HomeMy WebLinkAboutStaff Comments (irifil5111111111111 CITY OF COLLEGE STATION Planning cr Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM September 6, 2007 TO: Natalie Ruiz,AICP, IPS Group, via Nataliegipsgroup.us FROM: Jeffrey Missal, P&DS SUBJECT: Fish Daddy's - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the attached comments and submit the following information for further staff review: Seven (7) complete sets of building construction documents for the proposed development with two additional revised site and one additional landscaping plans attached; If you have any questions or need additional information,please call me at 979-764-3570. Attachments: Staff review comments cc: Michael F. Twitchell, L.P., via fax 214-599-0583 John Welsh,Maroon City Partners II, via fax 979-485-0884 Case file #06-00500153 ENGINEERING COMMENTS NO. 1 1. Add fire suppression line and appurtenances as constructed to the Site Plan. Reviewed by: Carol Cotter Date: September 5, 2007 Home of Texas A&M University 1101 Texas Avenue, P.O. Box 9960 OlffCollege Station, Texas 77842 Phone 979.764.35701 Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM June 18, 2007 TO: Natalie Ruiz, AICP, IPS Group, via Natalieipsqroup.us FROM: Jason Schubert, Staff Planner SUBJECT: FISH DADDY'S (SP) — Color Elevations Staff reviewed the above-mentioned elevations and reply comments as requested. Below is a list of staff review comments detailing items that need to be addressed. Staff Review Comments: 1. No further comments regarding the building elevations. 2. Only 5 additional offsite parking spaces would be required for the use of the Fish Daddy's Main Patio as an outdoor seating area. There have been 83 spaces provided on site and 88 spaces would be required (5,282+438= 5,720/65 = 88 spaces). 3. The parking calculations listed for the Cheddar's restaurant differ from the approved site plan. The approved site plan states that 117 spaces are required (7,575/65=117) while 129 spaces were provided. In either case, it does not appear that the outdoor patio area was considered when calculating the required number of parking spaces. When including the Cheddar's patio, the restaurant does not have extra parking spaces to share in a parking agreement with Fish Daddy's. Unless resolved in some other manner, the Main Patio in front of Fish Daddy's cannot be utilized for outdoor seating. If you have any questions or need additional information, please call me at 979.764.3570. pc: Michael F. Twichell, L.P., via fax 214.599.0583 John Welsh, Maroon City Partners II, LTD, via fax 979.485.0884 Case file #06-00500153 �1 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM June 4, 2007 TO: Jane Kee, AICP, IPS Group, via ianeipsgroup.us FROM: Jason Schubert, Staff Planner SUBJECT: FISH DADDY'S (SP)— Color Elevations Staff reviewed the above-mentioned elevations as requested. Below is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised set of color building elevations Staff Review Comments: 1. The Non-residential Architecture Standards (UDO Section 7.9) limit the amount of Stucco/EIFS, etc to 75% on a façade. Please revise the North elevation to fit this limitation. 2. In the revised building permit application (submitted back in February but not yet approved), the main patio area in front of the South elevation illustrates outdoor seating. As per General Site Plan Note 5 on the approved site plan, if any outdoor seating is added, additional parking will be required. Please account for this. If you have any questions or need additional information, please call me at 979.764.3570. pc: VMichael F. Twichell, L.P., via fax 214.599.0583 John Welsh, Maroon City Partners II, LTD, via fax 979.485.0884 Case file #06-00500153 (*ffill11111111 CITY OF COLLEGE STATION Planning d Development Services 1101 Texas Avenue,P.O. Box 9960 College Station,Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM August 11,2006 TO: Michael Twichell,LP-Carl Lyon,Via fax 214.599.0583 FROM: Jennifer Reeves,Project Manager SUBJECT: FISH DADDY'S (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for stamping: Seven (7) complete sets of cons • -::on documents for the proposed development with - _ - ' - . .- . .scaping plans attached (one set will be returned to you, please sub..: ...'tional copies i .. nt more than one approved set) Two (2) revised site plans One (1) landscaping plan One (1) 11x17 grading and erosion control plan Easement Dedication Sheet and required documents(please allow 4 weeks to process). If there are comments that you are not addressing with the revised site plan,please attach a letter explaining the details. If you have any questions or need additional information,please call me at 764-3570. Attachments: Staff review comments cc: Maroon City partners II., LTD. _John Welsh, via fax 979.485.0884 I.P.S. Group, via email www.IPSGroup.us Case file#06-00500153 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 1 of 2 (*,111114 CITY OF COLLEGE STATION Planning 6Development Services 1101 Texas Avenue,P.O. Box 9960 College Station,Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM July 21, 2006 TO: Michael Twichell, LP-Carl Lyon, Via fax 214.599.0583 FROM: Jennifer Reeves, Project Manager SUBJECT: FISH DADDY'S (SP)-Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised site and landscaping plan. One(1) 11x17 grading and erosion control plan Easement Dedication Sheet and required documents (please allow 4 weeks to process). Public Utility Easement Abandonment application and required documents (please allow 6-8 weeks to process). Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information,please call me at 979.764.3570. Attachments: Staff review comments cc: Maroon City partners II., LTD._John Welsh, via fax 979.485.0884 Case file#06-00500153 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. P. (11*,441111111 CITY OF COJ I.FGE STATION S , Planning efr Development Service 1101 Texas Avenue,P.O. Box 9960 College Station,Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM June 21,2006 TO: Michael F. Twichell,LP Via fax 214.599.0583 FROM: Jennifer Reeves,Project Manager SUBJECT: FISH DADDY'S- Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Eleven (11) folded site plans One (1) folded landscape plan One (1) copy of the building elevations If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information,please call me at 979.764.3570. Case file#06-00500133 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: FISH DADDY'S (SP)—06-00500153 PLANNING Please be aware that a portion of the building and the dumpster enclosure are being shown in the existing 15-foot PUE. The building and dumpster enclosure will need to shifted or the easement must be abandoned. Structures, including dumpster enclosures are not permitted in any easements. 4. An easement abandonment application and all supporting documents will need to be submitted to for processing to be placed on a City Council agenda for approval. /i. An easement dedication sheet will also need to be submitted with all supporting documents. (0. Please be aware that staff review comments#2&3 above will need to be fully addressed prior to site plan approval. (The abandonment cannot be approved until the electric lines are relocated and a replacement PUE dedicated. As submitted, the Site Plan cannot be approved until PUE is abandoned.) (5. Please show the nearest existing fire hydrant for this site, if it is not located on this site then please show the distance and direction of the nearest hydrant. (6. Please identify the water meter on the site plan. 7. Under the General Site Notes on the site plan, #3 states:"all existing parking spaces are 9'x8' /3. "Please adjust to 9'x18'. The dumpster opening only appears to be 10-feet. Sanitation needs at least a 12-foot clear opening to access the dumpster. Please adjust accordingly. ,/9. The interior parking island along University Drive does not currently exist. Please identify this as proposed on the site plan. y.10. Please provide a note on the site plan stating: "That in the event that seating is added to any outside portion of this building, additional parking will be required and a new parking plan will need to be provided for review". rDSCAPING/STREETSCAPING/BUFFER Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. 2. Please identify the existing canopy and non-canopy trees with specie name as well as the existing shrubs (height & species) on the landscape plan with points accrued. (Possibly bubble the proposed plantings). It appears from a site visit that what is being shown as existing is not actually there. 113. Please provide streetscape legend with calculations (points required - points provided, see i4. Section 7.5.D streetscape requirements). Please do not reference old landscape plan. This project must stand on it's on. The landscape plan will need to show the above information that was requested (comments 13 & 14)on it. \i . Please provide a note on the landscape plan stating: "An irrigation plan is required to be submitted for review and approval prior to Certificate of Occupancy". If the same irrigation system is being used, please provide a copy of the plan with any changes. Reviewed by: Jennifer Reeves Date: July 13, 2006 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. P. STAFF REVIEW COMMENTS NO. 1 Project: FISH DADDY'S—06-00500133 (Due to the lack of information submitted staff could not provide a comprehensive review.) Below is a list of comments from a cursory review from Staff with the information that was turned in. (Please be aware the following comments would not be required if the site was not being altered. If the building was the only thing being changed then the Non-Residential Architectural Standards would be the only requirement) PLANNING 1. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot,measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. 2. This project does involve site changes, therefore will be required to turn in a site plan application for review of the site, landscape and elevations of the proposed building. (Application faxed to Michael Twichell 6/21/06). 3. Parking for a restaurant without a drive through is 1/65., with 5,590 square feet this will require 86 parking spaces. Currently this site would not meet the parking requirements. Please provide a parking legend on the site plan. (Parking required and parking provided) 4. Please show all existing and proposed utilities. 5. Please show all existing and proposed P.U.E's. 6. Please provide curbing and parking detail for revised parking areas. 7. Please provide a dumpster detail on the site plan. Dumpster pads are required to be a minimum of 12'x12'. Please be aware that if bollards are being placed in the dumpster enclosure they are required to have 12-feet of clearance on the width and depth. (Gates are required) 8. Please provide colored elevations with a legend providing colors, materials and percentages of materials for each facade per Section 7.9 Non-Residential Architectural Standards. 9. The correct zoning for the subject property is C-1 General Commercial located in the 0-V Corridor Overlay District. Please provide the correct zoning on the site plan. 10. Please provide building setbacks. 11. A 180 square foot end island is required at the end of every parking row. It appears that the parking space next the dumptser is not 180-square feet. 12. What is being proposed next to the dumpster 13. The drive going into the shopping center is not Glenhaven Drive, it is a private drive. Please remove Glenhaven. 14. There is a transformer where the dumpster is being proposed. Are there plans to relocated the transformer? LANDSCAPING/ST REET SCAPING/BUFFER 15. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback,rights- of-way,and adjacent property disturbed during construction. 16. Please provide a landscape plan with all applicable information from the site plan check list. Please provide existing landscape information along with all new landscaping. 17. All plantings must be irrigated. 18. Please provide a note on the landscape plan stating that an irrigation plan is required to be reviewed, approved and installed prior to Certificate of Occupancy. Reviewed by:Jennifer Reeves Date:June 21, 2006 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: FISH DADDY'S (SP)—06-00500153 PLANNING Please be aware that a portion of the building and the dumpster enclosure are being shown in the existing 15-foot PUE. The building and dumpster enclosure will need to shifted or the easement must be abandoned. Structures, including dumpster enclosures are not permitted in any easements. 4. An easement abandonment application and all supporting documents will need to be submitted to for processing to be placed on a City Council agenda for approval. /i. An easement dedication sheet will also need to be submitted with all supporting documents. (0. Please be aware that staff review comments#2&3 above will need to be fully addressed prior to site plan approval. (The abandonment cannot be approved until the electric lines are relocated and a replacement PUE dedicated. As submitted, the Site Plan cannot be approved until PUE is abandoned.) (5. Please show the nearest existing fire hydrant for this site, if it is not located on this site then please show the distance and direction of the nearest hydrant. (6. Please identify the water meter on the site plan. 7. Under the General Site Notes on the site plan, #3 states:"all existing parking spaces are 9'x8' /3. "Please adjust to 9'x18'. The dumpster opening only appears to be 10-feet. Sanitation needs at least a 12-foot clear opening to access the dumpster. Please adjust accordingly. ,/9. The interior parking island along University Drive does not currently exist. Please identify this as proposed on the site plan. y.10. Please provide a note on the site plan stating: "That in the event that seating is added to any outside portion of this building, additional parking will be required and a new parking plan will need to be provided for review". rDSCAPING/STREETSCAPING/BUFFER Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. 2. Please identify the existing canopy and non-canopy trees with specie name as well as the existing shrubs (height & species) on the landscape plan with points accrued. (Possibly bubble the proposed plantings). It appears from a site visit that what is being shown as existing is not actually there. 113. Please provide streetscape legend with calculations (points required - points provided, see i4. Section 7.5.D streetscape requirements). Please do not reference old landscape plan. This project must stand on it's on. The landscape plan will need to show the above information that was requested (comments 13 & 14)on it. \i . Please provide a note on the landscape plan stating: "An irrigation plan is required to be submitted for review and approval prior to Certificate of Occupancy". If the same irrigation system is being used, please provide a copy of the plan with any changes. Reviewed by: Jennifer Reeves Date: July 13, 2006 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. P. STAFF REVIEW COMMENTS NO. 1 Project: FISH DADDY'S—06-00500133 (Due to the lack of information submitted staff could not provide a comprehensive review.) Below is a list of comments from a cursory review from Staff with the information that was turned in. (Please be aware the following comments would not be required if the site was not being altered. If the building was the only thing being changed then the Non-Residential Architectural Standards would be the only requirement) PLANNING 1. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot,measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. 2. This project does involve site changes, therefore will be required to turn in a site plan application for review of the site, landscape and elevations of the proposed building. (Application faxed to Michael Twichell 6/21/06). 3. Parking for a restaurant without a drive through is 1/65., with 5,590 square feet this will require 86 parking spaces. Currently this site would not meet the parking requirements. Please provide a parking legend on the site plan. (Parking required and parking provided) 4. Please show all existing and proposed utilities. 5. Please show all existing and proposed P.U.E's. 6. Please provide curbing and parking detail for revised parking areas. 7. Please provide a dumpster detail on the site plan. Dumpster pads are required to be a minimum of 12'x12'. Please be aware that if bollards are being placed in the dumpster enclosure they are required to have 12-feet of clearance on the width and depth. (Gates are required) 8. Please provide colored elevations with a legend providing colors, materials and percentages of materials for each facade per Section 7.9 Non-Residential Architectural Standards. 9. The correct zoning for the subject property is C-1 General Commercial located in the 0-V Corridor Overlay District. Please provide the correct zoning on the site plan. 10. Please provide building setbacks. 11. A 180 square foot end island is required at the end of every parking row. It appears that the parking space next the dumptser is not 180-square feet. 12. What is being proposed next to the dumpster 13. The drive going into the shopping center is not Glenhaven Drive, it is a private drive. Please remove Glenhaven. 14. There is a transformer where the dumpster is being proposed. Are there plans to relocated the transformer? LANDSCAPING/ST REET SCAPING/BUFFER 15. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback,rights- of-way,and adjacent property disturbed during construction. 16. Please provide a landscape plan with all applicable information from the site plan check list. Please provide existing landscape information along with all new landscaping. 17. All plantings must be irrigated. 18. Please provide a note on the landscape plan stating that an irrigation plan is required to be reviewed, approved and installed prior to Certificate of Occupancy. Reviewed by:Jennifer Reeves Date:June 21, 2006 Home of Texas A&M University MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device,and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 3 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. Sanitation Comments 1. Sanitation is ok with this project. Reviewed by:Wally Urrutia Date: July 19,2006 ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION 1. Developer provides temporary blanket easement for construction purposes. 2. Developer provides easements for electric infrastructure as installed for electric lines GENERAL ELECTRICAL COMMENTS 1. Developer installs conduit per city specs and design. 2. Developer will install 3-4"PVC conduits from transformer to building service location. Service wire furnished and installed by CSU. 3. Meter will be located on building. Meter and CT's furnished by CSU and installed by owner. 4. City will provide drawings for conduit installation. 5. Developer to intercept existing conduit at designated transformers and extend as required. 6. If conduit does not exist at designated transformer,developer to furnish and install conduit as shown on electrical layout. 7. Developer pours transformer pad(s) per city specs and design. 8. Developer installs pull boxes as per city specs and design.(pull boxes provided by the city). 9. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan email to sweido(icstx.gov 10. Developer provides load data for project. 11. To discuss any of the above electrical comments,please contact Sam Weido at 979.764.6314. Reviewed by: Sam Weido Date: 7-19-06 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and`bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. P� MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device,and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 3 STAFF REVIEW COMMENTS NO. 2 Project: FISH DADDY'S (SP) - 06-00500153 PLANNING 1. Please put all easements back on the site plan. 2. Cleary note on the site plan that the existing 15-foot Public Utility Easement where the existing electrical runs through the property and a portion of the proposed building is to be removed and electrical is to be relocated prior to Certificate of Occupancy. 3. Please clearly depict on the site plan where the relocation of the 15-foot Public Utility Easement and electrical will be relocated too. 4. Please be aware that the relocation of the electrical and PUE's will be required prior to Certificate of Occupancy. 5. The parking legend should reflect the gross square footage (5,282). 6. Please reflect (18) number of parking spaces along University Drive. This parking legend should reflect 83 parking spaces provided. 7. On the landscape plan under "existing landscape" the legend reflects "10 - 5 gallon DWF. Wax Myrtle valued at 10 points for a total of 130 points" Please adjust the total points as 100. 8. Under new landscape the legend reflects the 1-gallon Daylilly & Bermuda as 10 points a piece, however the total points are correct. Please adjust the individual point value as 1 point a piece. Reviewed by:Jennifer Reeves Date:August 9,2006 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 2 of 2 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. Sanitation Comments 1. Sanitation is ok with this project. Reviewed by:Wally Urrutia Date: July 19,2006 ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION 1. Developer provides temporary blanket easement for construction purposes. 2. Developer provides easements for electric infrastructure as installed for electric lines GENERAL ELECTRICAL COMMENTS 1. Developer installs conduit per city specs and design. 2. Developer will install 3-4"PVC conduits from transformer to building service location. Service wire furnished and installed by CSU. 3. Meter will be located on building. Meter and CT's furnished by CSU and installed by owner. 4. City will provide drawings for conduit installation. 5. Developer to intercept existing conduit at designated transformers and extend as required. 6. If conduit does not exist at designated transformer,developer to furnish and install conduit as shown on electrical layout. 7. Developer pours transformer pad(s) per city specs and design. 8. Developer installs pull boxes as per city specs and design.(pull boxes provided by the city). 9. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan email to sweido(icstx.gov 10. Developer provides load data for project. 11. To discuss any of the above electrical comments,please contact Sam Weido at 979.764.6314. Reviewed by: Sam Weido Date: 7-19-06 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and`bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. P�