Water System Report
for
Saddle Creek Subdivision, Phases 7A
College Station, Texas
March 2008
Prepared By:
Civil Development, Ltd.
2033 Harvey Mitchell Parkway South
College Station, Texas 77840
(979) 764-7743
4‘4,
•
•
h'-•
v�
3/3%84
I
General Information
Location: Saddle Creek Subdivision,Phase 7A is located in southern Brazos County,near the
intersection of Wade Road and Stousland Road. Phase 1 was completed in the
Spring of 2007 and Phase 2 is currently under construction.
No. of Lots: Phase 7A- 8 lots
Land Use: Single Family Residential—rural estate lots that are 1 acre or larger
WATER SYSTEM ANALYSIS
Design Criteria
Primary Water Supply: Existing 12"line along Stousland Road operated by Wellborn SUD.
Domestic Demand:
Avg.Pop Density: 2.67 people per lot
Average Flow: 100 gpd/cap or 267 gpd per lot=0.18 gpm per lot
Peaking Factor: 4
Peak Flow: 0.74 gpm per lot
Design Flow: 1.50 gpm per lot
Fire Demand:
Fire Flow: 1000 gpm
Pipe: PVC DR-14 C909
Roughness Coef: 150(Hazen Williams)
Hydraulic Software: Haestad Methods WaterCAD v.6.0
Existing System Pressure Tests
Flow Hydrant: Fire Hydrant on Stousland Road, south of Wade Road.
Flowrate: 1300 gpm
Guage Location: 5401 Stousland Road(hose bib on side of house)
Static Pressure: 78 psi(180 ft water)
Residual Pressure: 75 psi(173 ft water)
Applicable Exhibits: Exhibit B—Flow Test Report
Water System Analysis Summary
1 As
Criteria Required Designed Location
Min. Pressure-fire(psi) 20 66.86 SC7A02
Max. Velocity(fps) 12 11.64 P7A01
Max. Length of 6"pipe(ft)
(connected to > 8"on both 1500 E NA
ends)
Max Length of 6"pipe(ft) 1800 585
(not connected on both ends)
Max.Length of 3"pipe(ft) 500 175
Applicable Exhibits: Exhibit A—Water System Schematic
Exhibit C—Water System Analysis—Junction Summary
Exhibit D—Water System Analysis—Pipe Summary
Conclusion
The proposed water system for Saddle Creek Subdivision, Phases 7A meets or
exceeds all of the design criteria for the City of College Station. It will provide
adequate water pressure and flow for both domestic and fire demands.
1
Exhibit B
Water System Flow Test Report
Date: November 16, 2006
Water System Owner: Wellborn Special Utility District
Development Project: Saddle Creek Subdivision
Flow Test Location: Fire Hydrant @ 5401 Stousland
Nozzle size (in.): 2.5 Discharge Coef: (c): 0.9
Pitot Reading (psi): 60 Flowrate formula: Q=29.84cd2p112
c=discharge coef.
d=orifice size(in)
p=pitot pressure(psi)
Flowrate (gpm): 1300 computed
Pressure Guage Location: Hose Bib on House at 5401 Straub
Static(psi): 78
Residual (psi): 75
Report prepared by: Z ijd 'i
signature
Kent Laza ����
in. 658'23
printed name �_.:
Others present: Steven Cast
Exhibit C
Saddle Creek Subdivision, Phases 1,2 & 7A
Water System Analysis - Junction Summary
Fire Flow Conditions
Hydraulic
Label Elevation Demand 11 Grade I Pressure
(ft) (gpm) (ft) (psi)
SC1 FH1 284 3.0 459.38 75.88
SC1 FH2 276 0.0 457.37 78.47
SC1 FH3 273 6.0 455.87 79.12
SC1 FH4 273 0.0 455.37 78.90
SC2 FH1 277 0.0 457.13 77.93
SC7A FH1 268 1,000.0 422.64 66.90
SC7A01 270 0.0 455.37 80.20 Ph 7A
SC7A02 268 12.0 422.54 66.86
SC7A03 267 13.5 422.48 67.27
SC102 275 7.5 457.14 78.80
SC103 274 9.0 457.07 79.21
SC104 273 4.5 455.37 78.90
SC105 275 4.5 455.37 78.04
SC106 282 0.0 455.37 75.01
SC201 277 15.0 457.13 77.93
SC202 277 0.0 457.13 77.93
SC203 274 7.5 457.07 79.21
SC204 279 0.0 457.13 77.07
Tested Hydrant 286 0.0 460.39 75.45
Lowest Pressure = 66.86 Ph 7A
Exhibit D
Saddle Creek Subdivision, Phases 1, 2 & 7A
Water System Analysis - Pipe Summary
Fire Flow Conditions
I Length Diameter Discharge Velocity
Label Material
(ft) (in) Williams C (gpm) (ft/s)
P7A01 549 6 PVC 150 1,025.50 11.64
P7A02 270 3 PVC 150 -13.50 0.61 Ph 7A
P7A03 216 3 PVC 150 12.00 I 0.54
P101 446 12 PVC 150 -1,082.50 3.07
P102 898 12 PVC 150 -1,079.50 3.06
P103 103 12 PVC 150 -1,079.50 3.06
P104 264 3 PVC 150 9.00 0.41
P105 610 12 PVC 150 1,040.50 2.95
P106A 241 12 PVC 150 -1,034.50 2.93
P106B 555 12 PVC 150 -9.00 0.03
P107 23 8 PVC 150 0.00 0.00
P108 994 8 PVC 150 0.00 0.00
P109 634 12 PVC 150 -4.50 0.01
P201 960 8 PVC 150 -22.50 0.14
P202 22 8 PVC 150 -22.50 0.14
P203 81 8 PVC 150 -7.50 0.05
P204 292 3 PVC 150 7.50 0.34
P205 292 8 PVC 150 0.00 0.00
Highest Velocity= 11.64 Ph 7A
Water System Report
for
Saddle Creek Subdivision, Phases 7A
College Station, Texas
March 2008
Prepared By:
Civil Development, Ltd.
2033 Harvey Mitchell Parkway South
College Station, Texas 77840
(979) 764-7743
ir..r- t-tt‹.-'.1.. ,
. - * A.
........igo,
-3/31084
General Information
Location: Saddle Creek Subdivision, Phase 7A is located in southern Brazos County, near the
intersection of Wade Road and Stousland Road. Phase 1 was completed in the
Spring of 2007 and Phase 2 is currently under construction.
No. of Lots: Phase 7A- 8 lots
Land Use: Single Family Residential—rural estate lots that are 1 acre or larger
WATER SYSTEM ANALYSES
Design Criteria
• Primary Water Supply: Existing 12"line along Stousland Road operated by Wellborn SUD.
Domestic Demand:
Avg. Pop Density: 2.67 people per lot
Average Flow: 100 gpd/cap or 267 gpd per lot=0.18 gpm per lot
Peaking Factor: 4
Peak Flow: 0.74 gpm per lot
Design Flow: 1.50 gpm per lot
Fire Demand:
Fire Flow: 1000 gpm
Pipe: PVC DR-14 C909
Roughness Coeff 150(Hazen Williams)
Hydraulic Software: Haestad Methods WaterCAD v.6.0
Existing System Pressure Tests
Flow Hydrant: Fire Hydrant on Stousland Road, south of Wade Road.
Flowrate: 1300 gpm
Guage Location: 5401 Stousland Road(hose bib on side of house)
Static Pressure: 78 psi(180 ft water)
Residual Pressure: 75 psi(173 ft water)
Applicable Exhibits: Exhibit B—Flow Test Report
Water System Analysis Summary
•
As
Criteria Required 1Designed Location
Min. Pressure-fire(psi) 20 66.86 SC7A02 *
Max. Velocity(fps) 12 11.64 P7A01
Max. Length of 6"pipe(ft)
(connected to > 8"on both 1500 NA
ends)
Max Length of 6"pipe(ft)
(not connected on both ends) 800 585
Max. Length of 3"pipe(ft) 500 175 •
Applicable Exhibits: Exhibit A—Water System Schematic
Exhibit C—Water System Analysis—Junction Summary
Exhibit D— Water System Analysis— Pipe Summary
Conclusion
The proposed water system for Saddle Creek Subdivision, Phases 7A meets or
exceeds all of the design criteria for the City of College Station. It will provide
adequate water pressure and flow for both domestic and fire demands.
Exhibit B
Water System Flow Test Report
Date: November 16, 2006
Water System Owner: Wellborn Special Utility District
Development Project: Saddle Creek Subdivision
Flow Test Location: Fire Hydrant @ 5401 Stousland
Nozzle size(in.): 2.5 Discharge Coef: (c): 0.9
Pitot Reading(psi): 60 Flowrate formula: Q=29.84cd2p1i2
c=discharge coef.
d=orifice size(in)
p=pitot pressure(psi)
Flowrate(gpm): 1300 computed
Pressure Guage Location: Hose Bib on House at 5401 Straub
Static (psi): 78
Residual (psi): 75
/Report prepared by: I% % •
signature40 .`k
Kent Laza '".`' • 85823 , .,
printed name ,•.%.1
ti`s`_ti • +•�'
Others present: Steven Cast
Exhibit C
Saddle Creek Subdivision, Phases 1 ,2 & 7A
Water System Analysis - Junction Summary
Fire Flow Conditions
L I
Hydraulic
Label Elevation I Demand Grade Pressure
(ft) (gpm) (ft) (psi)
SC1 FH1 284 3.0 459.38 75.88
SC1 FH2 276 0.0 457.37 78.47
SC1 FH3 273 6.0 455.87 79.12
SC1 FH4 273 0.0 455.37 78.90
SC2 FH1 277 0.0 457.13 77.93
SC7A FH1 268 1,000.0 422.64 66.90
SC7A01 270 0.0 455.37 80.20 Ph 7A
SC7A02 268 12.0 422.54 66.86
SC7A03 267 13.5 422.48 67.27
SC102 275 7.5 457.14 78.80
SC103 274 9.0 457.07 79.21
SC104 273 4.5 455.37 78.90
SC105 275 4.5 455.37 78.04
SC106 282 0.0 455.37 75.01
SC201 277 15.0 457.13 77.93
SC202 277 0.0 457.13 77.93
SC203 274 7.5 457.07 79.21
SC204 279 0.0 457.13 77.07
Tested Hydrant 286 0.0 460.39 75.45
Lowest Pressure= 66.86 Ph 7A
Exhibit D
Saddle Creek Subdivision, Phases 1 , 2 & 7A
Water System Analysis - Pipe Summary
Fire Flow Conditions
Label Length Diameter Hazen- Discharge Velocity
(ft) (in) - Material Williams C (gpm) (ft/s)
P7A01 549 6 PVC 150 1,025.50 11.64
P7A02 270 3 PVC 150 -13.50 , 0.61 Ph 7A
P7A03 216 3 PVC 150 12.00 0.54
P101 ! 446 12 PVC 150 -1,082.50 3.07
P102 898 12 PVC 150 -1,079.50 3.06
P103 103 12 PVC 150 -1,079.50 3.06
P104 264 3 PVC 150 9.00 0.41
P105 610 12 PVC 150 1,040.50 2.95
P106A 241 12 PVC 150 -1,034.50 2.93
P106B 555 12 PVC 150 -9.00 0.03
P107 23 8 PVC 150 0.00 0.00
P108 994 8 PVC 150 0.00 0.00
P109 634 12 PVC 150 -4.50 0.01
P201 960 8 PVC 150 -22.50 0.14
P202 22 8 PVC 150 -22.50 0.14
P203 81 8 PVC 150 -7.50 0.05
P204 292 3 PVC 150 7.50 0.34
P205 292 8 PVC 150 0.00 0.00
Highest Velocity= 11.64 Ph 7A
0
Exhibit A
Water System Flow Test Report
Date: August 7, 2008
Water System Owner: Wellborn SUD
Development Project: Saddle Creek Subdivision, Ph 7A
Flow Test Location: FH 2 at end of Creek Crossing Ct
Nozzle size (in.): 2.5 Discharge Coef: (c): 0.9
Pitot Reading (psi): 60 Flowrate formula: Q=29.84cd2 p 1/2
c=discharge coef.
d=orifice size(in)
p=pitot pressure(psi)
Flowrate (gpm): 1300 computed
Pressure Guage Location: FH 1 at corner of Gunoak Tr and Creek Crossing Ct
Static (psi): 87
Residual (psi): 56
This flow test was conducted in accordance with NFPA 291. The system meets or exceeds
minim m design tandards and flow reequirements of the City and the State of Texas.
Report prepared by: e ,o .-'``
signature ,Kent Lazaprinted name r,inlit.s,
j'... r. r4,6'
r. C5923 .
.. .11--*.
Others present: Steven Cast,Wellborn SUD ;.'= �, m
Ul io &
Meredith Carriker, CDL
Mike Marcus,Texcon
:It
II
Tested Hydrant
i
P101
C1 FH1
"_ ' 02
\ ,\ / I
,.� /
�,, 1 F /
,
/,
P1,0 /;
C
SCy103 104'; :;p ,/
\``^"'/ i I t k Q1
I. , �� 0204
`; i i v / /; P205
} 4 SC2 02
ill O1
Il ' \c-,-----f P 202
' , :
f
S H3 . __ N. P204
/ ',f? 6A •\
• �• C20
/C7A0 SC A01 ..' ;`
P7A A01 -
'0040 't":06B ,
F 1ti`
P7A
07
' S.C1 F.H
r A03 08.•
11 % \ \
C 6
/ .' . 'I) ,
SC105
EXHIBIT SADDLE CREEK, PH 7A (with 1 & 2) *C7u27,,FRr nrrL".*
29001ongmire Orive,SuilnK
A WATER SYSTEM SCHEMATIC College Stalin. Texas 77845
L'0 fin.„329.College SulounaSCALE: NOT TO SCALE 1 Les 77842
1979,704.7743 0a.19791764-7759
Tested Hydrant
101
Cl FH1
rv�yti's
02
\\\i.
�' \ 1 F /
/ /;
` P103
/ C i'
SC103v 104
i / A�
1 /
/ • C204
/ P205
i , SC2 ; 0 I1,21
'" 202
S H3
P204
/' P 06A
-- C20
/C7A0• :.SC A01 - --
P7A13 i" A01
- - tori . P 06B
e
F 1
P7A112
® 07
I -- '4,`SC1 FHS
'A03 08
/ \
/ v) C 16
SC105
Y
EXHIBIT SADDLE CREEK, PH 7A (with 1 & 2) *Cry D cop rLa.*
A •
'1929retat Solex SCALE: NOT TO SCALE
WATER SYSTEM SCHEMATIC College Slalion.Texas 77845
PO Br. .College Station Texas 77842
19791764-7743 Fax 19791764-7759