HomeMy WebLinkAboutStaff Review STAFF REVIEW COMMENTS NO. 1
COOS THOMAS PARK POOL BATH HOUSE (NRA) — NRA Review
08-00500172
PLANNING
1. Sheet A3.1 shows a "new chain link fence", but this section is not labeled as "new" on the
site plan. Therefore, please be aware that the new section needs to be screened from the
right-of-way to comply with screening standards found in the UDO, Section 3.5.E. This can
be shown on the next site plan or landscape plan submittal. Another option would be to
construct the "new" portion out of a different fence material which does not require
screening. Thank you!
2. Please remove the sign from the northern elevation, or add a note that all signage is
permitted separately.
3. The percentages of each material being used have been recalculated. Please check for
accuracy. Thank you!
4. The West Elevation does not meet the minimum standard for architectural relief elements.
Partitions are not on the approved architectural relief element list found in Article 7.9.2 of the
UDO. Please add 1 (one) element to this elevation in order to meet standards.
5. Please show the "Material and Description" table, from the NRA Building Review Minimum
Requirements sheet, on Sheet A3.1.
Reviewed by: Lauren A. Hovde, Staff Planner Date: September 16, 2008
1d/03/b8 40fiiieft (Q-)-f -'D t'-{i-'or) is a.Gf.Zp A.- ei • • -V0, '14."1". ` 4. --
STAFF REVIEW COMMENTS NO. 1
COOS THOMAS PARK POOL BATH HOUSE (NRA) — NRA Review 2
08-00500172
PLANNING
1. Please consolidate A3.1 and the NRA Building Review Minimum Requirements to one page,
or update and resubmit the NRA Building Review Minimum Requirements sheet to reflect all
changes.
2. The West Elevation does not meet the minimum standard for architectural relief elements.
Please add (1) one additional element, from Article 7.9.2 of the UDO, to this elevation.
3. A general note must be provided stating that all roof and ground-mounted mechanical
equipment shall be screened from view or isolated so as not to be visible from any public
right-of-way or residential district within 150' of the subject lot, measured from a point five
feet above grade. Such screening shall be coordinated with the building architecture and
scale to maintain a unified appearance.
Reviewed by: Lauren A. Hovde, Staff Planner Date: August 28, 2008