Loading...
HomeMy WebLinkAboutWater Report WATER SYSTEM FLOW TEST REPORT AS-BUILT VERIFICATION DATE: 11-6-07 WATER SYSTEM OWNER: WELLBORN SPECIAL UTILITY DISTRICT DEVELOPMENT PROJECT: HIDDEN SPRINGS SUBDIVISION, PHASE 1 FLOW TEST LOCATION: CORNER OF HIDDEN SPRINGS WAY & TRIPLE RIDGE DRIVE NOZZLE SIZE: 2.5" DISCHARGE COEF: 1.0 PITOT READING(psi): 58 FLOWRATE FORMULA: Q=29.84cd2pm C = discharge coe£ D =orifice size (in) P=pitot pressure (psi) FLOWRATE (Rpm): 1280 (computed) PRESSURE GAUGE LOCATION: FIRE HYDRANT AT THE INTERSECTION OF HIDDEN SPRINGS WAY AND FIELD STONE LANE STATIC PRESSURE: 70 psi RESIDUAL PRESSURE: 53 psi // REPORT PREPARED BY: �4a mit JEF L. ROBERTSON (printed name) OTHERS PRESENT: STEVEN CAST (WELLBORN SUD)