Spring Creek Townhomes, Phases 2 & 3
Water System Report
General Information
Location: Spring Creek Townhomes, Phases 2 & 3 are located in southern College Station
near the intersection of Decatur Drive and Arrington Road. 111ey are immediately
adjacent to Spring Creek Townhomes, Phase 1 and Spring Creek Gardens, Phase 1.
The subdivision has 71 lots along Heath Drive and Dawn Lynn Drive.
Land Use: Single Family Residential
Design Criteria
Primary Water Supply: Existing 12" line on Decatur Drive
Domestic Demand:
Avg. Pop Density: 2.67 people per lot
Average Flow:
Peaking Factor:
100 gpd/cap or 267 gpd per lot = 0.18 gpm per lot
4
Peak Flow:
Design Flow:
Fire Demand:
0.74 gpm per lot
1.50 gpm per lot
Fire Flow:
Pipe:
1000 gpm at most hydraulically remote point
PVC DR-14 C909
Roughness Coeff: 150 (Hazen Williams)
Hydraulic Software: Haestad Methods WaterCAD v.6.0
Existing City System Pressure Tests
Flow Hydrant#: R-048 (Decatur@ Alexandria)
Flowrate: 1500 gpm
Static Hydrant#: R-051 (Spring Garden)
Static Pressure: 104 psi (240 ft water)
Residual Pressure: 102 psi (236 ft water)
Applicable Exhibits: Exhibit A -College Station Utilities Flow Test Report
Water System Summary
Criteria Required As
Designed
Min. Pressure -fire (psi) 20 102
Max. Velo city (fps) 12 7.01
Max. Length of 6 "pipe (ft) 1500 1059 (connected to ~ 8 "011 both
Max Length of 6 "pipe (ft) 800 NA (not connected on both ends
Max. Length of 3 "pipe (ft) 500 MA
Applicable Exhibits: Exhibit B -Water System Schematic
Exhibit C -Summary of Results -Fire Flow
Water System Conclusion
Location
FH-2
W-1-1
The proposed water system for Spring Creek Townhomes, Phases 2 & 3 meets or
exceeds all of the design criteria fo r the City of Coll ege Station.
JJ /ll!/ZUU4 Jt>:ZZ l'l\A l11 t1 tt>4 .>4 J.l
II -1( College Station Utilities ~ Reliable, Affordable, Community Owm.·d
1601 GRAHAM ROAD
COLLEGE STATION TEXAS 77845
Date: 18 NOVEMBER 2004
Number pages including cover sheet -1
Fax to: 764-7759
Attention: JOE SCHULTZ
Company: TEXCON
From: Butch Willis Water Wastewater Division
Phone: 979-764-3435 Fax: 979-764-3452
FLOW TEST REPORT
Nozzle size: 2.5 inch
Location: ALEXANDRIA AT DECATUR
Flow hydrant number: R-048
Pi tot reading: 80
(GPM): 1500
Static hydrant number: R-046
Static PSI: 104 1
Residual PSI: 102 1
Exhibit A
' / //
/ /
/ // /
/ / / ////~ ',
/ / ' '
ii // I;
j ii i ;,: .:; 1! : / J
/ /
/ // / "
/ / / / " ,,· / / / / I I / I I I / I ,., ,., /
; /,,. I/ ,.,/
I :' I I
I / 1
1 I , I : i !
;
i/
/ //
i i :
i I I I I I / I I , ,
/ //
! I ! ! I I
I :'
f !
i
I /
// :
// , ;
EXHIBIT
B
Wr 1-j3
SPRING CREEK TOWNHOMES
PHASES 2 & 3
WATER SYSTEM SCHEMATIC
-I
__ _I
2
.. t--·---Q) > ·c
0
£ -+-J
0
Q) :r:
SCT2-1
* CIVll.lkva.OPMENI; Lt,,_* Cf'l,[~(AING,Nl:r ........ o~··.rr•
2033 Har, .. y t·.lttl•ell Pr11< 1 Seiulll
Coll.•9·· $1.11,,,.1 1. · '" 7i~tt0
P O Bo • 11c.2~l I.nu •. ., .. ':ii '''''" 1._., •!> i'7.~.!.:'
,.:;q, ifil.. 7 i .11 r .1, I .. '~'.'! "I"~: :'i'•I
TESTED FH
-----1"'1 SCT3-1
~ -1
"" I
L
[''
I~
I ~-I ""
SCALE: NOT TO SCALE
Label
W-1 -1
W-1-2
W-1-3
W-2-1
W-2-2
W-2-3
Exhibit C
Spring Creek Townhomes, Phases 2 & 3
Water System Analysis
Pipe Summary -Fire Flow Conditions
--------~-Length Diameter Material Hazen-Discharge Velocity
(ft) (in) Williams C (gpm-) --(ft/s)
337 8 PVC 150 -1,097.50 7.01
354 6 PVC 150 -216.90 2.46
706 6 PVC 150 194.40 2.21
309 8 PVC 150 -856.60 5.47
235 8 PVC 150 173.40 1.11
135 8 PVC 150 -6.00 0.04
Maximum Velocity = 7.01
Junction Summary -Fire Flow Conditions
Label Elevation Demand Hydraulic Pressure Grade
(ft) (gpm) (ft) (psi)
FH 1 275 22.5 517.65 104.98
FH 2 280.5 1,030.0 515.59 101 .71
SCT2-1 279.5 15.0 515.71 102.20
SCT2-2 279 6.0 515.71 102.41
SCT3-1 286 9.0 524.45 103.16
SCT3-2 281 24 .0 518.84 102.90
Lowest Pressure = 101.71