Loading...
HomeMy WebLinkAboutStaff Comments 3Q -co 9C. ENGINEERING COMMENTS NO. 2 1. Cl — Show and label all easements on or adjacent to the site (include volume & page number). Label the existing 15-ft PUE adjacent to the property with volume and page number. )� 2. (Alan) Cl — Label the meter sizes, fire line, and isolation valve. Based on the size of the meter, a meter vault needs to be provided. Water meter vault appears to be too close to building. C1/C6 — Per Water Services, a 15-ft separation is required between the building and the 0a water & sanitary sewer lines. The only exception to this is the sanitary sewer line adjacent to the southern property line, which may remain in its existing location. V-1 Additional pavement repair will likely be needed. • (Alan) Sewer on Cherry private? 0)416( \4\4. C2/05 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is '\0\/3 set back away from the back of curb and sections that are sidewalk only without the tree. The detail without the tree should still include the underdrain pipe and \\A' moisture barrier per the similar Site Design Standards detail. 5. (Izzy) C3 — It seems like additional pavement removal & replacement will be needed for areas where water and sanitary sewer are being relocated. 6. (Izzy) C3— It appears that the proposed waterline on the north side will require part of the street to be removed in order to be installed in that location. • (Izzy) Additional pavement will need to be removed for trench to install water along Second St.? t *� ... rt �o�t o r� 7n (ervlov� ---r est -#ke, til re;7; eri-hre.. 7. C3/C6 — Please provide additional details for the removal of the sanitary sewer line & C 4 repair of the manhole. (i.e. label linear footage of line to be removed; PVC, rubber boot,-t`r"e'l-5 mcku ntlgi etc. needs to be completely removed from or cut out of the manhole; what type ofik. concrete should fill the void in the manhole; specify how the hole should be filled and concrete smoothed inside and outside the mahole). a-r.&'4 8. C8 — Provide more details for the detention pond including cross sections. It is unclear ceplact how water will actually enter the detention pond. Regarding Notes #1 & 2 pertaining c k1 takwt- to the detention pond, the structural drawings and stormwater piping into the i vxtedecl . pond are details that need to be included in the civil plan set. 9. (Ben)Water Report Since the parking garage will be a different building material type from the remainder of the building and typically unsprinkled, Appendix B of the n f International Fire Code requires that a combination fire flow be calculated. -w\,�," ( 00. (Alan) Water Report — The Fire Marshal requires that the actual fire flow test produce �lV the necessary fire flow per the IFC. This fire flow cannot be based on a theoretical o,, calculation of potential flowrate. -t t4cy 11. Drainage Report — Please include a detail of the pond in the report and indicate how 1 water will collected and routed to the detention pond. Details showing how the stormwater will be routed to the pond need to be provided in the drainage report and civil construction plans, not just the building plans. X41- )W19 12. Drainage Report — Provide an analysis of the ponding in the parking area. Are any X" ) grate inlets/drains proposed in the parking area? \ ,p� 13. FYI...Additional Development Permit Fee in the amount of 1% of the total public 6• infrastructure cost will be required. Based on the Engineer's Cost Estimate, the DP 44, `, Fee balance is $1,117.97. c 14. (Alan) 010 — Pleasequovidbepisesifig such that closures are limited to no more than two streets at any time. �Wc VAA, . IS f�Sca Te_. fl ?k),011-C, tWO(k-5 l5 �h I) �ur�.�ll'�`� -I'LLeekir)' �cL (/� i-h v\aCoves .m-fr5vv�,�,11�1 � o vin r � • 15. C10 — The intersection of Cherry/Boyett will need to be partially or completely closed at some point to install the storm sewer. Please provide traffic control for this scenario. 16. C10 — Note #9 references "appropriate signage" is going to be up at night. Should the appropriate signage be specified? Reviewed by: Erika Bridges Date: 3/9/15 f-Thie, Gamed -iv '' CA,,ern' $- Ari-s" ENGINEERING COMMENTS NO. 1 'V! rovide an erosion Vontrol plan, traffic 5ontrol plan, and an 01. Cost Estimate — It appears that public storm, sidewalk, and street repair are missing from the estimate. Tp 'Q Cl — Show and label all easements on or adjacent to the site (include volume & page vnumber). Cl — Add a note with the building size, material, whether or not it's sprinkled, and the required fire flow. . 55.. Cl — Label the meter sizes, fire line, and isolation valve. Based on the size of the G6) meter, a meter vault needs to be provided. ,�-(-� VJ - - op Upv_ID 19C1/C6 — Per Water Services, a 15-ft separation is required between the building ane _a� ��� water & sanitary sewer lines. The only exception to this is the sanitary sewer line adjacent to the southern property line, which may remain in its existing location. StA, ainetiNest Additional pavement repair will likely be needed. 3ewej- Dv1 ,VGhtcy 'hi' �covcif C1/ 06 — Per Electrical, additional PUE is needed for the proposed transformer. Please show and label. FYI...A blanket easement or specific PUE must be dedicated prior to site plan approval. c 4W-- Ape. T-Df. Ge_CtI,i CA,( ge R)-. C1/C6 — It looks like the irrigation line dead-ends on the north side of the property. Is 3that the correct or is does it have another connection? 9. C2/C5 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is set b ck away frpm the back of curb and sections that are sidewalk only w'thout the y� tree. ' u`ypD�+,1� phi -Iy,Zde. s%1.ould. inch td,2 n pi.x,vv.wstu r e W• —Why doesWe "Tree GYate CTef�ll't specify that the 4-inch drain line should be within ee bedding areas only? . C2/C5 — Include the street tree detail showing the cross-section of the trees/sidewalk arallel to the street (shown on page 49 of the Site Design Standards). 1 . CC2 — The Site Design Standards allow for an engineered alternative to structural soil. Nfr The specified Bedding Mix alternative and structural design should "bridge the bedding O material by tying the sidewalk into the curb and back to undisturbed soil & provide enough structural support to handle vehicles parking & driving on the sidewalk." Please provide a letter certifying that these objectives are achieved with the proposed I21, I`r ' alternative design. �� 3 — It seems like additional pavement removal & replacement will be needed for areas Wt.Lerco b? here water and sanitarysewer are e C3 — The limits of the sanitary sr line removalrelocatd. are unclear. Are you proposing grout illing a portion of the sewer between manholes/cleanouts and removing a portion? Ct3 — How do you propose detouring pedestrian traffic while the sidewalks are closed °c during construction? 1`§. 03 — Include a note regarding the contractor coordinating with Water Services, CSU, and Atmos well ahead of disruption of service and/or removal of utility lines. 17 C — It appears that the proposed waterline on the north side will require part of the 10reet to be removed in order to be installed in that location. iv '? 6 It is difficult to tell the difference between proposed lines & lines that� arb proposed be removed. Please distinguish. 1 . — Clearly label private irrigation, storm, and sanitary sewer lines. 0 6 — Water and sanitary sewer lines need to be at least 3-ft horizontally from other utilities (storm, electrical, gas, etc.) . C7 — The scale of the plan drawings are too small and difficult to read. It is unclear hich lines the labels correspond to. This will need to be reviewed again once the scale is more legible. . 7 —There should be at least a 1-ft vertical separation between storm and water lines. C8 — Specify how much riprap should be added at the storm outfall? PI w'5 Oj P CohM✓v-2rN+S C8 — Please label all flowlines. 8 — Provide more details for the detention pond including cross sections. It is unclear 9w water will actually enter the detention pond. (.3Lbk,J r9) — p of don the — It It needsappears to bethat clearlythetolabeledJB101 thatis everythingabove upstreamexistingground of bas JB102 will be privateprofile. . C9 — Please add a note regarding the ownership and maintenance of the private storm/detention. Q 29. Water Report — Since the parking garage will be a different building material type from �Jlik the remainder of the building and typically unsprinkled, Appendix B of the International Fire Code requires that a combination fire flow be calculated. 30. Water Report — Provide an exhibit showing the existing water system surrounding the property including fire hydrants that will serve the site. 31. Water Report — The report should indicate how many fire hydrants are needed to serve the site and the required spacing of them. 32. Water Report — Provide velocity and pressure information for the surrounding water system when subject to multiple hydrants being flown simultaneously and peak domestic demands. 0 Water Report — The Fire Marshal requires that the actual fire flow test produce the necessary fire flow per the IFC. This fire flow cannot be based on a theoretical calculation of potential flowrate. b -1145 siA-fei(As„,„� yok- 1-1). it,,, ,r FF ? 334 Drainage Report — Please include a detail of the pond in the report and indicate how water will collected and routed to the detention pond. 3 1 ill w. °.ir1J� Aci,n SP\. IZ. Drainage Report— Provide an analysis of the ponding in the parking area. Nio ecvsiiiii, ii,Drainage Report — What is the 100-year clogged WSE? There should be 6-in`bf freeboard between the clogged WSE and the top of the outfall. WO FYI...Additional Development Permit Fee in the amount of 1% of the total public infrastructure cost will be required. >SA 6v-\, CE, T7-f . .1(..•-iic-e. tS 11, 1 I-i M7 Reviewed by: Erika Bridges Date: 1/30/15 Trafi C 03V041 — Th e w,l I inQ,ec111) - &_ -rid \ cic�(Ace, G fie. ciAerl 1601eit1 rte-c4iv,,, c,+ p,.` . W wi l I TC, loot — iissthiALut -P(A-6Vx5 ? „ s , — Ntb*e---#01 — kAlt\m-- It 'urfilfn''rc 5r°± °6vn .11,, Im_ uf 0- vvilki."7. O os e.S ar\ y ' / Clerk,) /fecir‘d ca- * C3 I �- p�vtd� - a_ io►\0-A c1 -} 05 -I'kt- 0-AA flEteetrif of -41/‘-e- ft-*`k sovo . se sez liar2, r of w‘a,r,\„ove,• C `e\( Lf ' ) coil. et, , ' •.! _r A £ �_ A it 1 .; LA � � i 1 G,7 111. N - 12QacLrc 4 A9 KID122 Fer— +/u +p . I2-dle.-i-a4i eonci, A-Ke siyva,t-ra * C) - Lel 41Ae -Piet line, d� i•nolVtfic ww-e. BaZed ovx *te5Ze C -1-ksz weer; rv\e-{ervtl-1- h.e s -t) pr 1dad - - Waw e.ef):Nr-t- -`lOrlUv 0 t' 144k3 c +w,w,hctl �-. . K2eJCLtla FFA /fr. 6 acI- ai '_A. -11nDd- 101 is MNE. exi5b 3 ofm,(18 > - . ��- \ -do\��s >�. ► Fav ck `✓�- \,-how 6 Altu, w46( irev , W-er ii`S'\ bkci i-H/ C5- ona-1 t aftui (411 r e '/ S vl'v&l a-14,4Aiti; 11,ti2. 'removal O r f \-P rA are g- -r` O��f �e r okS a►� b,P->lovN -.11". p1t,ttl&da± & , hp Le_, -Fire' -2 Cif tt.. .i 1it,6vt m.i of ke- fitt")_ C� F �-Ie. �w ►.�s�i i Y22. ett Lmixisved , does -Er oc an do v ) aci7 WC-5 - Incik La* -eke cov\--1-aolDr moS± croorck4A--i‹.- kit5 r w64-or 5e vi cis , Ca/t Amt n f -1-a diW/L.9tir\ii r'etmou;/l� C(o -' } is c c& 14 -j a --Jel I -1-1AE. ckkce. k e rropz. d re rvveved 4( C, - C l 1 / 1a -€A 1 iTt2h'O►r 3-ewer--- CG" — l�; CCo - We (55 Y .e.QA -\1:60- off- 1- .5f 3` -rirmi crltitP� ( v✓N of,ec; 6.5, 'I h� •9v5cd WL bin v o(k - Si d.lZ._ )_: f c . �c ,►' -- i -iv I L eve.a • Ilett ` Cocl.e- of ply c ,wi Gzre - l 4 alit Ott cea .` -i- Clan uthad- &A t --1',Nz rt/Ixts a,re o,�, A +D. W [1 v'l& .-1-144' rem V\ - .e, cute vtiw�,n 1- +021-e, ezcre 4D ? D'ity io ( 149.e.15 orx. *e. we 1- II2. rn & wn,. 24. C8 — Please label all flowlines. 25. C8 — Provide more details for the detention pond including cross sections. It is unclear how water will actually enter the detention pond. 26. C9 — It appears that the top of JB101 is above existing ground based on the profile. 27. C9 — It needs to be clearly labeled that everything upstream of JB102 will be private. 28. C9 — Please add a note regarding the ownership and maintenance of the private storm/detention. 29. Water Report — Since the parking garage will be a different building material type from the remainder of the building and typically unsprinkled, Appendix B of the International Fire Code requires that a combination fire flow be calculated. 30. Water Report — Provide an exhibit showing the existing water system surrounding the property including fire hydrants that will serve the site. 31. Water Report — The report should indicate how many fire hydrants are needed to serve the site and the required spacing of them. 32. Water Report — Provide velocity and pressure information for the surrounding water system when subject to multiple hydrants being flown simultaneously and peak domestic demands. 33. Water Report — The Fire Marshal requires that the actual fire flow test produce the necessary fire flow per the IFC. This fire flow cannot be based on a theoretical calculation of potential flowrate. 34. Drainage Report — Please include a detail of the pond in the report and indicate how water will collected and routed to the detention pond. 35. Drainage Report— Provide an analysis of the ponding in the parking area. 36. Drainage Report — What is the 100-year clogged WSE? There should be 6-in of freeboard between the clogged WSE and the top of the outfall. 33 FYI...Additional Development Permit Fee in the amount of 1% of the total public infrastructure cost will be required. 7&zed on, CZ, iS I, 111.63 Reviewed by: Erika Bridges Date: 1/30/15 Tc Ei c. an-1/4 1 - Acre, ww I &, -rut 1 ctcz ., 6-F-4-1,,e etAarliEeict X1 2- vr\ C�-�- �o�v+� � /-' . WIC wilI C bot_ lea_ ( -1/ -7 �� � - 'Na -FLUS Gt - Uov\m- I' a r 30`A 06`f — o os n Drt / Okeikev) cd- - =► ted 7_1--- 00711 -�- yvie +0 re,Vi ch) --HA,t S ouVut Si�(lCx V� Glee No 10 n S� (111 iff1111111 CITY OF COLLEGE STATION ',: Home of Texas AuM University` MEMORANDUM v DATE: January 30, 2015 TO: Keller Webster/Gary Daily, KWA Construction, via; gdailyAkwaconstruction.com FROM: Jessica Bullock, Staff Planner SUBJECT: SECOND STREET APTS (NG) Staff reviewed the above-mentioned Northgate Building Review Application as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised set of elevation drawings Please note that this application will expire in 90 days from the date of this memo, if the applicant has not provided written response comments and revised documents to the Administrator that seek to address the staff review comments contained herein. If there are comments that you are not addressing with the revised elevations, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments PC: CS Second Street Apartments II, LLC, via; therbelin@newsschooladv.com .� Deven Doyen, Schultz Engineering, LLC, via; devenOschultzengineeringllc.com Tom Ekenberg, via USPS; 16800 Westgrove Suite 100, Addison TX, 75001 P&DS Project No. 15-00900003 Planning er Development Services P.O.BOX 9960 • 1101 TEXAS AVENUE •COLLEGE STI'ION •TEXAS •77842 TEL.979.764.3470•FAX. 979.764.3496 0 STAFF REVIEW COMMENTS NO. 1 Second Street Apts (NG) —Review 15-00900003 PLANNING 1. Please label the color of the roof on the plans. This color must be from the approved colors list. Please also label brick color. Colors normally found in manufactured brick are permitted. 2. The facade facing the Traditions is not within 15 feet. It will need to meet material requirements of min 25% brick on the first two stories or 28 feet, no more than 75% of the hard board/cement fiber board, and 2 different design elements from the Northgate options list every 40 feet. 3. Please include the windows, doors, and openings in the Mat'l Sq. Footage tables. Please also provide percentages of the materials. 4. Please identify material and color for the roll-up doors by the compactor. 5. Please identify the elements selected to meet the architectural relief requirement. I count 7 25-foot sections on Cherry, Second, and Boyett. Pilasters and awnings are options to meet the requirement but I am not sure what others you propose with this design. Reviewed by: Jessica Bullock Date: 1/26/15 11110, (44.11 CITY OF COLLEGE STATION ea c4,,/<: Home of Texas A&M University' ...,, K. ;mom- MEMORANDUM DATE: January 7, 2015 TO: Keller Webster/Gary Daily, KWA Construction, via; qdaily@kwaconstruction.com FROM: Jessica Bullock, Staff Planner SUBJECT: SECOND STREET APTS (NG) Thank you for the submittal of your Northgate Building Review application. I have been assigned to review this project and it is anticipated that the review will be completed and any staff comments returned to you on or before Wednesday, January 21, 2015. If you have questions in the meantime, please feel free to contact me. PC: CS Second Street Apartments II, LLC, via; therbelin@newsschooladv.com Deven Doyen, Schultz Engineering, LLC, via; deven a(�schultzengineeringllc.co Tom Ekenberg, via USPS; 16800 Westgrove Suite 100, Addison TX, 75001 ,/ P&DS Project No. 15-00900003 Planning d''Development Services P.O.BOX 9960 • 1101 TEXAS AVENUE •COLLEGE SThTION •TEXAS •77842 TMT Q?{) 7!A d<71) .MAV cr7o 77..4 2(.{1f STAFF REVIEW COMMENTS NO. 1 Second Street Apts (NG) —Review 15-00900003 PLANNING /1. Please label the color of the roof on the plans. This color must be from the approved colors list. Please also label brick color. Colors normally found in manufactured brick are permitted. NTS Arch. Response: Browse Brown#6012 has been chosen for the roof color. Noted in Legend notes on elevation sheets A417-A4.20. . 2. The facade facing the jaditions is not within 15 feet. It will need to meet material quirements c ofeet, o m µ� `ncb and board/ceofmentmin fiber 25%boabnrd, andnthe 2 differentfirsttwo designstories elementsor28fromntheore Northgatethan75%optionsofthe Gt list every 40 feet. NTS Arch. Response: Elements have been added per request. Material brick percentage has been modified to match the min. 25% requirement. Ref. Sheet A4.18. ✓3. Please include the windows, doors, and openings in the Mat'l Sq. Footage tables. Please also provide percentages of the materials. NTS Arch. Response: Mat'l sq. footage table has been updated per request. tyt. Please identify material and color for the roll-up doors by the compactor. NTS Arch. Response: Aesthetic White color#7035 has been chosen for the Metal Roll-up door. 5. Please identify the elements selected to meet the architectural relief requirement. I count 7 25-foot sections on Cherry, Second, and Boyett. Pilasters and awnings are options to meet the requirent but I am not sure what others you propose with this design. NTS Arch. Response:4itherry St. Architectural elements include - Brick column projections, Sloped roofs, Box awnings with metal supports, Brick banding (String Courses), Recessed Entries. ,'econd St. elements include — Brick column projections, Sloped roofs, Brick banding (String /douses), Recessed garage entry with Wrought iron gate. ./Boyett St. elements include — Brick column projectsions, Sloped roofs, Large Box awning with metal supports over garage entry, Brick banding (String Courses), Recessed entry. Note: All comments have been responded to per request. Architectural sheets have been updated per comments/request and forwarded to the client for re-submission. Please let me know if there are any further questions/comments. Thanks!! Darryl Dabbs, Project Architect. NTS Architects & Planners IC( STAFF REVIEW COMMENTS NO. 1 Project: Second Street Apartments (SP) 15-00900002 tJW_ LUN, IT 1. Please include unit mix on the site plan. The unit mix has been added to the site plan. 2. Please add general note to show the required floor -to -area ratio of 1:1 is met by the proposed square footage. This calculation does not include easements, setbacks, and sidewalk. General Note 4 has been added to show floor to area ratio is met. 3. 1 have looked at the administrative adjustment briefly to see the proposal. Please formerly submit the application for full review. The administrative adjustment is attached to this response to comments. 4. Parkland dedication in the amount of $209,408 ($1,636 x 128 Units) will be due prior to issuance building permits. Noted. 5. Please label existing and proposed street lights and include label in the legend. Existing and proposed street lights have been labeled. 6. Please revise site plan comment 14 to say it is a compactor and indicate gate clearance. Note 14 has been revised. 7. Please revise bicycle count. More bike racks should be provided. Area between the building fagade and sidewalk to be used to install bicycle racks is a potential location. Additional bicycle racks have been added to compensate for the 18 space reduction requested by administrative adjustment. 8. Please add color to detail for benches. Black or bronze (Brown) powder coating color are permitted. Bench color has been added to detail. 9. Please change building orientation on sheet 2 to match sheet 1. Building orientation on sheet 2 has been revised. 10. The throat depth for the gated entry requires a minimum 100-foot from Boyett. The current design does not meet that. Refer to the attached letter regarding throat depth. 11. Brick pavers on Cherry should follow the running bond pattern with the long side parallel to Cherry. Noted, detail shows running bond pattern with long side paralleling roadways. The hatching has been revised to reflect the correct pattern. 12. Where tree grates are not along the back of curb, please place benches on the same side. Benches have been relocated to match tree grate location on sidewalk. • All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. Reviewed by: Jessica Bullock Date: 1/26/15 ENGINEERING COMMENTS NO. 1 25. Provide an erosion control plan, traffic control plan, and an NOI. Erosion control plan has been added to drainage plan. Traffic control plan have been added. This site is smaller than 5 acres of disturbance and does not require an NOL The small construction site notice will be submitted prior to release of construction plans. 26. Cost Estimate — It appears that public storm, sidewalk, and street repair are missing from the estimate. A revised engineer's estimate is attached. 27. C1 — Show and label all easements on or adjacent to the site (include volume & page number). All easements have been labeled with information available. 28. C1 — Add a note with the building size, material, whether or not it's sprinkled, and the required fire flow. Site specific note 3 gives information above. 29. C1 — Label the meter sizes, fire line, and isolation valve. Based on the size of the meter, a meter vault needs to be provided. Inset has been added to sheet C1. 30. C1/C6 — Per Water Services, a 15-ft separation is required between the building and the water & sanitary sewer lines. The only exception to this is the sanitary sewer line adjacent to the southern property line, which may remain in its existing location. Additional pavement repair will likely be needed. Water lines have been relocated to 15' separation from the building. The sewer line on Cherry Street will become a private service. Additional pavement will be removed and repaired on Boyett Street. The curb and gutter will be removed on Second Street. 31. C1/C6 — Per Electrical, additional PUE is needed for the proposed transformer. Please show and label. FYI ... A blanket easement or specific PUE must be dedicated prior to site plan approval. A PUE has been added and an easement application will be submitted separately. An easement application for the blanket easement is being prepared and will be submitted separately. 32. C1/C6 — It looks like the irrigation line dead -ends on the north side of the property. Is that the correct or is does it have another connection? The irrigation system will extend to property line to provide irrigation to proposed landscaping. 33. C2/C5 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is set back away from the back of curb and sections that are sidewalk only without the tree. Additional details have been added. 34. C2 — Why does the "Tree Grate Detail' specify that the 4-inch drain line should be within tree bedding areas only? The Tree Grate Detail has been revised to remove the wording specifying the 4" drain only be within tree bedding areas. 35. C2/C5 — Include the street tree detail showing the cross-section of the trees/sidewalk parallel to the street (shown on page 49 of the Site Design Standards). Street tree detail from site design standards have been added. 36. C2 — The Site Design Standards allow for an engineered alternative to structural soil. The specified Bedding Mix alternative and structural design should "bridge the bedding material by tying the sidewalk into the curb and back to undisturbed soil & provide enough structural support to handle vehicles parking & driving on the sidewalk." Please provide a letter certifying that these objectives are achieved with the proposed alternative design. A letter certifying the alternate sidewalk design is attached. 37. C3 — It seems like additional pavement removal & replacement will be needed for areas where water and sanitary sewer are being relocated. Pavement removal is shown on the Pavement and Demolition Plans. No additional pavement removal and replacement is proposed. 38, C3 — The limits of the sanitary sewer line removal are unclear. Are you proposing grout filling a portion of the sewer between manholes/cleanouts and removing a portion? The sewer line through the lot and down Cherry will either be removed or abandoned and grouted in place. The contractor is requesting the flexibility to determine between the two approved methods shown on the demolition plan. A portion of the 8" sewer line will be removed. 39. C3 — How do you propose detouring pedestrian traffic while the sidewalks are closed during construction? The pedestrian traffic will be detoured to College Main. Refer to the traffic control plan. 40, C3 — Include a note regarding the contractor coordinating with Water Services, CSU, and Atmos well ahead of disruption of service and/or removal of utility lines. Note #9 has been added to sheet C3. 41. C3 — It appears that the proposed waterline on the north side will require part of the street to be removed in order to be installed in that location. We are proposing removal of the curb and gutter along Second Street for the installation of the proposed waterline. No additional pavement removal is proposed. 42. C6 — It is difficult to tell the difference between proposed lines & lines that are proposed to be removed. Please distinguish. Lines to be removed have been taken off sheet C6 and are shown on sheet C3 Demolition Plan. 43. C6 — Clearly label private. irrigation, storm, and sanitary sewer lines. Additional labels have been added to sheet C6. 44. C6 — Water and sanitary sewer lines need to be at least 3-ft horizontally from other utilities (storm, electrical, gas, etc.). Noted, utilities have been adjusted to provide horizontal clearances. 45. C7 — The scale of the plan drawings are too small and difficult to read. It is unclear which lines the labels correspond to. This will need to be reviewed again once the scale is more legible. The plan view scale has been increased, to provide more clarification. 46. C7 — There should be at least a 1-ft vertical separation between storm and water lines. The water line has been revised to provide I'clearance. 47. C8 — Specify how much riprap should be added at the storm outfall? No rock riprap will be provided. The detail has been revised. 48. C8 — Please label all flowlines. Storm sewer flowline labels have been added to sheet C8. 49. C8 — Provide more details for the detention pond including cross sections. It is unclear how water will actually enter the detention pond. Additional details have been added on sheet C8 and C9. Storm water captured from the roof and interior drains will be piped directly to the detention facility. 50. C9 — It appears that the top of JB101 is above existing ground based on the profile. The top of JB101 has been adjusted to match existing ground. 51. C9 — It needs to be clearly labeled that everything upstream of JB102 will be private. Additional labels have been added to clearly label private infrastructure. 52. C9 — Please add a note regarding the ownership and maintenance of the private storm/detention. Note 4 has been revised to clarify owenership and maintanence of detention and private storm improvements. 53. Water Report — Since the parking garage will be a different building material type from the remainder of the building and typically unsprinkled, Appendix B of the International Fire Code requires that a combination fire flow be calculated. The parking garage is required to be sprinkled. The fire flow was calculated using the total building square footage at the more intense fire demand use. 54. Water Report — Provide an exhibit showing the existing water system surrounding the property including fire hydrants that will serve the site. A water exhibit is attached. 55. Water Report — The report should indicate how many fire hydrants are needed to serve the site and the required spacing of them. The report has been revised to indicate fire hydrant requirements. 56. Water Report — Provide velocity and pressure information for the surrounding water system when subject to multiple hydrants being flown simultaneously and peak domestic demands. Velocity and pressure information for the existing system has been modeled and added to the water report. 57. Water Report — The Fire Marshal requires that the actual fire flow test produce the necessary fire flow per the IFC. This fire flow cannot be based on a theoretical calculation of potential flowrate. The water services department was contacted and the flow test requested. Water services replied that they could not perform this test. 58. Drainage Report — Please include a detail of the pond in the report and indicate how water will collected and routed to the detention pond. A detail of the detention facility has been added to the drainage report. Water will be piped directly into detention facility as shown in the Building Construction Drawings. 59. Drainage Report — Provide an analysis of the ponding in the parking area. There will be no ponding in parking areas. 60. Drainage Report — What is the 100-year clogged WSE? There should be 6-in of freeboard between the clogged WSE and the top of the outfall. In the case of the outlet clogging the water will overflow the outlet structure through the grate on the top of the structure and discharge into the public right-of-way. 61. FYI... Additional Development Permit Fee in the amount of 1 % of the total public infrastructure cost will be required. Noted. Reviewed by: Erika Bridges Date: 1/30/15 ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION 62. SITE PLAN/PLAT: Developer will provide CSU with a digital, AutoCAD dwg format, version of plat and / or site plan as soon as it is available. Email to: sweidona.cstx.gov. CAD files have been provided. 63. LOAD DATA: The developer will provide load data to CSU as soon as it is available. This information is critical for CSU to accurately determine the size and number of transformers, and other equipment, required to provide service to the project. Failure to provide load data will result in construction delays and, due to clearance requirements, could affect the final building footprint. Delivery time for transformers and other equipment not in stock is approximate 26 weeks. Load data has been provided. 64. EASEMENTS: Developer provides temporary blanket easement for construction purposes and upon completion of project must provide descriptive easements for electric infrastructure as designed by CSU. Noted. 65. EASEMENTS: Developer provides descriptive easements for electric infrastructure as designed by CSU, as shown on plat or site plan. Noted. 66. If easements are existing, the developer will be responsible for locating easements on site to insure that electrical infrastructure is installed within easement boundaries. Noted. 67. GENERAL ELECTRICAL COMMENTS 68. Developer installs conduit per CSU specs and design. Noted. 69. CSU will provide drawings for electrical installation. Noted. 70. Developer will intercept existing conduit at designated transformers or other existing devices and extend as required. Noted. 71. If conduit does not exist at designated transformer or other existing devices, developer will furnish and install conduit as shown on CSU electrical layout. Noted. 72. Developer pours electric device pads or footings, i.e. transformers, pull boxes, or other device, per CSU specs and design. Noted. 73. Final site plan must show all proposed electrical facilities necessary to provide electrical service, i.e. transformers, pull boxes, or switchgears, all meter locations, and conduit routing as designed by CSU. Noted. 74. To discuss any of the above electrical comments please contact Sam Weido at 979.764.6314. Noted. Reviewed by: Sam Weido Date: 1/9/15 FIRE 75. Parking on Boyett St., next to the building, will need to be removed for the Aerial Access Easement. No obstructions allowed in this area. (Overhead electric lines) Noted, this is still under review with Development Services. 76. Knox Box required (Contractor to contact Fire Marshal for application and location). Site specific note # 15 addresses Knox Box requirements. 77. Electric power (normal and back up) will have shunt trip switches. Noted. Reviewed by: Steve Smith Date: 1/7/15 SANITATION 78. Need to discuss how garbage services will be collected. Garbage services will be a compactor with a 15 cy roll off container located in an enclosure accessed from Second Street. Reviewed by: Wally Urrutia Date: 1/9/15 STAFF REVIEW COMMENTS NO. 1 Project: Second Street Apartments (SP) 15-00900002 PLANNING /1. Please include unit mix on the site plan. The unit mix has been added to the site plan. dy J' � v3. Please add general note to show the required floor -to -area ratio of 1:1 is met by the proposed square footage. This calculation does not include easements, setbacks, and sidewalk. General Note 4 has been added to show floor to area ratio is met. have looked at the administrative adjustment briefly to see the proposal. Please formerly submit the application for full review. The administrative adjustment is attached to this response to comments. L,/4. Parkland dedication in the amount of $209,408 ($1,636 x 128 Units) will be due prior to issuance building permits. Noted. 5 Please label existing and proposed street lights and include label in the legend. Existing and proposed street lights have been labeled. L,6. Please revise site plan comment 14 to say it is a compactor and indicate gate clearance. Note 14 has been revised. ✓7. Please revise bicycle count. More bike racks should be provided. Area between the building facade and sidewalk to be used to install bicycle racks is a potential location. Additional bicycle racks have been added to compensate for the 18 space reduction requested by administrative adjustment. l/8. Please add color to detail for benches. Black or bronze (Brown) powder coating color are permitted. Bench color has been added to detail. ti/9. Please change building orientation on sheet 2 to match sheet 1. Building orientation on sheet 2 has been revised. �— 10. The throat depth for the gated entry requires a minimum 100-foot from Boyett. The current design does not meet that. Refer to the attached letter regarding throat depth. \ j/11. Brick pavers on Cherry should follow the running bond pattern with the long side parallel to Cherry. Noted, detail shows running bond pattern with long side paralleling roadways. The hatching has been revised to reflect the correct pattern. ✓12. Where tree grates are not along the back of curb, please place benches on the same side. Benches have been relocated to match tree grate location on sidewalk. CCrnrne'AK- -A� �' C,x q e 3, cLJ c l e Vices n } t� �kA O JC ' orf'wr Ord aw �Cr�e.a p s ,-ko 5noc.,.7 cnr neck . ebhor)CIA VinSa Pr„V,c'ecl {4r--re, taker-r eca e to (rxC nS G(nOeJ 13. Please note that any changes made to the plans that have not been requested by the City of College Station must be explained in your next transmittal letter. Noted. The project name has been changed to Cherry Street Apartments. Attached is a revised application. Reviewed by: Jessica Bullock Date: 1/29/15 LAN DSCAPING/STREETSCAPING/BUFFER I14. Please revise the landscape plan to show tree grates and benches as proposed on the site plan. Landscape plan has been revised. /15. Due to the proximity of the tree to the building please verify that the Cedar Elm will be able to survive. If not, please propose a tree that will meet the same requirements for review. Cedar elms will be able to survive per landscape architect. �16. A Private Improvement in the Public Right -Of -Way agreement (PIP) will need to be submitted for the landscape/streetscape improvements. PIP application submittal is attached. ✓17. The tree planter detail on the site plan shows that 4" min caliper will be on Boyett St with 3" min caliper on Cherry and Second. The landscape plan shows 4" min caliper all around, please confirm which is used and revise plans accordingly. All street trees will be 4" caliper. The details have been revised. v11 S. Please provide detail for tree grates that are not located back of curb. Tree grate details are shown on sheet C2-Site Plan sheet 2 of 2. J19. Please remove landscaping point calculations. Landscape point calculations have been removed. 20. The label shows 54 H.D. Nandina but I am showing 59. Please revise plantings or quantity. Nandina count has been revised. n 21. Please label existing and proposed street lights. Street lights have been labeled. /22. Decomposed granite does not meet accessibility standards. From the doorway to the sidewalk there needs to be a hard, solid surface landing and sidewalk. Sidewalks will be provided to doorways. z3. Provide a general note that 100% coverage of groundcover, decorative paving, v/ decorative rock (not loose), or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights -of -way, and adjacent property disturbed during construction. Note has been added. 24. Please add the following notes to the landscape plan. The notes below have been added to landscape plan. G• Irrigation system must be protected by a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. �.� All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. Reviewed by: Jessica Bullock Date: 1/26/15 ENGINEERING COMMENTS NO. 1 25. Provide an erosion control plan, traffic control plan, and an NOI. Erosion control plan has been added to drainage plan. Traffic control plan have been added. This site is smaller than 5 acres of disturbance and does not require an NOI. The small construction site notice will be submitted prior to release of construction plans. 26. Cost Estimate — It appears that public storm, sidewalk, and street repair are missing from the estimate. A revised engineer's estimate is attached. 27. C1 — Show and label all easements on or adjacent to the site (include volume & page number). All easements have been labeled with information available. 28. C1 — Add a note with the building size, material, whether or not it's sprinkled, and the required fire flow. Site specific note 3 gives information above. 29. C1 — Label the meter sizes, fire line, and isolation valve. Based on the size of the meter, a meter vault needs to be provided. Inset has been added to sheet C1. 30. C1/C6 — Per Water Services, a 15-ft separation is required between the building and the water & sanitary sewer lines. The only exception to this is the sanitary sewer line adjacent to the southern property line, which may remain in its existing location. Additional pavement repair will likely be needed. Water lines have been relocated to 15' separation from the building. The sewer line on Cherry Street will become a private service. Additional pavement will be removed and repaired on Boyett Street. The curb and gutter will be removed on Second Street 31. C1/C6 — Per Electrical, additional PUE is needed for the proposed transformer. Please show and label. FYI ... A blanket easement or specific PUE must be dedicated prior to site plan approval. A PUE has been added and an easement application will be submitted separately. An easement application for the blanket easement is being prepared and will be submitted separately. 32. C1/C6 — It looks like the irrigation line dead -ends on the north side of the property. Is that the correct or is does it have another connection? The irrigation system will extend to property line to provide irrigation to proposed landscaping. 33. C2/C5 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is set back away from the back of curb and sections that are sidewalk only without the tree. Additional details have been added. 34. C2 — Why does the `Tree Grate Detail' specify that the 4-inch drain line should be within tree bedding areas only? The Tree Grate Detail has been revised to remove the wording specifying the 4" drain only be within tree bedding areas. 35. C2/C5 — Include the street tree detail showing the cross-section of the trees/sidewalk parallel to the street (shown on page 49 of the Site Design Standards). Street tree detail from site design standards have been added. 36. C2 — The Site Design Standards allow for an engineered alternative to structural soil. The specified Bedding Mix alternative and structural design should "bridge the bedding material by tying the sidewalk into the curb and back to undisturbed soil & provide enough structural support to handle vehicles parking & driving on the sidewalk." Please provide a letter certifying that these objectives are achieved with the proposed alternative design. A letter certifying the alternate sidewalk design is attached. 37. C3 — It seems like additional pavement removal & replacement will be needed for areas where water and sanitary sewer are being relocated. Pavement removal is shown on the Pavement and Demolition Plans. No additional pavement removal and replacement is proposed. 38. C3 — The limits of the sanitary sewer line removal are unclear. Are you proposing grout filling a portion of the sewer between manholes/cleanouts and removing a portion? The sewer line through the lot and down Cherry will either be removed or abandoned and grouted in place. The contractor is requesting the flexibility to determine between the two approved methods shown on the demolition plan. A portion of the 8" sewer line will be removed. 39. C3 — How do you propose detouring pedestrian traffic while the sidewalks are closed during construction? The pedestrian traffic will be detoured to College Main. Refer to the traffic control plan. 40. C3 — Include a note regarding the contractor coordinating with Water Services, CSU, and Atmos well ahead of disruption of service and/or removal of utility lines. Note #9 has been added to sheet C3. 41. C3 — It appears that the proposed waterline on the north side will require part of the street to be removed in order to be installed in that location. We are proposing removal of the curb and gutter along Second Street for the installation of the proposed waterline. No additional pavement removal is proposed. 42. C6 — It is difficult to tell the difference between proposed lines & lines that are proposed to be removed. Please distinguish. Lines to be removed have been taken off sheet C6 and are shown on sheet C3 Demolition Plan. 43. C6 — Clearly label private irrigation, storm, and sanitary sewer lines. Additional labels have been added to sheet C6. 44. C6 — Water and sanitary sewer lines need to be at least 3-ft horizontally from other utilities (storm, electrical, gas, etc.). Noted, utilities have been adjusted to provide horizontal clearances. 45. C7 —The scale of the plan drawings are too small and difficult to read. It is unclear which lines the labels correspond to. This will need to be reviewed again once the scale is more legible. The plan view scale has been increased, to provide more clarification. 46. C7 — There should be at least a 1-ft vertical separation between storm and water lines. The water line has been revised to provide 1' clearance. 47. C8 — Specify how much riprap should be added at the storm outfall? No rock riprap will be provided. The detail has been revised. 48. C8 — Please label all flowlines. Storm sewer flowline labels have been added to sheet C8. 49. C8 — Provide more details for the detention pond including cross sections. It is unclear how water will actually enter the detention pond. Additional details have been added on sheet C8 and C9. Storm water captured from the roof and interior drains will be piped directly to the detention facility. 50. C9 — It appears that the top of J13101 is above existing ground based on the profile. The top of JB101 has been adjusted to match existing ground. 51. C9 — It needs to be clearly labeled that everything upstream of JB102 will be private. Additional labels have been added to clearly label private infrastructure. 52. C9 — Please add a note regarding the ownership and maintenance of the private storm/detention. Note 4 has been revised to clarify owenership and maintanence of detention and private storm improvements. 53. Water Report — Since the parking garage will be a different building material type from the remainder of the building and typically unsprinkled, Appendix B of the International Fire Code requires that a combination fire flow be calculated. The parking garage is required to be sprinkled. The fire flow was calculated using the total building square footage at the more intense fire demand use. 54. Water Report — Provide an exhibit showing the existing water system surrounding the property including fire hydrants that will serve the site. A water exhibit is attached. 55. Water Report — The report should indicate how many fire hydrants are needed to serve the site and the required spacing of them. The report has been revised to indicate fire hydrant requirements. 56. Water Report — Provide velocity and pressure information for the surrounding water system when subject to multiple hydrants being flown simultaneously and peak domestic demands. Velocity and pressure information for the existing system has been modeled and added to the water report. 57. Water Report — The Fire Marshal requires that the actual fire flow test produce the necessary fire flow per the IFC. This fire flow cannot be based on a theoretical calculation of potential flowrate. The water services department was contacted and the flow test requested. Water services replied that they could not perform this test 58. Drainage Report — Please include a detail of the pond in the report and indicate how water will collected and routed to the detention pond. A detail of the detention facility has been added to the drainage report. Water will be piped directly into detention facility as shown in the Building Construction Drawings. 59. Drainage Report — Provide an analysis of the ponding in the parking area. There will be no ponding in parking areas. 60. Drainage Report — What is the 100-year clogged WSE? There should be 6-in of freeboard between the clogged WSE and the top of the outfall. In the case of the outlet clogging the water will overflow the outlet structure through the grate on the top of the structure and discharge into the public right-of-way. 61. FYI... Additional Development Permit Fee in the amount of 1% of the total public infrastructure cost will be required. Noted. Reviewed by: Erika Bridges Date: 1/30/15 ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION 62. SITE PLAN/PLAT: Developer will provide CSU with a digital, AutoCAD dwg format, version of plat and / or site plan as soon as it is available. Email to: sweido(aa)cstx.gov. CAD files have been provided. 63. LOAD DATA: The developer will provide load data to CSU as soon as it is available. This information is critical for CSU to accurately determine the size and number of transformers, and other equipment, required to provide service to the project. Failure to provide load data will result in construction delays and, due to clearance requirements, could affect the final building footprint. Delivery time for transformers and other equipment not in stock is approximate 26 weeks. Load data has been provided. 64. EASEMENTS: Developer provides temporary blanket easement for construction purposes and upon completion of project must provide descriptive easements for electric infrastructure as designed by CSU. Noted. 65. EASEMENTS: Developer provides descriptive easements for electric infrastructure as designed by CSU, as shown on plat or site plan. Noted. 66. If easements are existing, the developer will be responsible for locating easements on site to insure that electrical infrastructure is installed within easement boundaries. Noted. 67. GENERAL ELECTRICAL COMMENTS 68. Developer installs conduit per CSU specs and design. Noted. 69. CSU will provide drawings for electrical installation. Noted. 70. Developer will intercept existing conduit at designated transformers or other existing devices and extend as required. Noted. 71. If conduit does not exist at designated transformer or other existing devices, developer will furnish and install conduit as shown on CSU electrical layout. Noted. 72. Developer pours electric device pads or footings, i.e. transformers, pull boxes, or other device, per CSU specs and design. Noted. 73. Final site plan must show all proposed electrical facilities necessary to provide electrical service, i.e. transformers, pull boxes, or switchgears, all meter locations, and conduit routing as designed by CSU. Noted. 74. To discuss any of the above electrical comments please contact Sam Weido at 979.764.6314. Noted. Reviewed by: Sam Weido Date: 1/9/15 FIRE 75. Parking on Boyett St., next to the building, will need to be removed for the Aerial Access Easement. No obstructions allowed in this area. (Overhead electric lines) Noted, this is still under review with Development Services. 76. Knox Box required (Contractor to contact Fire Marshal for application and location). Site specific note # 15 addresses Knox Box requirements. 77. Electric power (normal and back up) will have shunt trip switches. Noted. Reviewed by: Steve Smith Date: 1/7115 SANITATION 78. Need to discuss how garbage services will be collected. Garbage services will be a compactor with a 15 cy roll off container located in an enclosure accessed from Second Street. Reviewed by: Wally Urrutia Date: 1/9/15 STAFF REVIEW COMMENTS NO. 1 Project: Second Street Apts (SP) 15-00900002 PLANNING 1. Please include unit mix on the site plan. 2. Please add general note to show the required floor -to -area ratio of 1:1 is met by the proposed square footage. This calculation does not include easements, setbacks, and sidewalk. 3. 1 have looked at the administrative adjustment briefly to see the proposal. Please formerly submit the application for full review. 4. Parkland dedication in the amount of $209,408 ($1,636 x 128 Units) will be due prior to issuance building permits. 5. Please label existing and proposed street lights and include label in the legend. 6. Please revise site plan comment 14 to say it is a compactor and indicate pate clearance. 8. Please add color to detail for benches. Black or bronze (Brown) powder coating color are permitted. 9. FOR ME —Wait for sams comment about the width of the transformer easement 10. Please change building orientation on sheet 2 to match sheet 1. 11. CHECK WITH BEN on inoress/eoress, Landina'area by upper route. sidewalk outside 12. CHECK WITH DANIELLE the throat depth with the gate. She said they will need to meet requirements possibly with a decal lane. Or remove gate. Check with Erika. Other option is moving gates back and providing on one side? 13. CHECK WITH ERIKA about rebar for sidewalk spec. 14. Brick pavers on Cherry should follow the running bond pattern with the long side parallel to Cherry. 15. Where tree grates are not along the back of curb, please place benches on the same side. 16. Provide a aeneral mote on the site Han that all mof'and arrnind-mmintarl manhaninn 17. Please note that any changes made to the plans that have not been requested by the City of College Station must be explained in your next transmittal letter. Reviewed by: Jessica Bullock Date: 1/26/15 LANDSCAPING/STREETSCAPING/BUFFER 1. Please revise the landscape plan to show tree grates and benches as proposed on the site plan. 2. Due to the proximity of the tree to the building please verify that the Cedar Elm will be able to survive. If not, please propose a tree that will meet the same requirements for review. Page 2 of 3 Staff reviewed the above -mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: City of College Station Transmittal Letter; Memoproviding written responses to all of staff's comments (identify the specific page that each comment was addressed on or the reason for not addressing the comment); One (1) complete sets of site civil construction documents for the proposed development with the revised site and landscaping plans attached; One (1) 24"x36" revised site plan; One (1) 24"x36" revised landscaping plan; Easement Dedication Sheet and required documents (please note that the Site Plan will not be stamped approved until the Blanket Easement, or all other appropriate easements, have been dedicated to the City of College Station). One (1) Private Improvement in the Public Right -Of -Way agreement (PIP). Please note that this application will expire in 90 days from the date of this memo, if the applicant has not provided written response comments and revised documents to the Administrator that seek to address the staff review comments contained herein. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please contact Jessica Bullock at 979.764.3570. Attachments: Staff Review Comments PC: P&DS Project No. 15-00900002 Page 1 of 3 4. The tree planter detail on the site plan shows that 4" min caliper will be on Boyett St with 3" min caliper on Cherry and Second. The landscape plan shows 4" min caliper all around, please confirm which is used and revise plans accordingly. 5. Please provide detail for tree grates that are not located back of curb. 6. Please remove landscaping point calculations. 7. The label shows 54 H.D. Nandina but I am showing 59. Please revise plantings or quantity. 8. Please label existing and proposed street lights. 9. Decomposed granite does not meet accessibility standards. From the doorway to the sidewalk there needs to be a hard, solid surface landing and sidewalk. 10. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock (not loose), or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights -of -way, and adjacent property disturbed during construction. 11. Please add the following notes to the landscape plan. • Irrigation system must be protected by a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. • All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. Reviewed by: Jessica Bullock Date: 1/26/15 Staff Review Comments No. 2 Project: Second Street Apts (SP)—15-00900002 I W 1I:\►R ►Ce1 1. See engineering comments regarding the throat depth requirement. Noted 2. Please change the bicycle parking calculation in the parking analysis to reflect the additional bicycle parking spaces added. In the administrative adjustment explanation please add that additional bicycle parking spaces are provided to help with the decrease in vehicular parking spaces. The parking analysis has been revised and the revised administrative adjustments explanation is attached. ✓3. Please note, exact location of street lights will be determined in the field. Site specific note #17 has been added to the site plan. 4. Please note that any changes made to the plans that have not been requested by the City of College Station, must be explained in your next transmittal letter. Noted. LANDSCAPING �/1. Please label existing and proposed street lights. Existing and proposed street lights have been labeled Reviewed by: Jessica Bullock Date: 3/17/15 ENGINEERING COMMENTS NO.2 Y (Original Comment) Cl — Show and label all easements on or adjacent to the site (include volume & page number). Label the existing 15-ft PUE adjacent to the property with volume and page number. The volume and page information has been added (Original Comment) Cl/C6—Per Water Services, a 15 ft separation is required between the building and the water & sanitary sewer lines. The only exception to this is the sanitary sewer line adjacent to the southern property line, which may remain in its existing location. Additional pavement repair will likely be needed. Please verify that the sewer line has been visually inspected and there are no flows through the line. The sewer line has been visually inspected and there are no, flows through the line. $/ (Original Comment) C2105 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is set back away from the back of curb and sections that are sidewalk only without the tree. The detail without the tree should still include the underdrain pipe and moisture barrier per the similar Site Design Standards detail. The detail mentioned has been revised. (Original Comment) C8 — Provide more details for the detention pond including cross sections. It is unclear how water will actually enter the detention pond. Regarding Notes #1 & 2 pertaining to the detention pond, the structural drawings and stormwater piping into the pond are details that need to be included in the civil plan set. Notes I & 2 have been revised, structural drawings for detention facility have been added to the plan set, and approximate locations for incoming stormwater piping have been shown. (Original Comment) Water Report — The Fire Marshal requires that the actual fire flow test produce the necessary fire flow per the IFC This fire flow cannot be based on a theoretical calculation of potential flowrate. FYI...The Water Dept. is going to be running another simultaneous fire flow test this next week. We will forward results as soon as possible. Noted, attached is the revised Water Report with the updated fire flow data provided by the City. (Original Comment) Drainage Report — Please include a detail of the pond in the report and indicate how water will collected and routed to the detention pond. Details showing how the stormwater will be routed to the pond need to be provided in the drainage report and civil construction plans, not just the building plans. Details showing how stormwater will be routed to the pond have been added to the drainage report and construction drawings. A revised Drainage Exhibit is attached. (Original Comment) Drainage Report — Provide an analysis of the ponding in the parking area. Are any grate inlets/drains proposed in the parking area? The buildings drain system does have grate inlets. The building storm drain piping has been added to the construction plans ® (Original Comment) FYI —Additional Development Permit Fee in the amount of 1 % of the total public infrastructure cost will be required. Based on the Engineer's Cost Estimate, the DP Fee balance is $1,117.97. Noted JC3/C6 — Please provide additional details for the removal of the sanitary sewer line & repair of the manhole. (i.e. label linear footage of line to be removed; PVC, rubber boot, etc. needs to be completely removed from or cut out of the manhole; what type of concrete should fill the void in the manhole; specify how the hole should be filled and concrete smoothed inside and outside the mahole). Additional information has been added to sewer line removal and /C anhole repair. 10 — FYI ... These are preliminary comments regarding Traffic Control, as Public Works is I11 reviewing the plan. Noted, a meeting has been held to discuss traffic control, C10 — Where will the staging area and laydown yard be for this project? Were you still proposing to utilize all of Cherry St.? If so, this plan needs to reflect that. The contractor will be leasing the lots across Cherry Street for Construction Offices and laydown yard. The traffic control plan has been revised per meeting comments, including the closure of Cherry Street /CIO — Based on this plan, parking will need to be temporarily removed on one side of Boyett. This will also need to go to City Council for approval. Based on traffic control plan meeting Vmporary removal is not needed for Boyett Street. 10 — The intersection of Cherry/Boyett will need to be partially or completely closed at some point to install the storm sewer. Please provide traffic control for this scenario. Cherry Street will be closed completely during construction. Construction activities requiring lane closures will be temporary and roads will be reopened to two way traffic at night VC10 — Note #9 references "appropriate signage" is going to be up at night. Should the /appropriate signage be specified? Note 9 has been revised. U'S. Gate Variance — How will visitors know that they do not have access before attempting to enter the garage? Is there enough space to add a bailout lane so that there isn't a backing maneuver on the street by one or more cars in the queue? A "Residential Parking Only" sign will be located at the entrance. There is not enough room for a bailout lane. Gate Variance — How will the gate open/close? (i.e. swing gate, sliding gate, etc.) The gate will be an arm style gate with an up & down open/close action. Y/// Gate Variance — Where will the call box be located? There is no call box, the gate will be / controlled by remote gate FOBS. YB. Gate Variance — The letter indicates that there will be visitor parking along Cherry St., however, parking is proposed to be removed in that location. Please revise letter. The letter has been revised to indicate Boyett St as having visitor parking. Reviewed by: Erika Bridges Date: 3/9/15 d CITY OF COLLEGE SFATION Hoene of Texas A&M University* MEMORANDUM DATE: January 7, 2015 TO: Keller Webster/Gary Daily, KWA Construction, via; gdailyokwaconstruction.com FROM: Jessica Bullock, Staff Planner SUBJECT: SECOND STREET APTS (SP) Thank you for the submittal of your Site Plan - Residential application. Erika Bridges, Graduate Engineer 11, and I have been assigned to review this project. It is anticipated that the review will be completed and any staff comments returned to you on or before Wednesday, January 21, 2015. If you have questions in the meantime, please feel free to contact us. PC: CS Second Street Apartments II, LLC, via; thebelinpnewschooladv.com Deven Doyen, Schultz Engineering, LLC, via; deven schultzengineeringllc.com Tom Ekenberg, via; USPS; 16800 Westgrove Suite 100, Addison TX, 75001 P&DS Project No. 15-00900002 Planning & Development Services P.O. BOX 9960 • I101 TEXAS AVENUE • COLLEGE STATION • TEXAS - 77842 TEL 979.764.3570 • FAX. 979.764.3496 cstx.gov/devservices Thank you for the submittal of your Site Plan - Residential application. Erika Bridges, Graduate Engineer 11, and I have been assigned to review this project. It is anticipated that the review will be completed and any staff comments returned to you on or before Wednesday, January 21, 2015. If you have questions in the meantime, please feel free to contact us. DATE: TO: FROM: SUBJECT CITY OF COLLEGE STATION Home of Texas Ad-M University® MEMORANDUM Keller Webster/Gary Daily, KWA Construction, via; gdaily()kwaconstruction.com SECOND STREET APTS (SP) PC: CS Second Street Apartments II, LLC, via; therbelin(a)newschooladv.com Deven Doyen, Schultz Engineering, LLC, via; deven(a�schultzengineeringllc.com Tom Ekenberg, via; USPS; 16800 Westgrove Suite 100, Addison TX, 75001 P&DS Project No. 15-00900002 Planning ear Development Services P.O. BOX 9960 • 1101 TEXAS AVENUE • COLLEGE STATION • TEXAS • 77842 TEL. 979.764.3570 • FAX. 979.764.3496 cstx.gov/devservices (*k— ` CITY OF COLLEGE STATION Home of TexasA&M University' MEMORANDUM DATE: January 7, 2015 TO: Keller Webster/Gary Daily, KWA Construction, via; gdaily(a)-kwaconstruction.com FROM: Jessica Bullock, Staff Planner SUBJECT: SECOND STREET APTS (SP) Thank you for the submittal of your Site Plan - Residential application. Erika Bridges, Graduate Engineer II, and I have been assigned to review this project. It is anticipated that the review will be completed and any staff comments returned to you on or before Wednesday, January 21, 2015. If you have questions in the meantime, please feel free to contact us. PC: CS Second Street Apartments II, LLC, via; therbelin(a)newschooladv.com Deven Doyen, Schultz Engineering, LLC, via; deven(a�schultzengineeringllc.com Tom Ekenberg, via; USPS; 16800 Westgrove Suite 100, Addison TX, 75001 P&DS Project No. 15-00900002 Planning & Development Services P.O. BOX 9960 • 1101 TEXAS AVENUE • COLLEGE STATION • TEXAS • 77842 TEL. 979.764.3570 • FAX. 979.764.3496 cstx.gov/devservices FIRE 1) Parking on Boyett St., next to the building, will need to be removed for the Aerial Access Easement. No obstructions allowed in this area. (Overhead electric lines) 2) Knox Box required (Contractor to contact Fire Marshal for application and location) 3) Electric power (normal and back up) will have shunt trip switches. Reviewed by: Steve Smith Date: 01/07/2015 SANITATION 1. Need to discuss how garbage services will be collected. Reviewed by: Wally Urrutia Date: January 9, 2015 ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION SITE PLAN/PLAT: Developer will provide CSU with a digital, AutoCAD dwg format, version of plat and / or site plan as soon as it is available. Email to: sweido(cDcstx.gov LOAD DATA: The developer will provide load data to CSU as soon as it is available. This information is critical for CSU to accurately determine the size and number of transformers, and other equipment, required to provide service to the project. Failure to provide load data will result in construction delays and, due to clearance requirements, could affect the final building footprint. Delivery time for transformers and other equipment not in stock is approximate 26 weeks. EASEMENTS: Developer provides temporary blanket easement for construction purposes and upon completion of project must provide descriptive easements for electric infrastructure as designed by CSU. EASEMENTS: Developer provides descriptive easements for electric infrastructure as designed by CSU, as shown on plat or site plan. If easements are existing, the developer will be responsible for locating easements on site to insure that electrical infrastructure is installed within easement boundaries. GENERAL ELECTRICAL COMMENTS Developer installs conduit per CSU specs and design. CSU will provide drawings for electrical installation. Developer will intercept existing conduit at designated transformers or other existing devices and extend as required. If conduit does not exist at designated transformer or other existing devices, developer will furnish and install conduit as shown on CSU electrical layout. Developer pours electric device pads or footings, i.e. transformers, pull boxes, or other device, per CSU specs and design. Final site plan must show all proposed electrical facilities necessary to provide electrical service, i.e. transformers, pull boxes, or switchgears, all meter locations, and conduit routing as designed by CSU. To discuss any of the above electrical comments please contact Sam Weido at 979.764.6314. Reviewed by: Sam Weido Date: 1.9.15 Staff reviewed the above -mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: City of College Station Transmittal Letter; Memo providing written responses to all of staff's comments; One (1) complete sets of site civil construction documents for the proposed development with the revised site and landscaping plans attached; One (1) 24"x36" revised site plan; One (1) 24"x36" revised landscaping plan; Easement Dedication Sheet and required documents (please note that the Site Plan will not be stamped approved until the Blanket Easement, or all other appropriate easements, have been dedicated to the City of College Station). One (1) Private Improvement in the Public Right -Of -Way agreement (PIP). Please note that this application will expire in 90 days from the date of this memo, if the applicant has not provided written response comments and revised documents to the Administrator that seek to address the staff review comments contained herein. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please contact Jessica Bullock at 979.764.3570. Attachments: Staff Review Comments PC: P&DS Project No. 15-00900002 Page 1 of 3 STAFF REVIEW COMMENTS NO. 1 Project: Second Street Apts (SP) 15-00900002 PLANNING 1. Please include unit mix on the site plan. 2. Please add general note to show the required floor -to -area ratio of 1:1 is met by the proposed square footage. This calculation does not include easements, setbacks, and sidewalk. 3. 1 have looked at the administrative adjustment briefly to see the proposal. Please formerly submit the application for full review. 4. Parkland dedication in the amount of $209,408 ($1,636 x 128 Units) will be due prior to issuance building permits. 5. Please label existing and proposed street lights and include label in the legend. 6. Please revise site plan comment 14 to say it is a compactor and indicate gate clearance. 7. Please revise bicycle count. More bike racks should be provided. Area between the building fagade and sidewalk to be used to install bicycle racks is a potential location. 8. Please add color to detail for benches. Black or bronze (Brown) powder coating color are permitted. 9. Please change building orientation on sheet 2 to match sheet 1. 10. The throat depth for the gated entry requires a minimum 100-foot from Boyett. The current design does not meet that. 11. Brick pavers on Cherry should follow the running bond pattern with the long side parallel to Cherry. 12. Where tree grates are not along the back of curb, please place benches on the same side. 13. Please note that any changes made to the plans that have not been requested by the City of College Station must be explained in your next transmittal letter. Reviewed by: Jessica Bullock Date: 1/29/15 LANDSCAPING/STREETSCAPING/BUFFER 1. Please revise the landscape plan to show tree grates and benches as proposed on the site plan. 2. Due to the proximity of the tree to the building please verify that the Cedar Elm will be able to survive. If not, please propose a tree that will meet the same requirements for review. 3. A Private Improvement in the Public Right -Of -Way agreement (PIP) will need to be submitted for the landscape/streetscape improvements. 4. The tree planter detail on the site plan shows that 4" min caliper will be on Boyett St with 3" min caliper on Cherry and Second. The landscape plan shows 4" min caliper all around, please confirm which is used and revise plans accordingly. 5. Please provide detail for tree grates that are not located back of curb. 6. Please remove landscaping point calculations. 7. The label shows 54 H.D. Nandina but I am showing 59. Please revise plantings or quantity. 8. Please label existing and proposed street lights. 9. Decomposed granite does not meet accessibility standards. From the doorway to the sidewalk there needs to be a hard, solid surface landing and sidewalk. 10. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock (not loose), or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights -of -way, and adjacent property disturbed during construction. 11. Please add the following notes to the landscape plan. Page 2 of 3 • Irrigation system must be protected by a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. • All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. Reviewed by: Jessica Bullock Date: 1/26/15 ENGINEERING COMMENTS NO. 1 1. C1 — Show and label all easements on or adjacent to the site (include volume & page number). 2. C1 — Add a note with the building size, material, whether or not it's sprinkled, and the required fire flow. 3. C1 — Label the meter sizes, fire line, and isolation valve. Based on the size of the meter, a meter vault needs to be provided. 4. C2/C5 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is set back away from the back of curb and sections that are sidewalk only without the tree. 5. C2 — Why does the "Tree Grate Detail" specify that the 4-inch drain line should be within tree bedding areas only? 6. C2/C5 — Include the street tree detail showing the cross-section of the trees/sidewalk parallel to the street (shown on page 49 of the Site Design Standards). 7. C2 — The Site Design Standards allow for an engineered alternative to structural soil. The specified Bedding Mix alternative and structural design should "bridge the bedding material by tying the sidewalk into the curb and back to undisturbed soil & provide enough structural support to handle vehicles parking & driving on the sidewalk." Please provide a letter certifying that these objectives are achieved with the proposed alternative design. 8. Cost Estimate — It appears that public storm, sidewalk, and street repair are missing from the estimate. 9. C3 — It seems like additional pavement removal & replacement will be needed for areas where water and sanitary sewer are being relocated. 10. C3 — It is unclear where the limits of the sanitary sewer line Reviewed by: Date: (*400r� CITY OF COLLEGE STATION Home of Texas Ad-M University' MEMORANDUM DATE: January 30, 2015 TO: Keller Webster/Gary Daily, KWA Construction, via; gdaily(a)_kwaconstruction.com FROM: Jessica Bullock, Staff Planner SUBJECT: SECOND STREET APTS (SP) Staff reviewed the above -mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: City of College Station Transmittal Letter; Memo providing written responses to all of staff's comments; One (1) complete sets of site civil construction documents for the proposed development with the revised site and landscaping plans attached; One (1) 24"x36" revised site plan; One (1) 24"x36" revised landscaping plan; Easement Dedication Sheet and required documents (please note that the Site Plan will not be stamped approved until the Blanket Easement, or all other appropriate easements, have been dedicated to the City of College Station). One (1) Private Improvement in the Public Right -Of -Way agreement (PIP). Please note that this application will expire in 90 days from the date of this memo, if the applicant has not provided written response comments and revised documents to the Administrator that seek to address the staff review comments contained herein. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please contact Jessica Bullock at 979.764.3570. Attachments: Staff Review Comments PC: P&DS Project No. 15-00900002 CS Second Street Apartments II, LLC, via; therbelin(a)newschooladv.com Deven Doyen, Schultz Engineering, LLC, via; deven(a�schultzengineeringllc.com Tom Ekenberg, via; USPS; 16800 Westgrove Suite 100, Addison TX, 75001 Planning ear Development Services P.O. BOX 9960 • 1101 TEXAS AVENUE • COLLEGE STATION • TEXAS • 77842 TEL. 979.764.3570 • FAX. 979.764.3496 cstx.gov/devservices STAFF REVIEW COMMENTS NO. 1 Project: Second Street Apts (SP) 15-00900002 PLANNING 1. Please include unit mix on the site plan. 2. Please add general note to show the required floor -to -area ratio of 1:1 is met by the proposed square footage. This calculation does not include easements, setbacks, and sidewalk. 3. 1 have looked at the administrative adjustment briefly to see the proposal. Please formerly submit the application for full review. 4. Parkland dedication in the amount of $209,408 ($1,636 x 128 Units) will be due prior to issuance building permits. 5. Please label existing and proposed street lights and include label in the legend. 6. Please revise site plan comment 14 to say it is a compactor and indicate gate clearance. 7. Please revise bicycle count. More bike racks should be provided. Area between the building fagade and sidewalk to be used to install bicycle racks is a potential location. 8. Please add color to detail for benches. Black or bronze (Brown) powder coating color are permitted. 9. Please change building orientation on sheet 2 to match sheet 1. 10. The throat depth for the gated entry requires a minimum 100-foot from Boyett. The current design does not meet that. 11. Brick pavers on Cherry should follow the running bond pattern with the long side parallel to Cherry. 12. Where tree grates are not along the back of curb, please place benches on the same side. 13. Please note that any changes made to the plans that have not been requested by the City of College Station must be explained in your next transmittal letter. Reviewed by: Jessica Bullock Date: 1/29/15 LANDSCAPING/STREETSCAPING/BUFFER 1. Please revise the landscape plan to show tree grates and benches as proposed on the site plan. 2. Due to the proximity of the tree to the building please verify that the Cedar Elm will be able to survive. If not, please propose a tree that will meet the same requirements for review. 3. A Private Improvement in the Public Right -Of -Way agreement (PIP) will need to be submitted for the landscape/streetscape improvements. 4. The tree planter detail on the site plan shows that 4" min caliper will be on Boyett St with 3" min caliper on Cherry and Second. The landscape plan shows 4" min caliper all around, please confirm which is used and revise plans accordingly. 5. Please provide detail for tree grates that are not located back of curb. 6. Please remove landscaping point calculations. 7. The label shows 54 H.D. Nandina but I am showing 59. Please revise plantings or quantity. 8. Please label existing and proposed street lights. 9. Decomposed granite does not meet accessibility standards. From the doorway to the sidewalk there needs to be a hard, solid surface landing and sidewalk. 10. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock (not loose), or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights -of -way, and adjacent property disturbed during construction. 11. Please add the following notes to the landscape plan. • Irrigation system must be protected by a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. • All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. Reviewed by: Jessica Bullock Date: 1 /26/15 ENGINEERING COMMENTS NO. 1 1. Provide an erosion control plan, traffic control plan, and an NOI. 2. Cost Estimate — It appears that public storm, sidewalk, and street repair are missing from the estimate. 3. C1 — Show and label all easements on or adjacent to the site (include volume & page number). 4. C1 — Add a note with the building size, material, whether or not it's sprinkled, and the required fire flow. 5. C1 — Label the meter sizes, fire line, and isolation valve. Based on the size of the meter, a meter vault needs to be provided. 6. C1/C6 — Per Water Services, a 15-ft separation is required between the building and the water & sanitary sewer lines. The only exception to this is the sanitary sewer line adjacent to the southern property line, which may remain in its existing location. Additional pavement repair will likely be needed. 7. C1/C6 — Per Electrical, additional PUE is needed for the proposed transformer. Please show and label. FYI ... A blanket easement or specific PUE must be dedicated prior to site plan approval. 8. C1/C6 — It looks like the irrigation line dead -ends on the north side of the property. Is that the correct or is does it have another connection? 9. C2/C5 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is set back away from the back of curb and sections that are sidewalk only without the tree. 10. C2 — Why does the "Tree Grate Detail" specify that the 4-inch drain line should be within tree bedding areas only? 11. C2/C5 — Include the street tree detail showing the cross-section of the trees/sidewalk parallel to the street (shown on page 49 of the Site Design Standards). 12. C2 — The Site Design Standards allow for an engineered alternative to structural soil. The specified Bedding Mix alternative and structural design should "bridge the bedding material by tying the sidewalk into the curb and back to undisturbed soil & provide enough structural support to handle vehicles parking & driving on the sidewalk." Please provide a letter certifying that these objectives are achieved with the proposed alternative design. 13. C3 — It seems like additional pavement removal & replacement will be needed for areas where water and sanitary sewer are being relocated. 14. C3 — The limits of the sanitary sewer line removal are unclear. Are you proposing grout filling a portion of the sewer between manholes/cleanouts and removing a portion? 15. C3 — How do you propose detouring pedestrian traffic while the sidewalks are closed during construction? 16. C3 — Include a note regarding the contractor coordinating with Water Services, CSU, and Atmos well ahead of disruption of service and/or removal of utility lines. 17. C3 — It appears that the proposed waterline on the north side will require part of the street to be removed in order to be installed in that location. 18. C6 — It is difficult to tell the difference between proposed lines & lines that are proposed to be removed. Please distinguish. 19. C6 — Clearly label private irrigation, storm, and sanitary sewer lines. 20. C6 — Water and sanitary sewer lines need to be at least 3-ft horizontally from other utilities (storm, electrical, gas, etc.) 21. C7 — The scale of the plan drawings are too small and difficult to read. It is unclear which lines the labels correspond to. This will need to be reviewed again once the scale is more legible. 22. C7 — There should be at least a 1-ft vertical separation between storm and water lines. 23. C8 — Specify how much riprap should be added at the storm outfall? 24. C8 — Please label all flowlines. 25. C8 — Provide more details for the detention pond including cross sections. It is unclear how water will actually enter the detention pond. 26. C9 — It appears that the top of JB101 is above existing ground based on the profile. 27. C9 — It needs to be clearly labeled that everything upstream of JB102 will be private. 28. C9 — Please add a note regarding the ownership and maintenance of the private storm/detention. 29. Water Report — Since the parking garage will be a different building material type from the remainder of the building and typically unsprinkled, Appendix B of the International Fire Code requires that a combination fire flow be calculated. 30. Water Report — Provide an exhibit showing the existing water system surrounding the property including fire hydrants that will serve the site. 31. Water Report — The report should indicate how many fire hydrants are needed to serve the site and the required spacing of them. 32. Water Report — Provide velocity and pressure information for the surrounding water system when subject to multiple hydrants being flown simultaneously and peak domestic demands. 33. Water Report — The Fire Marshal requires that the actual fire flow test produce the necessary fire flow per the IFC. This fire flow cannot be based on a theoretical calculation of potential flowrate. 34. Drainage Report — Please include a detail of the pond in the report and indicate how water will collected and routed to the detention pond. 35. Drainage Report — Provide an analysis of the ponding in the parking area. 36. Drainage Report — What is the 100-year clogged WSE? There should be 6-in of freeboard between the clogged WSE and the top of the outfall. 37. FYI... Additional Development Permit Fee in the amount of 1% of the total public infrastructure cost will be required. Reviewed by: Erika Bridges Date: 1 /30/15 ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION SITE PLAN/PLAT: Developer will provide CSU with a digital, AutoCAD dwg format, version of plat and / or site plan as soon as it is available. Email to: sweido(cDcstx.gov LOAD DATA: The developer will provide load data to CSU as soon as it is available. This information is critical for CSU to accurately determine the size and number of transformers, and other equipment, required to provide service to the project. Failure to provide load data will result in construction delays and, due to clearance requirements, could affect the final building footprint. Delivery time for transformers and other equipment not in stock is approximate 26 weeks. EASEMENTS: Developer provides temporary blanket easement for construction purposes and upon completion of project must provide descriptive easements for electric infrastructure as designed by CSU. 4. EASEMENTS: Developer provides descriptive easements for electric infrastructure as designed by CSU, as shown on plat or site plan. 5. If easements are existing, the developer will be responsible for locating easements on site to insure that electrical infrastructure is installed within easement boundaries. GENERAL ELECTRICAL COMMENTS 1. Developer installs conduit per CSU specs and design. 2. CSU will provide drawings for electrical installation. 3. Developer will intercept existing conduit at designated transformers or other existing devices and extend as required. 4. If conduit does not exist at designated transformer or other existing devices, developer will furnish and install conduit as shown on CSU electrical layout. 5. Developer pours electric device pads or footings, i.e. transformers, pull boxes, or other device, per CSU specs and design. 6. Final site plan must show all proposed electrical facilities necessary to provide electrical service, i.e. transformers, pull boxes, or switchgears, all meter locations, and conduit routing as designed by CSU. 7. To discuss any of the above electrical comments please contact Sam Weido at 979.764.6314. Reviewed by: Sam Weido Date: 1 /9/15 FIRE 1. Parking on Boyett St., next to the building, will need to be removed for the Aerial Access Easement. No obstructions allowed in this area. (Overhead electric lines) 2. Knox Box required (Contractor to contact Fire Marshal for application and location) 3. Electric power (normal and back up) will have shunt trip switches. Reviewed by: Steve Smith Date: 1/7/15 SANITATION 1. Need to discuss how garbage services will be collected. Reviewed by: Wally Urrutia Date: 1/9/15 ENGINEERING COMMENTS NO. 2 1. (Original Comment) C1 — Show and label all easements on or adjacent to the site (include volume & page number). Label the existing 15-ft PUE adjacent to the property with volume and page number. 2. (Original Comment) C 1/C6 — Per Water Services, a 15-ft separation is required between the building and the water & sanitary sewer lines. The only exception to this is the sanitary sewer line adjacent to the southern property line, which may remain in its existing location. Additional pavement repair will likely be needed. Please verify that the sewer line has been visually inspected and there are no flows through the line. 3. (Original Comment) C2/C5 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is set back away from the back of curb and sections that are sidewalk only without the tree. The detail without the tree should still include the underdrain pipe and moisture barrier per the similar Site Design Standards detail. 4. (Original Comment) C8 — Provide more details for the detention pond including cross sections. It is unclear how water will actually enter the detention pond. Regarding Notes #1 & 2 pertaining to the detention pond, the structural drawings and stormwater piping into the pond are details that need to be included in the civil plan set. 5. (Original Comment) Water Report — The Fire Marshal requires that the actual fire flow test produce the necessary fire flow per the IFC. This fire flow cannot be based on a theoretical calculation of potential flowrate. FYI... The Water Dept. is going to be running another simultaneous fire flow test this next week. We will forward results as soon as possible. 6. (Original Comment) Drainage Report — Please include a detail of the pond in the report and indicate how water will collected and routed to the detention pond. Details showing how the stormwater will be routed to the pond need to be provided in the drainage report and civil construction plans, not just the building plans. 7. (Original Comment) Drainage Report — Provide an analysis of the ponding in the parking area. Are any grate inlets/drains proposed in the parking area? 8. (Original Comment) FYI... Additional Development Permit Fee in the amount of 1 % of the total public infrastructure cost will be required. Based on the Engineer's Cost Estimate, the DP Fee balance is $1,117.97. 9. C3/C6 — Please provide additional details for the removal of the sanitary sewer line & repair of the manhole. (i.e. label linear footage of line to be removed; PVC, rubber boot, etc. needs to be completely removed from or cut out of the manhole; what type of concrete should fill the void in the manhole; specify how the hole should be filled and concrete smoothed inside and outside the mahole). 10. C10 — FYI... These are preliminary comments regarding Traffic Control, as Public Works is still reviewing the plan. 11. C10 — Where will the staging area and Iaydown yard be for this project? Were you still proposing to utilize all of Cherry St.? If so, this plan needs to reflect that. 12. C10 — Based on this plan, parking will need to be temporarily removed on one side of Boyett. This will also need to go to City Council for approval. 13. C10 — The intersection of Cherry/Boyett will need to be partially or completely closed at some point to install the storm sewer. Please provide traffic control for this scenario. 14. C10 — Note #9 references "appropriate signage" is going to be up at night. Should the appropriate signage be specified? 15. Gate Variance — How will visitors know that they do not have access before attempting to enter the garage? Is there enough space to add a bailout lane so that there isn't a backing maneuver on the street by one or more cars in the queue? 16. Gate Variance — How will the gate open/close? (i.e. swing gate, sliding gate, etc.) 17. Gate Variance — Where will the call box be located? 18. Gate Variance — The letter indicates that there will be visitor parking along Cherry St., however, parking is proposed to be removed in that location. Please revise letter. Reviewed by: Erika Bridges Date: 3/9/15 (*)rq" CITY OF COLLEGE STATION Home of TexasA&M University' 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM TO: FROM: Jessica Bullock, Staff Planner SUBJECT: Second Street Apts (SP) - Site Plan Staff reviewed the above -mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $932 processing fee will need to be submitted for the subsequent set of three (3) reviews. OR City of College Station Transmittal Letter Seven (7) complete sets of site civil construction documents for the proposed development with the revised site and landscaping plans attached (one set will be returned to you, please submit additional copies if you want more than one approved set) Two (2) revised site plans One (1) landscaping plan One (1) 1 1x1 7 grading and erosion control plan Four (4) revised site and one (1) landscaping plan. Please note that this application will expire in 90 days from the date of this memo, if the applicant has not provided written response comments and revised documents to the Administrator that seek to address the staff review comments contained herein. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments Planning & Development Services P.O. BOX 9960 • 1101 TEXAS AVENUE • COLLEGE STATION • TEXAS • 77842 TEL. 979.764.3570 • FAX. 979.764.3496 cstx.gov/devservices we Case file #15-00900002 Page 2 of 3 STAFF REVIEW COMMENTS NO. 2 Project: Second Street Apts (SP) - 15-00900002 PLANNING 1. See engineering comments regarding the throat depth requirement. 2. Please change the bicycle parking calculation in the parking analysis to reflect the additional bicycle parking spaces added. In the administrative adjustment explanation please add that additional bicycle parking spaces are provided to help with the decrease in vehicular parking spaces. 3. Please note, exact location of street lights will be determined in the field. 4. Please note that any changes made to the plans that have not been requested by the City of College Station, must be explained in your next transmittal letter. LANDSCAPING 1. Please label existing and proposed street lights. Reviewed by: Jessica Bullock Date: Page 3 of 3 LEGAL NOTICE DATE TO BE PUBLISHED: MONDAY, MARCH 23, 2015 ONLY BILL TO: Brittany Caldwell City of College Station P.O. Box 9960 College Station, TX 77842 ---------------------------------------------------------------------------- NOTICE OF PUBLIC HEARING: The College Station City Council will hold a public hearing to consider parking removal along the south side of Cherry Street from Second Street to Boyett Street for the Second Street Apartment development. The hearing will be held in the Council Chambers of the College Station City Hall, 1101 Texas Avenue at the 7:00 p.m. meeting of the Council on Thursday, April 9, 2015. For additional information please contact Danielle Singh, the Project Manager, at 979.764.3570. Any request for sign interpretive services for the hearing impaired must be made 48 hours before the meeting. To make arrangements call 979.764.3541 or (TDD) 1.800.735.2989. CITY OF COLLEGE STATION Home of Texas A&M University' MEMORANDUM DATE: TO: Keller Webster/Gary Daily, KWA Construction, via; gdaily(a)-kwaconstruction.com FROM: SUBJECT: SECOND STREET APTS (SP) Staff reviewed the above -mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. City of College Station Transmittal Letter One (1) complete sets of site civil construction documents for the proposed development with the revised site and landscaping plan attached Please note that this application will expire in 90 days from the date of this memo, if the applicant has not provided written response comments and revised documents to the Administrator that seek to address the staff review comments contained herein. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments PC: CS Second Street Apartments II, LLC, via; therbelin(a)newschooladv.com Deven Doyen, Schultz Engineering, LLC, via; deven(a�schultzengineeringllc.com Tom Ekenberg, via; USPS; 16800 Westgrove Suite 100, Addison TX, 75001 P&DS Project No. 15-00900002 Planning & Development Services P.O. BOX 9960 • 1101 TEXAS AVENUE • COLLEGE STATION • TEXAS • 77842 TEL. 979.764.3570 • FAX. 979.764.3496 cstx.gov/devservices STAFF REVIEW COMMENTS NO. 2 Project: Second Street Apts (SP) - 15-00900002 PLANNING 1. See engineering comments regarding the throat depth requirement. 2. Please change the bicycle parking calculation in the parking analysis to reflect the additional bicycle parking spaces added. In the administrative adjustment explanation please add that additional bicycle parking spaces are provided to help with the decrease in vehicular parking spaces. 3. Please note, exact location of street lights will be determined in the field. 4. Please note that any changes made to the plans that have not been requested by the City of College Station, must be explained in your next transmittal letter. LANDSCAPING 1. Please label existing and proposed street lights. Reviewed by: Jessica Bullock Date: 3/17/15 ENGINEERING COMMENTS NO. 2 1. (Original Comment) C1 — Show and label all easements on or adjacent to the site (include volume & page number). Label the existing 15-ft PUE adjacent to the property with volume and page number. 2. (Original Comment) C 1/C6 — Per Water Services, a 15-ft separation is required between the building and the water & sanitary sewer lines. The only exception to this is the sanitary sewer line adjacent to the southern property line, which may remain in its existing location. Additional pavement repair will likely be needed. Please verify that the sewer line has been visually inspected and there are no flows through the line. 3. (Original Comment) C2/C5 — Provide "Sidewalk Section at Tree Grates" details for sections where the tree is set back away from the back of curb and sections that are sidewalk only without the tree. The detail without the tree should still include the underdrain pipe and moisture barrier per the similar Site Design Standards detail. 4. (Original Comment) C8 — Provide more details for the detention pond including cross sections. It is unclear how water will actually enter the detention pond. Regarding Notes #1 & 2 pertaining to the detention pond, the structural drawings and stormwater piping into the pond are details that need to be included in the civil plan set. 5. (Original Comment) Water Report — The Fire Marshal requires that the actual fire flow test produce the necessary fire flow per the IFC. This fire flow cannot be based on a theoretical calculation of potential flowrate. FYI ... The Water Dept. is going to be running another simultaneous fire flow test this next week. We will forward results as soon as possible. 6. (Original Comment) Drainage Report — Please include a detail of the pond in the report and indicate how water will collected and routed to the detention pond. Details showing how the stormwater will be routed to the pond need to be provided in the drainage report and civil construction plans, not just the building plans. 7. (Original Comment) Drainage Report — Provide an analysis of the ponding in the parking area. Are any grate inlets/drains proposed in the parking area? 8. (Original Comment) FYI... Additional Development Permit Fee in the amount of 1 % of the total public infrastructure cost will be required. Based on the Engineer's Cost Estimate, the DP Fee balance is $1,117.97. 9. C3/C6 — Please provide additional details for the removal of the sanitary sewer line & repair of the manhole. (i.e. label linear footage of line to be removed; PVC, rubber boot, etc. needs to be completely removed from or cut out of the manhole; what type of concrete should fill the void in the manhole; specify how the hole should be filled and concrete smoothed inside and outside the mahole). 10. C10 — FYI... These are preliminary comments regarding Traffic Control, as Public Works is still reviewing the plan. 11. C10 — Where will the staging area and Iaydown yard be for this project? Were you still proposing to utilize all of Cherry St.? If so, this plan needs to reflect that. 12. C10 — Based on this plan, parking will need to be temporarily removed on one side of Boyett. This will also need to go to City Council for approval. 13. C10 — The intersection of Cherry/Boyett will need to be partially or completely closed at some point to install the storm sewer. Please provide traffic control for this scenario. 14. C10 — Note #9 references "appropriate signage" is going to be up at night. Should the appropriate signage be specified? 15. Gate Variance — How will visitors know that they do not have access before attempting to enter the garage? Is there enough space to add a bailout lane so that there isn't a backing maneuver on the street by one or more cars in the queue? 16. Gate Variance — How will the gate open/close? (i.e. swing gate, sliding gate, etc.) 17. Gate Variance — Where will the call box be located? 18. Gate Variance — The letter indicates that there will be visitor parking along Cherry St., however, parking is proposed to be removed in that location. Please revise letter. Reviewed by: Erika Bridges Date: 3/9/15 LEGAL NOTICE DATE TO BE PUBLISHED: MONDAY, MARCH 23, 2015 ONLY BILL TO: Brittany Caldwell City of College Station P.O. Box 9960 College Station, TX 77842 ---------------------------------------------------------------------------- NOTICE OF PUBLIC HEARING: The College Station City Council will hold a public hearing to consider parking removal along the south side of Cherry Street from Second Street to Boyett Street for the Second Street Apartment development. The hearing will be held in the Council Chambers of the College Station City Hall, 1101 Texas Avenue at the 7:00 p.m. meeting of the Council on Thursday, April 9, 2015. For additional information please contact Danielle Singh, the Project Manager, at 979.764.3570. Any request for sign interpretive services for the hearing impaired must be made 48 hours before the meeting. To make arrangements call 979.764.3541 or (TDD) 1.800.735.2989.