HomeMy WebLinkAboutCorrespondence MEMORANDUM PROJECT: 0806 THOMAS PARK POOL HOUSE REPLACEMENT CITY OF COLLEGE STATION PROJECT NO. PK0802 Friday,January 16, 2009 To: Lauren Hovde Staff Planner City of College Station From: Steven Schloss Re: R7'resubmittal Please find attached our response(s)to the most recent round of staff comments 71° regarding our July 28,2008 NRA submittal for Thomas Park Pool House Replacement. Planning 1. 4/A1.1 displays an accessible parking sign detail, not a fire lane sign. Please move the fire lane sign closer to the are not being striped as fire lane. The It 4/A1.1 shows an accessible parking sign, and a note to replace the graphic and text with the correct fire lane verbiage. We have done this Arkitex one other projects, and saves space on the drawing. We have moved Studio, Inc. the fire lane sign further down the driveway. 308 N.Bryan Ave. 2.Please add a detail to the site plan for the 6" curb. Bryan,TX 77803 This detail has been added above 4/A1.1. (We typically show this de- P(979)821-2635 tail on the Civil drawings, so we have duplicate information in this F(979)775-8224 case.) www.arkitex.com Enclosed: Eight(8)complete sets of construction documents (C1, C2,A1.1,A3.1) Four(4) additional revised site plans. otc \qic) cft' \ / c 1 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 Cory or COLLEGE ST/0'10N MEMORANDUM November 9, 2008 TO: Steven Schloss and Eva Read-Warden, AIA, Arkitex Studio, Inc via fax: 979- 775-8224 FROM: Lauren A. Hovde, Staff Planner SUBJECT: COCS THOMAS PARK POOL BATH HOUSE (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. Please address the attached comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with a revised site plan attached to each set (one set will be returned to you, please submit additional copies if you want more than one approved set) Four (4) additional revised site plans If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments pc: Pete Vanecek via email pvanecek@cstx.gov Case file #08-00500170 0 ' '7)ILi ; o I� MEMORANDUM PROJECT: 0806 THOMAS PARK POOL HOUSE REPLACEMENT CITY OF COLLEGE STATION PROJECT NO. PK0802 Thursday, October 30, 2008 To: Lauren Hovde Staff Planner City of College Station From: Steven Schloss Re: Site Plan resubmittal#2 Please find attached our response(s)to staff comments regarding our July 28, 2008 site plan submittal for Thomas Park Pool House Replacement. Planning Please show the fire lane striping in the parking lot. Fire lane striping and fire lane sign are now shown on the site plan. The Please add the curb and pavement details to the site plan. Arkitex Curb and pavement details are now shown on the site plan. Studio, Inc. If any other parking spaces will be affected by the new handicap striping, please inform staff. 308 N.Bryan Ave. The only parking space affected by the striping is the one adjacent to Bryan,TX 77803 P(979)821-2635 the handicapped space. The dimensions are now shown correctly on F(979)775-8224 the site plan. www.arkitex.com FYI...The minimum parking space dimension on a 60 degree angle is 9'x 22.3'. The existing parking spaces are 9' wide, except for the handicapped space which is 13' wide. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. This note has been added to the site plan Please note that any changes made to the plans, that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled" on your plans. Any additional changes on these plans that the City has not be made of aware of will constitute a completely new review. The revised entry has been added to the Site Plan and bubbled. Enclosed: One (1)revised site plan 1101 Texas Avenue, P.O. Box 9960 �.� College Station, Texas 77842 1_l Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM August 29, 2008 TO: Steven Schloss and Eva Read-Warden, AIA, Arkitex Studio, Inc via fax: 979-775-8224 FROM: Lauren A. Hovde, Staff Planner SUBJECT: COOS THOMAS PARK POOL BATH HOUSE (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with a revised site plan attached to each set (one set will be returned to you, please submit additional copies if you want more than one approved set) Four (4) additional revised site plans If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. Attachments: Staff review comments cc: Pete Vanecek via email pvanecek@cstx.gov Case file #08-00500170 TRANSMISSION VERIFICATION REPORT TIME : 09/02/2008 18:20 NAME : FAX . TEL . SER.# : 000L5J596800 DATE,TIME 09102 18: 19 FAX NO./NAME 99797758224 DURATION 00:00:36 PAGE(S) 02 RESULT OK MODE STANDARD ECM 1101 Texas Avenue, P.O. Box 9960 41.ful"11 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 Cru OF COLLEGE STATION MEMORANDUM August 29, 2008 TO: Steven Schloss and Eva Read-Warden, AIA, Arkitex Studio, Inc via fax: 979-775-8224 FROM: Lauren A. Hovde, Staff Planner SUBJECT: COCS THOMAS PARK POOL BATH HOUSE (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. if all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with a revised site plan attached to each set (one set will be returned to you, please submit additional copies if you want more than one approved set) Four(4) additional revised site plans If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. TRANSMITTAL PROJECT: PK0802 THOMAS POOL BATH HOUSE REPLACEMENT Tuesday, August 18, 2008 Lauren Hovde City of College Station Planning College Station, TX Dear Lauren, Enclosed please find each of the following: Resubmittal: NRA Resubmittal: Site Plan The e Arkitex Studio, Inc. 308 N.Bryan Ave. Bryan,TX 77803 F(979)821-2635 F(979)775-8224 See attached memos for details. www.arkitex.com Sincerely, Associate Principal The Arkitex Studio, Inc. MEMORANDUM PROJECT: 0806 THOMAS PARK POOL HOUSE REPLACEMENT CITY OF COLLEGE STATION PROJECT NO. PK0802 Monday,August 18, 2008 To: Lauren Hovde Staff Planner City of College Station From: Steven Schloss Re: Site Plan resubmittal Please find attached our response(s)to staff comments regarding our July 28, 2008 site plan submittal for Thomas Park Pool House Replacement. Planning Please show the fire lane striping in the parking lot. Fire lane striping and fire lane sign are now shown on the site plan. The Also, please show the existing fire hydrants within close proximity to the site. There should be four in that vicinity. Arkitex Distance and location to the existing fire hydrants are now shown on Studio, Inc. the site plan. 308 N.Bryan Ave. Please add the curb and pavement details to the site plan. Bryan,TX 77803 P(979)821-2635 Curb and pavement details are now shown on the site plan. F(979)775-8224 Please provide the number of bicycle parking spaces on the site plan. www.arkitex.com The existing bike rack holds 18 bikes and will be relocated. The new location is shown on the site plan. If any other parking spaces will be affected by the new handicap striping, please inform staff. The only parking space affected by the striping is the one adjacent to the handicapped space. The dimensions are now shown correctly on the site plan. FYI...The minimum parking space dimension on a 60 degree angle is 9'x 22.3'. The existing parking spaces are 9' wide, except for the handicapped space which is 13'wide. Please remove the label showing the new landscaped area. We do not understand this comment. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. There is neither roof nor ground-mounted mechanical equipment in the scope of work. We're concerned that including this note would be confusing to the contractor. pr'(JJ `83-a 1 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 /—� Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM August 29, 2008 TO: Steven Schloss and Eva Read-Warden, AIA, Arkitex Studio, Inc via fax: 979-775-8224 FROM: Lauren A. Hovde, Staff Planner SUBJECT: COCS THOMAS PARK POOL BATH HOUSE (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with a revised site plan attached to each set (one set will be returned to you, please submit additional copies if you want more than one approved set) Four (4) additional revised site plans If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. Attachments: Staff review comments cc: Pete Vanecek via email pvanecek@cstx.gov Case file #08-00500170 TRANSMISSION VERIFICATION REPORT TIME : 08/29/2008 15:52 NAME : FAX . TEL . SER.# : 000L5J596800 DATE,TIME 08129 15:51 FAX NO./NAME 99797758224 DURATION 00:00.27 PAGE(S) 02 RESULT OK MODE STANDARD ECM 4ffs-•••44 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLI.RC.E STATION MEMORANDUM August 29, 2008 TO: Steven Schloss and Eva Read-Warden, AIA, Arkitex Studio, Inc via fax: 979-775-8224 FROM: Lauren A. Hovde, Staff Planner SUBJECT: COGS THOMAS PARK POOL BATH HOUSE (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with a revised site plan attached to each set (one set will be returned to you, please submit additional copies if you want more than one approved set) Four (4) additional revised site plans If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 (Arff Phone 979.764.3570/Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM August 4, 2008 and Eva Read-Warden, AIA, Arkitex Studio, Inc via fax: 979-775-8224 TO: Steven Schloss tag FROM: Lauren A. Hovde, Staff Planner SUBJECT: COCS THOMAS PARK POOL BATH HOUSE (SP)- Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Cover memo providing written responses to all of staff's comments (identify the specific page that each comment was addressed on or the reason for not addressing the comment); Seven (7) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (one set will be returned to you, please submit additional copies if you want more than one approved set); Three (3) revised site plans; One (1) landscaping plan; One (1) 11x17 grading and erosion control plan; If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please contact Lauren Hovde at 979.764.3570. Attachments: Staff review comments pc: Pete Vanecek via email pvanecek@cstx.gov Case file#08-00500170 TRANSMISSION VERIFICATION REPORT TIME : 08115/2008 16:51 NAME : FAX . TEL . SER.# : 000L5J596800 DATE,TIME 08115 16:50 FAX NO./NAME 96932554 DURATION 00:00:34 PAGE(S) 04 RESULT OK MODE STANDARD ECM "PI% CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue South, PO Box 9960 College Station,Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 FACSIMILE COVER SHEET Date: August 15, 2008 # of pages including cover: 4 If you did not receive a complete fa',please call our office immediately for a new transmittal. TO: Dale FAX: 693.2554 COMPANY: McClure &Browne RE: Thomas Pool House comments FROM: Moll Hitchcock Planni : Administrator COMPANY: City of College Station REMARKS: ❑ Urgent ® For your review ❑ Reply ASAP ❑ FYI Page 1 of 1 Lauren Hovde - Thomas Pool From: Lauren Hovde To: eva@arkitex.com; Vanecek, Pete Date: 9/2/2008 8:27 AM Subject: Thomas Pool The Fire Department has no comments to add. Thank you! Lauren Amelia Hovde '06 Staff Planner Planning&Development Services Department 979-764-3570 f;te•l/C•\Documents and Settings\lhovde\Local Settings\Temp\XPGrpWise\48BCF8F5City ... 9/2/2008