HomeMy WebLinkAboutWater Report WINN PROFESSIONAL ENGINEERS AND CONSTRUCTORS,LIC Texas Registered Firm No. F-7846 WATER SYSTEM FIRE HYDRANT FLOW TEST REPORT Date: 2/11/2015 Water System Owner: Wellborn SUD Development Project: Jeremy Boyd Service Flow Test Location: Fire Hydrant near 12318 N. Dowling Rd.,College Station,TX Nozzle size (in.): 2.5 Discharge Coeff: (c) =0.90 Pitot Reading(psi): 60 Flowrate Formula: QF= 29.84cd2p1/2 c=discharge coeff. Flowrate(gpm): 1,300 (from chart) d =orifice size (in.) p= pitot pressure (psi) Pressure Gauge Location: Hose bib on nearby house,4655 Rock Prairie Road, College Station Static Pressure (psi): 71-72 Residual Pressure(psi): 63 Computed Discharge at 20 psi Residual Pressure(gpm): QR= 1,994 Discharge Formula: QR=QF(hr0.54/hf.54) Note: The flow test and report were prepared in accordance with NFPA 291. Testing Witnessed and Recorded by: William R. Dierksen, P.E. Report Prepared by: Walter T.Winn,Jr., P.E. Others Present: Clendon Adams(Wellborn SUD) Jonathan Provazek(Wellborn SUD) WINN PROFESSIONAL ENGINEERS Y a 4 r b : r s r AND CONSTRUCTORS, LLC February 16, 2015 via Email and US Mail Mr. Stephen Cast Wellborn Special Utility District P.O. Box 250 Wellborn, Texas 77881 RE: Jeremy Boyd Fire Flow Test Dear Stephen: Our Mr. Will Dierksen, P.E. witnessed a fire hydrant flow test conducted by Wellborn Special Utility District personnel, Clendon Adams and Jonathan Provazek. The results of the testing are shown in the attached report prepared in accordance with NFPA 291. Our calculations indicate that approximately 1,994 gpm should be available from the hydrant when operated with a residual pressure of 20 psi. We appreciate the opportunity to provide this information. Please do not hesitate to call if you have any questions or comments. Sincerely yours, Winn Professional Engineers & Constructors, LLC Texas Registered Firm No. F-7846 • ,ri . rr ,rd�r,nr JR. • 3 ,l7J Walter T. Wi , Jr., P.E. " "" • Principal ., WTW/pkw II�A� Attachmentl0(LC— • • Q2 WE�Jererny.Boyd Service�Fire Flow Test Ltr 021615.doc 505 Padon • P 0. Box 2727 • Longview,Texas 75606 t. 903-553-0500 f, 903-553-0555 • wwwwinnpec.com