Attached is the Fire Hydrant Flow Test Report for 12 at Rock Prairie.
If you have any questions,please do not hesitate to call.
Sincerely,
Schultz Engineering,LLC.
/___ C____
Ricky ores
P.O. Box 11995 • College Station,Texas 77842
schultzengineeringllc.com
Schultz Engineering, LLC
FIRM #12327
WATER SYSTEM FIRE HYDRANT FLOW TEST REPORT
Date: 12-16-2014
Water System Owner: Wellborn SUD
Development Project: 12 at Rock Prairie
Flow Test Location: SW corner of Summerway Drive and Papa Bear Drive
Nozzle Size (inch): 2.5 Discharge Coeff(c) = 0.90
Pitot Reading (psi): 50 Flowrate Forula: Q=29.84cd2p1/2
Flowrate (gpm): 1187 c = discharge coeff.
d = orifice size
P = pitot pressure (psi)
Pressure Gauge Location: NW corner of Summerway Drive and Towers Parkway
Static Pressure (psi): 68
Residual Pressure (psi): 50
Compute Discharge at 20 psi Residential Pressure: OR = 2015
Discharge Formula: QR = QF x (hr0.54/hf0.54)
Note: The Flow Test and Report were prepared in accordance with NFPA 291
Report Prepared By: Deven Doyen of Xq
Ricky Flores • •••"•••s
Others Present: Clenden Adams - Wellborn SUD ark: •'*Q
ç
P�4 ll`4
FOR OFFICE
U$ EO ILY
CASE NO.: ` if \a/
DATE SUBM ED:
(kr'
CITY OF COLLEGE STATION TIME: I
Home ofTexasAd`MUniversity' STAFF:
PLANNING & DEVELOPMENT SERVICES
TRANSMITTAL LETTER
Please check one of the options below to clearly define the purpose of your submittal.
❑ New Project Submittal
Incomplete Project Submittal-documents needed to complete an application. Case No.:
❑x Existing Project Submittal. Case No.: 14-00900181
Project Name 12 at Rock Prairie
Contact Name JOE SCHULTZ, P.E. Phone Number 979-764-3900
We are transmitting the following for Planning & Development Services to review and comment(check all that apply):
❑ Comprehensive Plan Amendment ❑ Non-Residential Architectural Standards
❑ Rezoning Application ❑ Irrigation Plan
❑ Conditional Use Permit ❑ Variance Request
Preliminary Plan Development Permit
❑ Final Plat ❑ Development Exaction Appeal
] Development Plat FEMA CLOMA/CLOMR/LOMA/LOMR
❑ Site Plan ❑ Grading Plan
❑ Special District Site Plan x❑ Other- Please specify below
❑ Special District Building/Sign Fire Hydrant Flow Test Report
❑ Landscape Plan
INFRASTRUCTURE AND ENGINEERING DOCUMENTS
All infrastructure documents must be submitted as a complete set.
The following are included in the complete set:
❑ Comprehensive Plan Amendment ❑ Waterline Construction Documents
❑ TxDOT Driveway Permit ❑ Sewerline Construction Documents
❑ TxDOT Utility Permit ❑ Street Construction Documents
❑ Drainage Letter or Report ❑ Easement Application
❑ Fire Flow Analysis ❑ Other- Please specify
Special Instructions:
10/10 Print Form,;.'