HomeMy WebLinkAboutWater Report Fire Flow Analysis & Water Service Report
for
Cherry Street Apartments
College Station, Texas
February 2015
Revised March 2015
Prepared By:
Schultz Engineering, LLC
TBPE Firm Registration No. 12327
2730 Longmire, Suite A
College Station, Texas 77845
979.764.3900 ! o�`k
* •le
•,o• .*
•
DEVEN L. DOYEN 14
:• 109835
r► �1 E :��Q`�
p3/2 ll
FIRM # 12327
SCHULTZ ENGINEERING, LLC
General Information
Location: The development includes Block 20, Lots 1-8, W.C. Boyett Estate Partition,
College Station, Texas. The project lots are located at the corner of Second
Street and Cherry Street and at the corner of Cherry Street and Boyett Street.
General Note: An 8"water line will connect to the existing 8"water line under the sidewalk on
Second Street and extend to the proposed building. The 8" water line will be
used for the fire line. Domestic and irrigation services will come off the 8"
water line to serve the building and irrigation. Two fire hydrants are required to
serve the project.The two existing fire hydrants will be used for hydrant flow.
Land Use: Residential—Multi Family
Design Criteria/Analysis
Primary Water Supply: Existing 8"water line in Second&Cherry Streets and existing 6"water line in
Boyett Street
Domestic Demand:
Fixture Units: 1281.6
Max.Demand Flow: 243 gpm-3"Water Meter
Fire Flow: Second Street Apartments is proposed to have a 177,233 sf building. The
building is proposed to be Type IIIA Construction per the International Building
Code. In accordance with Table B105.1 of the International Fire Code,the
minimum required fire hydrant flow is 6,000 gpm. The building is proposed to
be fully sprinkled;therefore the minimum required fire flow is reduced to 3,000
gpm.
Hydrants flowed at same time
Existing System Pressure Tests:(Representative of the Flows and Pressures in the area)—Exhibit A
Flow Hydrant:500 Boyett(A-053)
Flowrate: 1,190 gpm
Static Hydrant:309 College Main(A-046)
Static Pressure: 71 psi
Residual Pressure: 50 psi
Existing System Pressure Tests:(Representative of the Flows and Pressures in the area)—Exhibit B
Flow Hydrant: 404 Second(A-070)
Flowrate:2,241 gpm
Static Hydrant:309 College Main (A-046)
Static Pressure: 71 psi
Residual Pressure: 50 psi
Total Flowrate:3,431gpm
Exhibits: Exhibit A-Water System Flow Test Report
Exhibit B—Water Exhibit
Exhibit C—WaterCAD Analysis Summary
Water System Analysis: The existing system was modeled using the domestic demand and the
fire/domestic demand.The peak domestic demand is 243 and the fire domestic
flow required for this site is 3,243 gpm.The lowest pressures for domestic and
fire/domestic flow are 70.8 psi and 59.2 psi,respectfully.These pressures met
the residual pressure requirements of 20 psi for fire flow and 35 psi for domestic
flow.The maximum velocity is 9.79 ft/s under the fire/domestic scenario.
Conclusion
The existing system will provide the required water pressure and flowrate for
both domestic and fire protection demands.
Ex HTh h.
CiCo Heg:e Station Utilities
Reliable,Affordable, community Owned
Date test completed Wednesday March 18, 2015
Time completed 1:00 P.M.
Test completed by Justin Tamplin, Howard Mitchell
Witness Craig Jones
FLOW HYDRANT
Location 404 Second St. and 500 Boyett (FLOWED AT SAME TIME)
Nozzle size 4.5" on A-070 and the 2.5" on A-053
Hydrant number A-070 and A-053
Pitot reading in PSI 25psi on A-070 and 50psi on A-053
Flow in G.P.M. (2700gpm*0.83) on A-070 and the 1,190gpm on A-053 = 3,431 qpm
STATIC HYDRANT
Location 315 College Main
Hydrant number A-046
Static PSI 71
Residual PSI 50
Comments Requested
I
\1/4
\ 0
h N
i vim ism
ZL_M Z`—M— o so goo
SCALE IN FEET
••i--1\----
co
'\ I I
W-12
-* N
1
-4- \
w°
LJ '
co
>-
f---
I I
1�i1 Ik L�
D
U col
�.�
< N
c0 I I
3 U 3
W
= W
U it
I-
*(n
—W-8 I
co
U_
E
1—
Q
LZ
1
N �
I
co
I v
1
r��_ r 6k N
—M 1
�O
r:
9—M 8—M----_
--_____________i
v^'GhUItZ En! SCALE EXHIBIT
2]30 L VERTICAL
97976XHIBI1 HORIZONTAL 1'=100' )
SURVEYED DESIGNED n
MI£ STRONG OLD
PLOTT/NOSCALE 1,1
Exhibit C
WaterCAD Analysis Summary
Pipe Analysis- Domestic Demand
Pipe Hazen- Flow Velocity
Length (ft) Size (in) Material
Number Williams C (gpm) (ft/s)
P-1 _ 12 8 PVC 150 36 0.23
P-2 201 8 PVC _ 150 36 0.23
P-3 235 8 PVC _ 150 -114 0.73
P-4 261 8 PVC 150 -114 0.73
P-5 576 12 PVC 150 -114 0.32
P-6 479 12 PVC 150 129 0.37
P-7 310 12 PVC 150 129 0.37
P-8 309 12 PVC 150 36 _ 0.1
P-9 52 8 PVC 150 36 0.23
P-10 796 6 PVC 150 36 0.4
P-11 56 6 PVC 150 36 0.4
P-12 425 8 PVC 150 93 0.6
P-13 334 8 PVC 150 93 0.6
P-14 36 8 PVC 150 93 0.6
P-15 _ 67 8 PVC 150 -150 0.96
P-RES 17 12 PVC 150 243 0.69
WaterCAD Analysis Summary
Junction Analysis- Domestic Demand
Junction
Junction Elevation Demand Pressure
(gpm) (psi)
J-1 342 0 74.2
J-2 342 0 74.2
J-3 343 0 73.8
J-4 341.5 0 74.5
1-5 341 0 74.7
J-6 350 0 70.8
J-7 350 0 70.8
1-8 346.5 0 72.3
J-9 344 0 73.4
J-10 344.5 0 73.2
J-11 343 0 73.8
1-12 348.5 0 71.4
1-13 346 0 72.5
J-14 346 243 72.5
Exhibit C
WaterCAD Analysis Summary
Pipe Analysis- Fire Flow Demand (FH)
Pipe Length (ft) Size (in) Material Hazen- Flow Velocity
Number Williams C (gpm) (ft/s)
P-1 12 8 PVC 150 545 3.48
P-2 201 8 PVC 150 -955 6.09
P-3 235 8 PVC 150 -1,534 9.79
P-4 261 8 PVC 150 -1,534 9.79
P-5 576 12 PVC 150 -1,534 4.35
P-6 479 12 PVC 150 1,709 4.85
P-7 310 12 PVC 150 1,709 4.85
P-8 309 12 PVC 150 545 1.55
P-9 52 ` 8 PVC 150 545 3.48
P-10 796 6 PVC 150 545 6.19
P-11 56 6 PVC 150 545 6.19
P-12 425 8 PVC 150 1,164 7.43
P-13 334 8 PVC 150 1,164 7.43
P-14 36 8 PVC 150 -336 2.15
P-15 67 8 PVC 150 -579 3.7
P-RES 17 12 PVC 150 3,243 9.2
WaterCAD Analysis Summary
Junction Analysis- Fire Flow Demand (FH)
Junction
Junction Elevation
Demand Pressure
(gpm) (psi)
J-1 342 0 60
J-2 342 1,500 60
J-3 343 0 60.7
J-4 341.5 0 64.5
J-5 341 0 68.2
J-6 350 0 65.3
J-7 350 0 64.3
J-8 346.5 0 65.1
J-9 344 0 66.1
J-10 344.5 0 65.7
J-11 343 0 60
J-12 348.5 0 60.8
J-13 346 1,500 59.2
J-14 346 243 59.2
a
,()
Fire Flow Analysis & Water Service Report
for
Cherry Street Apartments
College Station, Texas
February 2015
Prepared By:
Schultz Engineering, LLC
TBPE Firm Registration No. 12327
2730 Longmire, Suite A
College Station, Texas 77845
979.764.3900 #���!''Ni
O��
N '• * 46
• DEVEN L. DOYEN 0
It.WOL5 4 r we. a e ...1'09855
�2 abler CLLt ada+c, ..'` •• 1C
r1�_ .. � 3
-c1C�W - f• FIRM # 12327
AreSCHULTZ ENGINEERING, LLC
- pit tti/15 'b --I-el I &(
wCC-LA S fF u t‘ t
I sl ov. cAuCu,(ascior,?
General Information
Location: The development includes Block 20, Lots 1-8, W.C. Boyett Estate Partition,
College Station, Texas. The project lots are located at the corner of Second
Street and Cherry Street and at the corner of Cherry Street and Boyett Street.
General Note: An 8"water line will connect to the existing 8"water line under the sidewalk on
Second Street and extend to the proposed building. The 8" water line will be
used for the fire line. Domestic and irrigation services will come off the 8"
water line to serve the building and irrigation. Two fire hydrants are required to
serve the project.The two existing fire hydrants will be used for hydrant flow.
Land Use: Residential—Multi Family
Design Criteria/Analysis
Primary Water Supply: Existing 8"water line in Second&Cherry Streets and existing 6"water line in
Boyett Street
Domestic Demand:
Fixture Units: 1281.6
Max.Demand Flow: 243 gpm-3"Water Meter
Fire Flow: Second Street Apartments is proposed to have a 177,233 sf building. The
building is proposed to be Type IIIA Construction per the International Building
Code. In accordance with Table B105.1 of the International Fire Code,the
minimum required fire hydrant flow is 6,000 gpm. The building is proposed to
be fully sprinlded;therefore the minimum required fire flow is reduced to 3,000
gpm.
Existing System Pressure Tests:(Representative of the Flows and Pressures in the area)—Exhibit A
Flow Hydrant:500 Boyett(A-053)
Flowrate: 1,300 gpm
Static Hydrant:309 College Main (A-046)
Static Pressure: 72 psi
Residual Pressure: 65 psi
Existing System Pressure Tests:(Representative of the Flows and Pressures in the area)—Exhibit B
Flow Hydrant:404 Second(A-070)
Flowrate: 1,275 gpm
Static Hydrant:309 College Main(A-046)
Static Pressure: 72 psi
Residual Pressure: 65 psi
Exhibits: Exhibit A-Water System Flow Test Report
Exhibit B—Water Exhibit
Exhibit C—WaterCAD Analysis Summary
Water System Analysis: The existing system was modeled using the domestic demand and the
fire/domestic demand.The peak domestic demand is 243 and the fire domestic
flow required for this site is 3,243 gpm.The lowest pressures for domestic and
fire/domestic flow are 71.5 psi and 26.2 psi,respectfully.These pressures met
the residual pressure requirements of 20 psi for fire flow and 35 psi for domestic
flow.The maximum velocity is 9.79 ft/s under the fire/domestic scenario.
Conclusion
The existing system will provide the required water pressure and flowrate for
both domestic and fire protection demands.
p , ,
' EXHIBIT A
ClCol0
lege Station Utilities
Reliable,Affordable, community Owned
Date test completed Monday December 22, 2014
Time completed 9:30 A.M.
Test completed by Eugene Marshall
Witness Justin Tamplin
FLOW HYDRANT
Location 500 Boyett
Nozzle size 2.5
Hydrant number A-053
Pitot reading in PSI 60
Flow in G.P.M. 1300
STATIC HYDRANT
Location 309 College Main
Hydrant number A-046
Static PSI 72
Residual PSI 65
Comments Requested
EXHIBIT B
elCit
College Stations Utilities
Reliable,Affordable, community Owned
Date test completed Monday December 22, 2014
Time completed 9:30 A.M.
Test completed by Eugene Marshall
Witness Justin Tamplin
FLOW HYDRANT
Location 404 Second
Nozzle size 2.5
Hydrant number A-070
Pitot reading in PSI 57
Flow in G.P.M. 1275
STATIC HYDRANT
Location 309 College Main
Hydrant number A-046
Static PSI 72
Residual PSI 65
Comments Requested
Exhibit C
WaterCAD Analysis Summary
Pipe Analysis- Domestic Demand
Pipe Hazen- Flow Velocity
Number Length (ft) Size (in) Material Williams C (gpm) (ft/s)
P-1 12 8 PVC 150 36 0.23
P-2 201 8 PVC 150 36 0.23
P-3 235 8 PVC 150 -114 0.73
P-4 261 8 PVC 150 -114 0.73
P-5 576 12 PVC 150 -114 0.32
P-6 479 12 PVC 150 129 0.37
P-7 310 12 PVC 150 129 0.37
P-8 309 12 PVC 150 36 0.1
P-9 52 8 PVC 150 36 0.23
P-10 796 6 PVC 150 36 0.4
P-11 56 6 PVC 150 36 0.4
P-12 425 8 PVC 150 93 0.6
P-13 334 8 PVC 150 93 0.6
P-14 36 8 PVC 150 93 0.6
P-15 67 8 PVC 150 -150 0.96
P-RES 17 12 PVC 150 243 0.69
WaterCAD Analysis Summary
Junction Analysis- Domestic Demand
Junction
Junction Elevation
Demand Pressure
(gpm) (psi)
1-1 342 0 74.9
J-2 342 0 74.9
J-3 343 0 74.5
J-4 341.5 0 75.2
J-5 341 0 75.4
J-6 350 0 71.5
J-7 350 0 71.5
J-8 346.5 0 73
J-9 344 0 74.1
J-10 344.5 0 73.9
J-11 343 0 74.5_
J-12 348.5 0 72.1
J-13 346 0 73.2
J-14 346 243 73.2
Exhibit C
WaterCAD Analysis Summary
Pipe Analysis- Fire Flow Demand (FH)
Pipe Hazen- Flow Velocity
Number Length (ft) Size (in) Material Williams C (gpm) (ft/s)
P-1 12 8 PVC 150 545 3.48
P-2 201 8 PVC 150 -955 6.09
P-3 235 8 PVC 150 -1,534 9.79
P-4 261 8 PVC 150 -1,534 9.79
P-5 576 12 PVC 150 -1,534 4.35
P-6 479 12 PVC 150 1,709 4.85
P-7 310 12 PVC 150 1,709 4.85
P-8 309 12 PVC 150 545 1.55
P-9 52 8 PVC 150 545 3.48
P-10 796 6 PVC 150 545 6.19
P-11 56 6 PVC 150 545 6.19
P-12 425 8 PVC 150 1,164 7.43
P-13 334 8 PVC 150 1,164 7.43
P-14 36 8 PVC 150 -336 2.15
P-15 67 8 PVC 150 -579 3.7 _
P-RES 17 12 PVC 150 3,243 9.2
WaterCAD Analysis Summary
Junction Analysis- Fire Flow Demand (FH)
Junction
Junction Elevation
Demand Pressure
(gpm) (psi)
J-1 342 0 27
J-2 342 1,500 27
J-3 _ 343 0 27.7
J-4 _ 341.5 0 31.5
J-5 341 0 35.2
J-6 350 0 32.4_
J-7 350 0 31.3
J-8 346.5 0 32.1
J-9 344 0 33.1
J-10 344.5 0 32.8
J-11 343 0 27.1
J-12 348.5 0 27.8
J-13 346 1,500 26.2
J-14 346 243 26.3
Summary of Calculations
Domestic Demand Pressure Min. 71.5
Velocity Max 0.96
Pressure Min. 26.2
Domestic Demand & FH Velocity Max 9.79