HomeMy WebLinkAboutCorrespondence 1 1101 Texas Avenue, P.O. Box 9960
Orff
College Station, Texas 77842
Phone 979.764.3570/ Fax 979.764.3496
CITY OF COLLEGE STATION
MEMORANDUM
September 29, 2008
TO: Rod Booze and Krystina Gnuechtel via fax: 817-226-1919
FROM: Lauren A. Hovde, Staff Planner
SUBJECT: ST JOSEPH OUTPATIENT CENTER (NRA) NRA Review
Staff reviewed the above-mentioned Non-Residential Architectural plans as requested. The
following page is a list of staff review comments detailing items that need to be addressed.
Please address the comments and submit the following information for further staff review:
One (1) revised set of elevation drawings
If there are comments that you are not addressing with the revised elevations, please attach a
letter explaining the details. If you have any questions or need additional information, please call
me at 979.764.3570.
Attachments: Staff review comments
pc: David Hall via fax: 979-776-5359
Case file #08-00500230
fn
K !gyp
Oil 11
Ascension maai0
atii
��
Group U .�
Architects Transmittal
Attention: Jason Schubert/ Lauren Hovde From: Krystina Gnuechtel
do City of College Station,
Building Planning
Address: 1101 Texas Ave. AGA#: 2008-035
College Station, TX 77840
Phone: 979-764-3754
Date: 10-17-08
Subject: St. Joseph EDI
Copies to:
We Transmit herewith items listed below:
Via: [Mail ❑ Fax ['Courier ®Overnight
#of Copies: Description:
1 Sets of drawings and comments
Purpose: ®Your Use ❑Your Records ['Your Comment
['Requested Prints ['Returned ❑For Bids Due
on 1/1/01
Remarks:
Architecture Planning Interior Design
1250 E.Copeland Rd.,Suite 500
Arlington,Texas 76011
Tel 817.226.1917
fax 817.226.1919
wwwascens iongroup.biz
Scension
Group
rchitects,ur
October 16,2008
Re:St.Joseph Health System,Outpatient/EDI Center-SH 6 South
Attn: Jason Schubert/Lauren Hovde
Plans Examiner
I have included the comments from the 10/06/08 correspondence with AGA's responses below each line item.
PLANNING
1. The date of signing was not included on the first page of the application. Resubmit a completed
first page.
Please see attached.
2. Place a note on the elevations that this property is part of a Building Plot with Lot 6 and future
Lots 9, 10, 11, and 12 and will meet the requirements for non-residential projects that exceed
150,000 square feet. Therefore,revise the note attached to the application regarding building plots
as well.
Added. Please see A3.01 clouded under General Notes.
3. The legal address and owner's name,address,and telephone number should be added to
title block.
Added.Please see title block on Sheet A3.01.
4. Please added the Sherman Williams color selections to Sheet A3.01.
Added.Please see revision clouds on Sheet A3.01.
5. No more than 33%of a facade can be on the same plane if facing a right-of-way.This applies to
the north and south elevations.The north elevation will be considered as facing a right-of-way due
to the future construction of Lakeway Drive.
Please see attached A3.01 and A1.01 for revisions.
6. No more than 66%of the roofline may be at the same elevation for the north and south elevations
Please see attached A3.01
7. Please add a note that all signage will be permitted separately.
Added.Please reference clouded general notes sheet A3.01.
8. The north and elevations must have a minimum of 50%stone.
Architecture Planning Interior Design
1250 East Copeland Road,Suite 500
Arlington,Texas 76011
tel 817.226.1917
fax 817.226.1919
www.ascensiongroup.biz
A' scension
Group
• rchitects,ur
Please see clouded revisions on sheet A3.01.
9. Please provide the material and color of the roof,canopies,and awnings.
Please see clouded revisions on sheet A3.01for the metal canopies,roof,and awnings as well as
included sample. This is a customer color and will match the exsiting St.Joseph Outpatient
Cente,but we could nto obtain exact custom color for review.We will submit sample from
custom color selection from General Contractor for review before installation/erection.
10. A note must be added that states,"All roof and ground-mounted mechanical equipment shall be
screened from view or isolated so as not to be visible from any public right-of-way or residential
district within 150'of the subject lot,measured from a point five feet above grade. Such screening
shall be coordinated with the building architecture and scale to maintain a unified appearance."
Added.Please see revision clouds on Sheet A3.01.
11. The east elevation meets minimum standards for achitectural elements found UDO
No response needed.
12. The west elevation does not meet minimum standards for architectural elements found in UDO
Article 7.9.Each half of the building should have at least 2 approved architectural elements.This
elevation is lacking two elements total.
Please see attached A3.01
13. The south elevation does not meet minimum standards for architectural elements found in UDO
Article 7.9. Each third of the building should have at least 2 approved architectural elements.This
elevation is lacking three elements total.
Please see attached A3.01
14. The north elevation does not meet minimum standards for architectural elements found in UDO
Article 7.9.Each third of the building should have at least 2 approved architectural elements.This
elevation is lacking two elements total.
Please see attached A3.01
Attached are three sets of plans addressing the sheets that correspond to each issue as requsted. Please do not
hesitate to contact me directly if there are any questions or concerns.
Regards,
Krystina Gnuechtel
401,
2191,04
Architecture Planning e 'or Design
1250 East Copeland Road, uite 500
Arlington,Texas 76011
tel 817.226.1917
fax 817.226.1919
www.ascensiongroup.biz
wrs.1% 1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570/ Fax 979.764.3496
CITY OF COLLEGE STATION
MEMORANDUM
November 3, 2008
TO: Rod Booze, Ascension Group Architects, via rbooze(a@ascensiongroup.biz
FROM: Jason Schubert, Staff Planner
SUBJECT: ST JOSEPH OUTPATIENT CENTER (NRA)— NRA Review
Staff reviewed the above-mentioned revised Non-Residential Architectural plans as requested.
The following page is a list of staff review comments detailing items that need to be addressed.
Please address the comments and submit the following information for further staff review:
One (1) revised set of elevation drawings
If there are comments that you are not addressing with the revised elevations, please attach a
letter explaining the details. If you have any questions or need additional information, please call
me at 979.764.3570.
Attachments: Staff review comments
pc: David Hall, St. Joseph Health System, via dhall a(�,st-ioseph.orq
Krystina Gnuechtel, Ascension Group Architects, via fax 817-226-1919
Case file#08-00500230
tOkek-
iiiiAscension 6C)
Group
Architects Transmittal
Attention: Jason Schubert From: Krystina Gnuechtel
do City of College Station,
Building Planning
Address: 1101 Texas Ave. AGA#: 2008-035
College Station, TX 77840
Phone: 979-764-3754
Date: 11-07-08
Subject: St. Joseph EDI
Copies to:
We Transmit herewith items listed below:
Via: ❑Mail [' Fax ❑Courier ®Overnight
# of Copies: Description:
1 Sets of drawings and comments
Purpose: ❑Your Use ['Your Records Your Comment
❑Requested Prints ❑Returned ❑Four Bids 1 Due
Remarks:
Architecture Planning Interior Design
1250 E.Copeland Rd.,Suite 500
Arlington,Texas 76011
Tel 817.226.1917
fax 817.226.1919
wwwascens iongroup.biz
_scension
Group
.4A
rchitects,up
November 7,2008
Re:St.Joseph Health System,Outpatient/EDI Center-SH 6 South
Attn: Jason Schubert
Plans Examiner
I have included the comments from the 11/03/08 correspondence with AGA's responses below each line item.
PLANNING
1. The material percentages provided are not correct and/or do not add to 100%per facade.When
calculating area,windows and doors are included as part of the total percentage.However,area
such as the screening walls on the roof and other area that are not part of the facada may be
excluded.Please revise,noting that the north and south elevations are to have a minimum of 50%
stone.
Please see clouded revisions on sheet A3.01. W have added more stone to both the north and
south elevations so that we meet the 50%requirement.
Attached is one set of elevations addressing each issue as requsted. Please do not hesitate to contact me directly if
there are any questions or concerns.