200 12,901-17,400 9,801-12,600 6,201-7,700 2,250 48,301-59,000 24,201-33,200 17,401-21,300 12,601-15,400 7,701-9,400 2,500 59,001-70,900 33,201-39,700 21,301-25,500 15,401-18,400 9,401-11,300 2,750 70,901-83, 700 39,701-47,100 25,501-30,100 18,401-21,800 11,301-13,400 3,000 83,701-97,700 47,101-54,900 30,101-35,200 21,801-25,900 13,401-15,600 3,250 3 97,701-112,700 54,901-63,400 35,201-40,600 25,901-29,300 15,601-18,000 3,500 112,701-128,700 63,401-72,400 40,601-46,400 29,301-33,500 18,001-20,600 3,750 128,701-145,900 72,401-82,100 46,401-52,500 33,501-37,900 20,601-23,300 4,000 145,901-164,200 82,101-92,400 52,501-59,100 37,901-42,700 23,301-26,300 4,250 164,201-183,400 92,401-103,100 59,101-66,000 42,701-47,700 26,301-29 ,300 4,500 183,401-203,700 103,101-114,600 66,001-73,300 47,701-53,000 29,301-32,600 4,750 203,701-225,200 114,601-126,700 73,301-81,100 53,001-58,600 32,601-36,000 5,000 225,201-247,700 126,701-139,400 81,101-89,200 58,601-65,400 36,001-39,600 5,250 247,701-271,200 139,401-152,600 89,201-97 '700 65,401-70,600 39,601-43,400 5,500 271,201-295,900 152,601-166,500 97,701-106,500 70,601-77 ,000 43,401-47,400 5,750 295,901-Greater 166,50 I -Greater 106,501-115,800 77,001-83,700 47,401-51,500 6,000 4 --115,801-125,500 83, 701-90,600 51,501-55,700 6,250 --125,501-135,500 90,601-97,900 55,701-60,200 6,500 --135,501-145,800 97,901-106,800 60,201-64,800 6,750 --145,801-156,700 106,801-113,200 64,801-69,600 7,000 --156,701-167,900 113,201-121,300 69,601-74,600 7,250 --167,901-179,400 121,301-129,600 74,601-79,800 7,500 --179,401-191,400 129,601-138,300 79,801-85,100 7,750 --191,401-Greater 138,301-Greater 85,101-Greater 8,000 For SI: 1 square foot= 0.0929 m2, I gallon per minute= 3.785 Um, I pound per square inch= 6.895 kPa. I a. The minimum required fire flow shall be permitted to be reduced by 25 percent for Group R. b. Types of construction are based on the International Building Code. c. Measured at 20 psi. 372 2003 INTERNATIONAL FIRE CODE®