HomeMy WebLinkAboutCorrespondence 1 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 /—� Phone 979.764.3570/Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM January 30, 2008 TO: Sam Vernon, Bleyl & Associates, via fax 260.3849 FROM: Matt Robinson, Staff Planner SUBJECT: REMAX (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Cover memo providing written responses to all of staff's comments (identify the specific page that each comment was addressed on or the reason for not addressing the comment); One (1) revised site plan; One (1) landscaping plan; Other Engineering Documents as described in the Staff Review Comments; Easement Dedication Sheet and required documents (please allow 4 weeks to process). Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments pc: Y/Tim Ware, via fax 764.7676 Case file #08-00500014 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 1 of 3 B Bleyl & Associates 1722 Broadmoor g, Suite 210 ', - .i (7L Project Engineering & Management Bryan, TX 77802 A lk February 25, 2008 . City of College Station ATTN: Matt Robinson, Staff Planner P 0 Box 9960 College Station,Texas 77842 RE: REMAX Site Plan Comments Below is a listing of the comments received January 30, 2008 regarding the site plan for the above referenced project. Following each comment is our response in italics. PLANNING 1. Please state and/or reconcile the square feet of the proposed building. The application states 11,850 while the site plan states 11,822. The square footage of the building is 11,822. There will also be a 96 square foot storage building built on site bringing the total square footage to 11,918. 2. State the proposed use of the building on the site plan. The building use is Commercial/Office Building. This has been added to the Site Synopsis. 3. Please provide a note on the site plan that signs are permitted separately. This note has been added. 4. Please make sure that the proposed building does not encroach into the rear setback. Noted. This has been checked. 5. For safety purposes, the parking spaces adjacent to the retaining wall will require wheelstops. Wheelstops, however, cannot be placed within 18' deep spaces but requires that the parkings spaces be at least 20' in depth. Please revise these parking spaces. These parking spaces have been lengthened and wheelstops added. 6. There appears to be off-site improvements with the grading at rear of property. This needs to be accounted for in the construction documents and potentially an associated easement. We have removed any grading on the Veteran's Park site. 7. Please note that the dumpster location will work for a side-load 300-gallon container. If the applicant desires to use a front-loaded metal container, the location and/or angle will need to be revised. Noted. The Owner desires the smaller 90 gallon containers. Their pick up location will be in front of the proposed storage building. This area has changed from the last review cycle and is now clouded on the site plan. LANDSCAPING/STREETSCAPING/BUFFER 1. A Landscape Plan was not submitted. Please provide in accordance with UDO Section 7.5. Noted. This plan was submitted today. 2. Provide a general note on the Landscape Plan that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. This comment appears on the Landscape Plan. Bryan Austin Conroe (979)-268-1125 (512)-328-7878 (936)-441-7833 (979)-260-3849 (512)-328-7884 Fax (936)-760-3833 Fax 3. Please provide a note on the Landscape Plan that the irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. This comment appears on the Irrigation Plan. ENGINEERING COMMENTS NO. 1 loleePlease submit development infrastructure fee. Noted. oePPlease submit plan/profile construction documents for public main/hydrant extension. A plan and profile has been developed for this extension. oc: lease submit easement dedication application as all public mains, hydrants and meters must be located within an easement. These will be submitted under a separate cover. .. 'lease submit letter of acknowledgement. This letter is included. 5 'lease submit fire flow report. This report is attached. Please submit drainage report, including technical design summary and the appropriate certification if no detention is proposed. Also, please include a summary of the conversation between Alan and Brett regarding this site location in the floodway/flood plain, the proposed City of Bryan LOMR, and the ability to develop this site. This is included. sib 4Please submit a depiction of the offsite sanitary sewer service connection. See comment 8. WV. This will be submitted when the route is finalized. sr Please provide written verification from CoCS Parks that the proposed off site construction and sanitary sewer service connection will be allowed. The owner of the property, Tim Ware, has met with David Coleman and Terry Childers on two occasions concerning this matter. It is my understanding that Mr. Coleman and PARD are working to find a route for a small diameter force ain. We are awaiting final approval of the route from Mr. Coleman. ease provide written verification from CoCS Parks that the proposed off site grading will be (lowed. We have removed all grading from within the Veteran's Park site. lease illustrate water meter size. The water meter has been sized, depicted, and called out on leplans. ase illustrate irrigation meter location and presence of back flow device. The irrigation meter and backflow preventer is depicted, and called out on the plans. ease submit erosion control plan. An erosion control plan is included. :44'lease submit engineer's cost estimate. An Engineer's cost estimate is included. ase contact TxDOT regarding their review of the site plan that was forwarded to them X� ��rom CoCS P&DS. I've spoken to Jay Page and we will be resubmitting our application to TxDOT jiith the additional information as requested by Mr. Page. Please include an illustration of the existing and proposed driveway on this portion of FM 60, verify that the minimum driveway spacing are being met. This exhibit is included for your review. ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION 1. Developer provides temporary blanket easement for construction purposes. Easement will be submitted under separate cover. 2. Developer provides easements for electric infrastructure as installed for electric lines. These easements will be executed after infrastructure is complete. 3. Developer must provide a 10' PUE along property line adjacent to Veteran's Park. Noted. In subsequent talks with Mr. Weido, this can be reduced to 7.5 feet on the ReMax site. GENERAL ELECTRICAL COMMENTS 1. Developer installs conduit per City specs and design. Noted. 2. City will provide drawings for conduit installation. Noted. 3. 2-4" PVC conduits from rear property line to front property line adjacent to Veterans Park. CSU will intercept conduit and extend as required, Primary wiring by CSU. Noted. 4. Transformer will be located on the plan East side of the bldg. Noted. 5. Meter will be located on transformer. Service conduit and wire will be furnished and installed by the Developer. Noted. 6. Developer pours transformer pad(s) per City specs and design. Noted. 7. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan. Email to: sweido©cstx.gov. Site plan has been emailed. 8. Developer provides load data for project. Noted. SANITATION 1. Sanitation is ok with this project. Thank you. Since our last submittal, Mr. Ware has reassessed his needs and now desires to put a small 8' x 12' storage building where the dumpster pad was previously shown. I have spoken with Mr. Urrutia about using a series of 90 gallon containers in lieu of the 300 gallon previously shown. Please do not hesitate to call if you have any questions about this submittal. 4)rely, Sam J. V-'T%•n, P.E. Project Engineer 1 1101 Texas Avenue,P.O. Box 9960 (hi to, College Station,Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM March 3, 2008 TO: Sam Vernon, Bleyl & Associates, via fax 260.3849 FROM: Matt Robinson, Staff Planner SUBJECT: REMAX (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (one set will be returned to you, please submit additional copies if you want more than one approved set); Two (2) revised site plans; One (1) landscaping plan; One (1) 11x17 grading and erosion control plan; Other Engineering Documents as described in the Staff Review Comments; Easement Dedication Sheet and required documents (please allow 4 weeks to process). If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. Attachments: Staff review comments cc: Tim Ware, via fax 764.7676 Case file #08-00500014 B Bleyl & Associates 1722 Broadmoor Suite 210 A Project Engineering & Management Bryan, TX 77802 ok, os- iiino, ,,ri.t/e.. March 17, 2008 /� •s5 City of College Station "4 ATTN: Matt Robinson, Staff Planner P 0 Box 9960 College Station, Texas 77842 RE: REMAX Site Plan Comments Below is a listing of the comments received March 3, 2008 regarding the site plan for the referenced project. Following each comment is our response in italics. PLANNING 1. Please be aware the site plan will not be able to be approved until the TxDOT permit, easements and other engineering documents have been reviewed and approved. Noted. 2. A ZBA variance request has been submitted for the property. It appears that the variance is not necessary to develop the property as proposed. Please advise Staff if you would like to continue with the variance request or not. Tim Ware, the owner, still wants to pursue this request. 3. Please revise plantings to be selected from the College Station Plant List or as appropriate from the USDA for Hardiness Zone 8. Our Landscape Designer, Casey Krueger has met with Staff on this issue and has told me that these plants will be acceptable. 4. There appears to be only 15 Southern Wax Myrtle's, please revise the quantity and point amount. A 16th Southern Wax Myrtle has been added. 5. Please revise the total points claimed. A le Southern Wax Myrtle has been added. 6. Under Street Scape calculations"campy" is misspelled. 7. Under Points Per Project Area, please revise the calculation "61.25 x 30 = 18375.5". This has been revised to 1837.5. ENGINEERING COMMENTS NO.2 1. Please re-submit TxDOT permit. TxDOT permit application was resubmitted on March 4, we are awaiting their comments. 2. Please submit a depiction of the off-site sanitary sewer service connection. On March 6th, we met with David Coleman, PARD, and others from Utility Services to discuss the possibility of another Developer interested in the tract of land north of University Drive building the lift station on Mr. Ware's property. Mr. Ware is going to allow this lift station to be built, and give an access easement to PARD for a future trail system. In return, sanitary sewer service to his building will be connected to this lift station. The forcemain will be the responsibility of this second Developer. At this time, details are being worked out that will actually size the amount of property needed to accomplish this. 3. Please submit additional detail of the proposed retaining wall. The structural details for the retaining wall will be submitted and approved through the building permit application before it Bryan Austin Conroe (979)-268-1125 (512)-328-7878 (936)-441-7833 (979)-260-3849 (512)-328-7884 Fax (936)-760-3833 Fax will be constructed. 4. Please submit easement dedication application as all public mains, hydrants and meters must be located within an easement. This document is enclosed. 5. The existing hydrant along SH 60 is not accessible for the fire department therefore cannot be counted toward your fire flow report calculations, please revise. A second fire hydrant has been added. I have talked with Jerry Duffy and coordinated a location with him. 6. As this project is not proposing detention, please verify that the development is utilizing rapid conveyance to the primary channel, verifying that the sites discharge hydrograph and peak is ahead of the main channels hydrograph is such a manner that it does not create a new resulting peak greater than the main channels existing peak, so that there are no negative impacts. As we discussed by email and phone, According to the drainage manual (Table B-1), detention is not required on Hudson Creek from Carter's Creek to Boonville Road. By the USGS map and visual inspection of the site, it appears that the confluence of Hudson and Carter's Creek are downstream of our site. Since manual states detention is not required at this point, I am submitting a revised drainage report that includes my findings and the certification requested by the next comment. 7. Please provide certification found on page 11 of Section 2 of the BCS Unified Storm Water Design Guidelines. I am submitting a revised drainage report that includes this certification. 8. Please illustrate the existing floodplain and floodway per the current FIRM Panel, as well as the proposed floodplain and floodway as determined by your drainage report and/or pending LOMR. As we discussed by phone on March 4th, I have revised the note describing the floodway line shown as being based on the current FIS cross-section. I have bubbled all information that has been changed without comment from the City. These items include: 1. Sanitary sewer service from building. As explained in Item 6 of the Engineering Comment section, this has changed due to pending agreements with PARD, and Utility Services. 2. Rock flumes. Since our last submittal, it was discovered that our survey information was vertically off by three feet. Kerr Surveying adjusted their previous topo and benchmark information. We have re-graded the site in light of this information. Two rock lined flumes have been added to prevent erosion and direct runoff into existing ditches. Because of the additional fill required, the retaining walls have been lengthened. Finally, a portion of the fill on the northeast corner will extend into the Veteran's Park property. This will be addressed in the agreement executed with PARD allowing an access easement to accommodate their proposed trail. Please do not hesitate to call if you have any questions about this submittal. *rely, rely, Sam J. -, on, P.E. Project ' •gineer 1 1101 Texas Avenue,P.O. Box 9960 College Station,Texas 77842 Cirff Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM March 24, 2008 TO: Sam Vernon, Bleyl & Associates, via fax 260.3849 FROM: Jason Schubert, AICP, Staff Planner SUBJECT: REMAX (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following revised information as necessary for further staff review: $200 processing fee for the next round of three (3) staff reviews Seven (7) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (one set will be returned to you, please submit additional copies if you want more than one approved set) Two (2) revised site plans One (1) landscaping plan One (1) 11x17 grading and erosion control plan Easement Dedication Sheet and required documents If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments pc: Tim Ware, owner, via fax 764.7676 Case file #08-00500014 B Bleyl & Associates 1722 Broadmoor "z;!„. & Suite 210 Project Engineering & Management Bryan, TX 77802 A March 20, 2008 City of College Station ATTN: Jason Schubert, Staff Planner Josh Norton, Development Engineer P 0 Box 9960 College Station, Texas 77842 RE: REMAX Site Plan Comments Gentlemen: As I noted in an email last week, there have been a number of changes to this project since the last submittal, I am noting each of the changes in this letter along with a brief explanation of why each is requested. This is done in lieu of"bubbling"the affected areas. 1. The parking area has been moved east 3.5 feet. This still leaves a 4' strip for landscaping along the east line of the property. One parking space was removed from each tier of parking. These changes were made to increase the distance between the west property line and the western edge of the parking lot. It was more cost effective to use two levels of landscaping walls rather than a single structural retaining wall. 2. The dumpster pad along the front has been deleted. 3. The parking lot was moved north by 3' to increase the green space along the immediate front of the building, and accommodate the porches of proposed building. 4. Instead of creating new easement for the fire hydrant, water meter, etc. We have moved the fire hydrant and meter back into the 20 foot easement already owned by the City. 5. The most easterly fire hydrant has been moved to the east side of the new driveway to better align the domestic water service that will serve this building. 6. There were subtle changes made to the access road to account for the 3.5' shift of the parking lot. This change did not occur outside of the property and do not affect any work currently permitted within the TxDOT right of way. 7. At the behest of our client, grading along the north half of the parking lot has changed to again try and minimize the amount of fill material to the site. The northwest corner has been lowered by 3'. 8. The building footprint has changed and the west end of the building is now about 5' east of the west line. This was done to move the retaining wall off of the property line. 9. Grading along the back of the building has changed. We had previously shown or slopes beginning at 262. Now that the slab design has been completed, there will be a 3' deep D b.„I(`�� grade beam around the perimeter. This allows our slope to begin at an elevation of 260. 10. Landscaping items have been adjusted to reflect these changes. The quantities and types of planting materials have remained the same. — I have also listed the comments from the last submittal dated March 24th and either addressed them or have given a status of the item in italics. Bryan Austin Conroe (979)-268-1125 (512)-328-7878 (936)-441-7833 (979)-260-3849 (512)-328-7884 Fax (936)-760-3833 Fax PLANNING 1. The Unified Development Ordinance requires that untreated concrete retaining walls in excess of 6-inches in height be adequately screened (Section 7.5.D.6). The previous engineering comment requesting retaining wall details is therefore necessary to determine whether screening will be required or not. Please provide those details and note that if screening is required, it is to be provided on the subject property. These walls have been reduced in height and will be constructed as a Keystone-type landscaping wall. 2. Please note that the items described in the Engineering Comments below that are required in order to receive a full development permit are also necessary for site plan approval. Noted. ENGINEERING COMMENTS NO. 3 1. Please revise construction cost estimate. A revised cost estimate is included. 2. The easement dedication application that was submitted was not complete, as none of the required supporting documentation was included. This documentation will need to be submitted prior to issuance of a full development permit. The easements will be dedicated through the platting process. The preliminary plat was resubmitted today. 3. Prior to any off-site grading, we will need documentation from the Parks Department verifying their approval of the proposed grading. PARD has been contacted and we expect to receive this letter this week. 4. The Full Development Permit for this project will not be issued until the proposed lift station proposal has been approved. Noted. Meetings have been held with the CoCS, the City of Bryan, PARD, and the developers engineer to finalize this lift station. 5. The Full Development Permit for this project will not be issued until the TxDOT Permit has been approved. TxDOT has issued a permit for the driveway. Josh, let me know if you need a copy of it for your files, but I think I talked to you when I came by and got it. Once again, I thank you for your work on these reviews. Please do not hesitate to call if you have any questions about this submittal, or if you require any more information. 0-rely, Al #\JA/14/‘- Sam J. Vernon, P.E. Project Engineer , • 1 1101 Texas Avenue, P.O. Box 9960 Or. College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM April 28, 2008 TO: Sam Vernon, Bleyl &Associates, via fax 260.3849 FROM: Jason Schubert, Staff Planner SUBJECT: REMAX (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (one set will be returned to you, please submit additional copies if you want more than one approved set) Two (2) revised site plans One (1) landscaping plan One (1) 11x17 grading and erosion control plan Staff recommends that this information not be submitted until the lift station construction documents are submitted to the City for review. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Tim Ware, via fax 764.7676 Case file #08-00500014 B Bleyl & Associates 1722 Broadmoor Suite 210 A Project Engineering & Management Bryan, TX 77802 � S$ og May 4, 2008 6'06 10'6° City of College Station ATTN: Jason Schubert, AICP, Staff Planner PtC' P. O. Box 9960 College Station,Texas 77842 RE: REMAX Site Plan Comments Below is a listing of the comments received April 29, 2008 regarding the site plan for the referenced project. Following each comment is our response in italics. PLANNING 1. Please revise the gross building area to match the new building dimensions and articulation. Also revise the parking calculations if that is necessary. The square footage is12,007 sf. The parking has been recalculated, but did not change. 2. Show and label all PUEs including those being dedicated with the plat. Noted. 3. Show easements above all other layers. Noted. 4. As stated in the first round of comments, the parking spaces with wheelstops are required to be at least 20 feet in depth. Please revise the parking spaces adjacent to the retaining wall. The wheelstops along the western edge of the parking lot have been removed. 5. The parking spaces in front of the building are 18 feet deep and do not have the associated 4- foot landscape strip or 6-foot sidewalk required to have that reduced depth (the canopy/column area in front of the building creates the obstruction). All spaces along the front of the building now abut either a 4 foot wide landscape strip or a 6'wide sidewalk. 6. Please place some type of curbing (perhaps lay-down curb)at the top of the parking space that provides access to the lift station area. Also, paving from the parking space to the property line is not necessary in this area. 9 LF of laydown curbing has been added. 7. Please place intermittent curbing at the drainage discharge area at the northwest corner of parking lot. As proposed the gap in the curb between the parking spaces is too wide. This gap cas been reduced to 2'in width. r . tate law for handicap accessibility will require a handicap accessible route from the building to the right-of-way. Please revise. It appears that utilizing the already proposed sidewalk through the interior island will help achieve this requirement. Added ramps to make this a compliant route. 9. Please confirm that with the removal of the dumpster pad that roll-out container service will be provided with this site. This has been confirmed with Wally Urrutia. 10. It appears that the future property line when TxDOT acquires the right-of-way will be right along the front parking row. Please be aware that once that occurs, the parking lot and landscaping which would then be in the ROW will make the site non-conforming. Noted. ENGINEERING COMMENTS NO.4 1. Per our conversation, please revise the fire hydrant placement of the second hydrant so it is accessible from the internal fire lane. The fire hydrant has been moved. There is an Bryan Austin Conroe (979)-268-1125 (512)-328-7878 (936)-441-7833 (979)-260-3849 (512)-328-7884 Fax (936)-760-3833 Fax existing 20' waterline easement along the front of the ReMax site. The direction I have been given by our client is to keep the new hydrant within this easement while satisfying the City's access requirements. 2. Prior to any off-site grading, we will need documentation from the Parks Department verifying their approval of the proposed grading. We have received the letter from Parks regarding the Lift Station and will follow up with Parks regarding the proposed grading. Thank you. 3. The Full Development Permit for this project will not be issued until the proposed lift station proposal has been approved. Noted. There have been changes made to the grading along the western side of the property that were not requested by the City. Again these were made to minimize the amount landscaping walls required. The owner is also proposing to use 6" h x 6" w landscaping timbers along this side. Details of this will be submitted under the Architectural plans. I feel confident that all of the items raised by Staff have been now been addressed with the exception of the agreement concerning the proposed lift station. At this time, I am asking that a Conditional Development Permit be issued contingent upon the resolution of this lift station. Please do not hesitate to call me if you have any questions, or desire any other information. cerel , •am J. -rnon, P.E. • 1101 Texas Avenue, P.O. Box 9960 ffs.144 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM May 9, 2008 TO: Sam Vernon, Bleyl &Associates, via fax 260.3849 FROM: Jason Schubert, Staff Planner SUBJECT: REMAX (SP) -Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (one set will be returned to you, please submit additional copies if you want more than one approved set) Two (2) revised site plans One (1) landscaping plan One (1) 11x17 grading and erosion control plan If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: � Tim Ware, owner, via fax 764.7676 Case file #08-00500014 I LI, 0 440,' 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570/Fax 979.764.3496 1 CITY OF COLLEGE.STATION I V MEMORANDUM b J May 9, 2008 TO: Sam Vernon, Bleyl &Associates, via fax 260.3849 FROM: Jason Schubert, Staff Planner SUBJECT: REMAX(SP) -Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another$200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (one set will be returned to you, please submit additional copies if you want more than one approved set) Two (2) revised site plans One (1) landscaping plan Ni One (1) 11x17 grading and erosion control plan If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc:1 Tim Ware, owner, via fax 764.7676 Case file#08-00500014 B • Bleyl & Associates 1722 Broadmoor k& Suite 210 Project Engineering & Management Bryan, TX 77802 A May 19, 2008 City of College Station ATTN: Jason Schubert, Staff Planner P 0 Box 9960 College Station,Texas 77842 RE: REMAX Site Plan Comments Below is a listing of the comments received May 9, 2008 regarding the site plan for the referenced project. Following each comment is our response in italics. PLANNING 1. In calculating the number of required parking spaces, fractional spaces round up. With the increase in building size, please revise the required number from 48 to 49. This has been changed. 2. Repeat Comment: There are additional PUEs being dedicated with the final plat that are not illustrated on the site plan. Please contact Kerr Surveying LLC (who is working on the plat) at 268-3195 to obtain this information. A 20' PUE along the possible location of the TxDOT right of way, a 15'PUE for the proposed fire hydrants, and a 10' PUE along the rear have been added as shown to coincide with the Final Plat. 3. Repeat Comment: Please show easements (including those to be added) above all other layers. It appears the 7.5-foot easement along the eastern property line is shown below the parking layer. A line has been added. 4. It appears that the revisions for a handicap accessible route from the building to the right-of- way are insufficient. Staff originated this comment so that the site could accommodate it, knowing State regulations will require it when building plans are submitted to them and that it is best to address this now than in the middle of construction. Staffs understanding of the requirements includes ramps, striping across drive aisles and a sidewalk stub to the right- of-way, all of which are to meet ADA requirements. It appears that these revisions will also cause changes to the proposed grading and landscaping. As established at our meeting on May 12, this was coordinated between the Owner and Mr. Hare. We have added a 3'wide striped walkway outside of the curb and first parking space of the middle island. All striping and construction shall be in conformance with TDLR requirements. 5. Please note that a complete set of constructions documents includes the landscape plan as well. Noted. 6. Please note that any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and 'bubbled" on Bryan Austin Conroe (979)-268-1125 (512)-328-7878 (936)441-7833 (979)-260-3849 (512)-328-7884 Fax (936)-760-3833 Fax your plans, Any additional changes on these plans that the City has not been made aware of will constitute a completely new review. Noted. ENGINEERING COMMENTS NO. 5 1. The Fire Marshall's Office will not accept the proposed fire hydrant spacing, due to obvious functionality issues. Please revise to the layout previously discussed in our meeting, which placed the hydrant at the northwest corner of the parking lot adjacent to the internal fire lane. The fire hydrants have been moved. Their present location was shown to, and approved by, the CoCS Fire Marshall. 2. FYI -The Full Development Permit for this project will not be issued until the proposed lift station proposal has been approved. Noted. I have included the latest documentation sent to David Coleman for your use. I have bubbled all information that has been changed without comment from the City. These items include: 1. Removed sidewalk from center island. 2. Reduced the center island square footage by 54 square feet (3' x 18') to accommodate ADA walkway. 3. Removed reference to offsite lift station, added a short landscaping wall, and removed all grading from inside of Veteran's Park. 4. Added a private grinder station at the rear of the building and re-routed the sanitary sewer service lines. Finally, a revised opinion of cost for the proposed fire hydrants is included. Ple.se do not hesitate to call if you have any questions about this submittal. • I erely, !/ j\k14,17 Sam J. - non, P.E. Project Engineer Grrffil1115441 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570/ Fax 979.764.3496 MEMORANDUM May 23, 2008 TO: Sam Vernon, Bleyl &Associates, via fax 260.3899 V FROM: Bridgette George, Development Coordinator SUBJECT: Engineering Document Comments No. 6 for Remax Site Plan Staff reviewed the above-mentioned engineering documents as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review and approval of the plans: $200 Plan Review Fee (This is the sixth and final review for this round of reviews. Please submit the $200 review fee for the next round of three reviews.) One (1)sets of revised construction documents. Sanitary sewer force main plan and profile drawings. If you have any questions or need additional information, please contact Carol Cotter or Erika Bridges at 979.764.3570. Attachments: Staff review comments pc: Time Ware, via fax 764.767 Case File No. 08-500014 B Bleyl & Associates Y 1722 Broadmoor Suite 210 iiiiik A Project Engineering & Management Bryan, Tx 77802 June 2, 2008 Carol Cotter City of College Station P 0 Box 9960 College Station, Texas 77842 RE: REMAX Site Plan Comments Below is a listing of the comments received May 23, 2008 regarding the site plan for the referenced project. Following each comment is our response in italics. 1. Plan and profile drawings for the proposed sanitary sewer force main need to be submitted for approval. The plan and profile for the force main has been added to Sheet 2 Utility Plan. 2. Please provide a detail for the proposed grinder pump. Shop drawing for the proposed station are included. 3. The 2-inch water service line needs to be removed from the 7.5' PUE. The water service has been moved. 4. Please label the proposed PUE for the sanitary sewer force main. This has been labeled. 5. Please ensure that no portion of the private grinder pump is located within the 10' PUE. Noted. No portion of the station lies inside of the easement. 6. FYI - The final plat cannot be filed for record until the grinder pump lift station and sanitary sewer force main have been constructed and accepted. Noted. Please do not hesitate to call if you have any questions about this submittal. incerely, Sam J. ernon, P.E. Project Engineer a- 14 collos ci : Lic iic Bryan Austin Conroe (979)-268-1125 (512)-328-7878 (936)-441-7833 (979)-260-3849 (512)-328-7884 Fax (936)-760-3833 Fax (41/11115111111114 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM June 10, 2008 TO: Sam Vernon, Bleyl & Associates, via fax 260.3849 FROM: Jason Schubert, Staff Planner SUBJECT: REMAX (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of revised construction documents. If there are comments that you are not addressing, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Tim Ware, via fax 764.7676 Case file #08-00500014 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. I of 2 Print Form ( )IAA ' Grfirs" PLANNING & DEVELOPMENT SERVICES qii°2 CITY OF COLLEGEST.91'1ON TRANSMITTAL COVER LETTER 0%, 14 Please check one of the options below to clearly define the purpose of your submittal. r Documents for a previous incomplete submittal [Existing Project Submittal Project Name: 3O 50 litiY%k e``j/'1 — `A— Contact Name: ( -7;4.4 WA-/ii Phone No.: f 3 Z‘,/ We are transmitting the following for Planning & Development Services to review and comment. (Please check all that apply). E Comprehensive Plan Amendment [Non-Residential Architectural Standards r Rezoning Application r Irrigation Plan [Master Development Plan [Variance Request r Preliminary Plat r Development Permit C Final Plat C Conditional Use Permit [Development Plat r FEMA CLOMA/CLOMR/LOMA/LOMR C Site Plan [Grading Plan r Special District Site Plan [Other- Please specify below ✓Special District Building /Sign itandscape Plan INFRASTRUCTURE AND ENGINEERING DOCUMENTS All infrastructure documents must be submitted as a complete set. The following are included in the complete set: r Waterline Construction Documents T TxDOT Driveway Permit r Sewerline Construction Documents ✓TxDOT Utility Permit r Drainage Construction Documents C Drainage Letter or Report [ Street Construction Documents E Fire Flow Analysis [ Easement Application [Other- Please specify Special Instructions: APel/. lJ /rr" °/V/41/21AS 29-Aug-08 CITY OF COLLEGE STATION Planning d Development Services 1101 Texas Avenue,P.O. Box 9960 College Station,Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 November 20,2008 Tim Ware 2417 E.Briargate Bryan,Texas 77802 RE:Property located at 3030 University Drive East;Lot 1,Block 1 Ware Addition Dear Mr.Ware: This letter is to inform you that the above referenced property has received an administrative adjustment of two (2) parking spaces from the number of spaces required by the Unified Development Ordinance, Article 7,Section 2, Off-Street Parking Standards (a 4%adjustment). According to the Unified Development Ordinance Section 3.15, the Administrator has the authority to authorize adjustment of up to 10 percent from any numerical zoning standard set forth in Articles 5, 6, or 7 of the Unified Development Ordinance. To approve the application for an administrative adjustment, the Administrator shall make an affirmative finding that specific criteria, as outlined in Section 3.15.E of the Unified Development Ordinance,have been met. The Administrator has found that: Granting the adjustment will ensure the same general level of land use compatibility as the otherwise applicable standards because the amount of the adjustment is negligible and will not significantly alter the intensity of the land use; Granting the adjustment will not materially or adversely affect adjacent land uses or the physical character of uses in the immediate vicinity of the proposed development because the land use is confined to one lot;and Granting the adjustment will be generally consistent with the purposes and intent of this UDO owing to the fact that the reduction of two parking spaces is negligible. If you have any questions,please feel free to call me at 979.764.3570. Sincerel „7. B bCow P Director,Planning and Development Services CC: File# 08-00500143 E-mail Correspondence From: "Sam Vernon" <svernon@bleylengineering.com> To: <jschubert@cstx.gov> CC: "'Josh Norton" <Jnorton@cstx.gov> Date: 4/16/2008 3:39 PM Subject: ReMax Site Plan Good Afternoon Jason! Tim Ware has directed us to make some changes to the site plan on his building. I believe you and he have talked about most of these, but they include: 1. Moving the parking lot east 3.5 feet 2. Deleting the dumpster pad in the front 3. Moving fire hydrants into existing easements We were very close to getting an approval last time. My question is, how would you like me to handle this resubmittal? It would be a lot to bubble out, but we can do it, or would you rather me write a letter explaining all changes and leaving the clouding off? We were down to submitting 7 sets for stamping, 2 site plans, and 1 landscaping plan, and an 11x17 erosion control sheet. Do you think it would be best to hold off on submitting the seven sets until you and Josh have had a chance to look at these new changes? I'd appreciate any direction you can give me. Thanks, Sam J. Vernon, P.E. Bleyl &Associates 1722 Broadmoor, Ste. 210 Bryan, TX 77802 Tel. (979) 268-1125 Fax (979) 260-3849 svernon@bleylengineering.com From: Jason Schubert To: Vernon, Sam CC: Norton, Josh Date: 4/17/2008 1:48 PM Subject: Re: ReMax Site Plan Sam, I agree with you that it would be a lot to bubble. I'm not the biggest fan of bubbling because it clutters up the site plan sometimes. A letter explaining the changes will suffice. If there are a lot of change still, it probably is best to only submit one set of documents. I have not heard of the progress on the lift station but those plans and easements will need to be worked out before the site plan can be approved and a full development permit issued. Josh also wanted to pass on some other things that he has identified: 1. Please revise construction cost estimate. 2. The easement dedication application that was submitted was not complete, as none of the required supporting documentation was included. This documentation will need to be submitted prior to issuance of a full development permit. 3. Prior to any off-site grading, we will need documentation from the Parks Department verifying their approval of the proposed grading. 4. The Full Development Permit for this project will not be issued until the proposed lift station proposal has been approved. 5. The Full Development Permit for this project will not be issued until the TxDOT Permit has been approved. As you may know, Tim has submitted a preliminary plat for this property since it actually appears that the property was not included with Veterans Park final plat when it was filed. Adding that to the list, the final plat will need to be filed before the site plan could be approved. If the lift station details are still being worked out, this may actually be advantageous since you could dedicate easements through the plat and wouldn't have to dedicated them by separate instrument (which frequently takes a while to work through). Hopefully this helps clarify some things. Let me know if you have any questions. Jason Schubert, AICP Staff Planner Planning & Development Services City of College Station tel: 979.764.3570 fax: 979.764.3496 www.cstx.gov >>> "Sam Vernon" < svernon@bleylengineering.com > 6/12/2008 11:44 AM >>> Good Morning Erika! We have gotten casing/spacer information this morning and are revising our plans. The casing size we will use is 5" min inside diameter steel with a 3/8" wall thickness. APS and PSI both make an HDPE casing spacer for this application. We can get the 3.5' of clearance under the flowline of the creek, so we will not be needing a concrete cap. I will bring these drawings over this afternoon as we discussed. In our comment letter, you requested a single set of revised plans, anticipating that these will be approved, may I bring the.entire 7 sets for stamping? Sam J. Vernon, P.E. Bleyl &Associates 1722 Broadmoor, Ste. 210 Bryan,TX 77802 Tel. (979) 268-1125 Fax (979) 260-3849 From: Erika Bridges To: Vernon, Sam CC: Cotter, Carol; Schubert, Jason Date: 6/12/2008 4:41 PM Subject: Re: ReMax Site Plan Sam, Unfortunately I was incorrect when I said we could probably issue the DP today. For some reason I was thinking that the plat had already been filed, but I apologize for not verifying that before I spoke. There are still a couple of outstanding issues that are holding things up: 1) City Council needs to vote on whether or not an easement for the force main will be permitted through Veterans Park(Council will vote on this tonight). 2)The plat is not scheduled to go to P&Z until next Thursday, June 19th. In order to issue the DP and approve the plans, we need a filed plat. You are welcome to bring the plans in for stamping, and I will be happy to hold onto them. Please call me if you have any more questions regarding the development permit. Thanks, Erika Bridges, EIT Graduate Civil Engineer Department of Public Works ******************** City of College Station 1101 Texas Ave. Phone: 979.764.3570 Fax: 979.764.3496 www.cstx.gov ******************** From: Josh Norton To: Vernon, Sam Date: 6/18/2008 3:07:56 PM Subject: Remax CC: Schubert, Jason Sam, I reviewed the Remax site plan submittal today. Everything looks fine with the exception of the force main encasement. This encasement needs to meet the minimum standard in the BCS Design Guidelines for Below Grade Crossings on Page 8 of the Sanitary Sewer section. If you would like you can come by and red-line these sheets as not to have to re-submit. Please check with Jason to verify there are not additional planning comments that need to be addressed. Thanks -Josh Norton Sam Vernon From: David Coleman [Dcoleman@cstx.gov] Sent: Wednesday, May 14, 2008 8:26 AM To: svernon@bleylengineering.com; Spencer Thompson; Tim Ware Subject: Re: Fwd: FW: REMAX SAN SWR EXHIBIT All - This route looks great, and since we already estimated the "easement" would be one- third acre (for purposes of the newpaper ad), then really the most useful info would be the length of the force line that's on City property, that way we can decide the width and calculate the area. Thanks much, Dave David M. Coleman, PE City of College Station Director, Water Services Department 979.764-3432 or cell 979.574-6128 >>> Spencer Thompson 05/13/08 11:50 AM >>> Sam, I think that looks great. Can you add a note: Easement Area Aprox. sqft. I think that'll do it unless Dave has something to add. thx st College Station. Heart of the Research Valley. 1