HomeMy WebLinkAboutFire Flow Letter A&M Consolidated Gym Expansion Fire Flow Letter March 4, 2015 Background College Station Independent School District is constructing a gym expansion on the A&M Consolidated High School campus.This expansion consists of an addition to the existing gymnasium along with additional men's and women's restrooms and a new dance gym. A site plan showing this expansion is attached as Exhibit 1. Fire Flow Area& Required Fire Flow Per the 2012 International Fire Code (IFC) Section B104— Fire Flow Calculation Area, the High School currently has a maximum fire flow area of 145,024 square feet. With the new gym expansion that area increases to 154,700 square feet or an increase in fire flow area of 9,767 square feet. The building type for the High School is Type IB. According to Table B105.1 the required fire flow for 145,024 square feet protected by a fire sprinkler system is 4,000 gpm and with a 50% reduction would be 2,000 gpm. The required fire flow for 154,700 is 4,250 gpm with a 50% reduction would be 2,125 gpm, or an increase of 125 gpm from the fire flow requirement for this existing structure. Required Number of Fire Hydrants According to Section C103 of the IFC both of these fire flows require only 2 hydrants available for this structure. If 2 hydrants are used for this area of the building, each hydrant would have to flow 1,063 gpm. If 3 hydrants are used for this area of the building, each hydrant would have to flow 709 gpm. As seen on Exhibit 2 there are 3 fire hydrants in proximity to this new expansion. Fire Flow Model To investigate the ability for the existing water supply system to provide this required fire flow we ran the current City of College Station water supply model under average day conditions with fire flows of 1063 gpm on nodes 1540 and 1567 in the model. A graphic representation of the model layout and these nodes is shown in Exhibit 2. The results of placing this fire flow on these 2 hydrants nodes can be seen in Exhibit 3. As seen,the existing system can accommodate the fire flow required for this building expansion with meeting a minimum pressure of 20psi and a maximum line velocity at or below 12 fps. .0107to, OF re IN st If ,�►- + s,� I * /\ VERONICA J.B.MORGAN 77689 jai l�.1 SFS FG,STE?� &.4,r 4+.) vo �t�S/ONAI.E.— I "' ` -/ �OAitF-1443 i EXHIBIT 2 MikeURBAN Node & Pipe Identifiers Description: Select MikeURBAN Node & Pipe Locations %tk _ VN. . ',/ \ ,, / N IIItrltl ifr tsMses ',,,1 56i \ / 1572 KI 9!• "7',.. n` atm i / 5 ttt• I 'ytp0 aJ t/ ..\.%1713 \ ^ A&M Consolidated High School Gym Expansion Exhibit 2