HomeMy WebLinkAboutStaff Review 1 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM October 22, 2008 TO: Jeff Cantrell via email: jeffcantre1150@yahoo.com FROM: Lauren A. Hovde, Staff Planner SUBJECT: CONVENTION AND VISTORS BUREAU (NRA) NRA Review 2 Staff reviewed the above-mentioned Non-Residential Architectural plans as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised set of elevation drawings If there are comments that you are not addressing with the revised elevations, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments pc: Convention and Visitors Bureau via email: Shannon@bcscvb.org Case file #08-00500240 STAFF REVIEW COMMENTS NO. 1 CONVENTION AND VISTORS BUREAU (NRA) — NRA Review 08-00500240 PLANNING /The horizontal line of a flat roof along any façade facing a right-of-way shall vary by a minimum of two feet (2') up or down so that no more than 66% of the roofline is on the same elevation. If this is to be considered a pad site, all facades are considered to be facing a right-of-way. C1Lle nn E: oL,Q l - } re4 aie.r 2. Façade articulation (wall plane projection dr recession of four feet (4')) is required on any facade facing a right-of-way. No more than 33% of any façade facing a right-of-way shall be on the same continuous geometric plane. Gienn‘5►'buor n t rt- `4' ' 3. The south (front) and west facades meet minimum standards for architectural elements. 4. The east and north (back) façades are required to have minimum of four architectural elements to meet minimum standards found in Article 7.9 of the UDO. Each façade is showing four elements, however, a single element type can not be used to satisfy this requirement. The applicant does have the option to seek a variance, and provide alternate architectural elements for the DRB to consider. 5. Please show the total square footage of the building on the NRA sheet. 6. A note must be added that states, "All roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance." 7. Please add a note stating that it is part of the Chimney Hill Retail Plaza building plot. 8. FYI...All signage is permitted separately. Reviewed by: Lauren A. Hovde, Staff Planner Date: October 2, 2008 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.76(rm.% 4.3496 QTY OF COLLEGE STATION MEMORANDUM October 2, 2008 TO: Jeff Cantrell via email: jeffcantre1150@yahoo.com FROM: Lauren A. Hovde, Staff Planner SUBJECT: CONVENTION AND VISTORS BUREAU (NRA) NRA Review Staff reviewed the above-mentioned Non-Residential Architectural plans as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised set of elevation drawings If there are comments that you are not addressing with the revised elevations, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments pc: Convention and Visitors Bureau via email: tiffanyc@bcscvb.org Case file #08-00500240 0 STAFF REVIEW COMMENTS NO. 1 CONVENTION AND VISTORS BUREAU (NRA) — NRA Review 08-00500240 PLANNING 1.✓Because this building is part of a building plot larger than 5,000 square feet, the use of 100% EIFS is not permitted by the Non-Residential Architectural Standards found in Article 7.9 of the Unified Development Ordinance. A maximum of 75% EIFS is allowed. 2.-Since this building plot is over 50,000 square feet, the north, south, and east elevations, which face a right-of way, must have a minimum of 25% stone, brick, marble, granite, or tile. The west elevation, which is not facing a right-of-way, should have a minimum of 10% stone, brick, marble, granite, or tile. 3.✓Each façade should have a materials legend that shows the material and color choice from the approved color palette, along with the square footage and percent of the color/material being utilized for that facade. Please see Article 7.9-3.0 for an example. This legend should also show the total square footage and percent of the façade that is taken up by doors and windows. ® The horizontal line of a flat roof along any façade facing a right-of-way shall vary by a minimum of two feet (2') up or down so that no more than 66% of the roofline is on the same elevation. 99. Façade articulation (wall plane projection or recession of four feet (4')) is required on any façade facing a right-of-way. No more than 33% of any façade facing a right-of-way shall be on the same continuous geometric plane. 67The south (front) and west facades meet minimum standards for architectural elements. D. The east façade needs a minimum of four additional architectural elements to meet minimum standards found in Article 7.9 of the UDO. The north (back) façade needs a minimum of four additional architectural elements to meet minimum standards found in Article 7.9 of the UDO. 9./Please provide the color and material of the canopies in a note. The color must be chosen from the approved color palette. Accent colors may be used on no greater that 10% of the façade on which the accent color is applied. 10.Please show the legal description of this property, the total square footage of the building, ✓✓and the CVB phone number on the NRA sheet. 11. A note must be added that states, "All roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance." 12/A graphic representation or description of the existing buildings in the building plot must be provided so as to determine the harmonious nature of the building facades. 1.a<Please add a note to the NRA sheet that this property is zoned C-1 and that it is part of the Overlay District along University Drive. U. Please add a note stating that it is part of the Chimney Hill Retail Plaza building plot. Reviewed by: Lauren A. Hovde, Staff Planner Date: October 2, 2008 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM October 22, 2008 TO: Jeff Cantrell via email: jeffcantre1150@yahoo.com FROM: Lauren A. Hovde, Staff Planner SUBJECT: CONVENTION AND VISTORS BUREAU (NRA) NRA Review 2 Staff reviewed the above-mentioned Non-Residential Architectural plans as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised set of elevation drawings If there are comments that you are not addressing with the revised elevations, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments pc: Convention and Visitors Bureau via email: Shannon@bcscvb.org Case file #08-00500240 STAFF REVIEW COMMENTS NO. 1 CONVENTION AND VISTORS BUREAU (NRA) — NRA Review 08-00500240 PLANNING 1. The horizontal line of a flat roof along any façade facing a right-of-way shall vary by a minimum of two feet (2') up or down so that no more than 66% of the roofline is on the same elevation. If this is to be considered a pad site, all facades are considered to be facing a right-of-way. 2. Façade articulation (wall plane projection or recession of four feet (4')) is required on any façade facing a right-of-way. No more than 33% of any façade facing a right-of-way shall be on the same continuous geometric plane. 3. The south (front) and west facades meet minimum standards for architectural elements. 4. The east and north (back) façades are required to have minimum of four architectural elements to meet minimum standards found in Article 7.9 of the UDO. Each façade is showing four elements, however, a single element type can not be used to satisfy this requirement. The applicant does have the option to seek a variance, and provide alternate architectural elements for the DRB to consider. 5. Please show the total square footage of the building on the NRA sheet. 6. A note must be added that states, "All roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance." 7. Please add a note stating that it is part of the Chimney Hill Retail Plaza building plot. 8. FYI...All signage is permitted separately. Reviewed by: Lauren A. Hovde, Staff Planner Date: October 2, 2008