Re: National Tire & Battery (SP) -07-00500022
Site Plan Submittal
Dear Crissy,
Attached are the following items for the National Tire & Battery site plan submittal.
• "Three (3) Copies of Architectural Drawings
• One (1) Copy of Civil Drawings—p'
• One (1) Revised Site Plan
• One (1) Landscape Plan & Irrigation Plan
• ,Building Permit Application
• Easement Dedication Sheet
• Brick & Color Samples
• Colored Elevation Drawings
• VTDLR Application
STAFF REVIEW COMMENTS NO. 1
PLANNING
,/Question:
This application is considered an incomplete submittal; however, at the applicant's request
we have reviewed the site plan and made the following comments. This will count as one
review.
Answer:
Understood
/Question:
This site plan cannot be approved until the plat has been filed.
Answer:
Acknowledged
511 UNIVERSITY DRIVE EAST,SUITE 204• COLLEGE STATION,TX 77840• T. 979.260.6963• F 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
Question:
Parking requirements for motor vehicle service and offices are calculated separately for this
type of use. Vehicle service areas require 1 space per 200 s.f. and office areas require 1
space per 250 s.f. Please separate out the uses on the plan and recalculate the parking
requirements.
Answer:
We have recalculated the parking requirement as requested. We have also calculated the
tire storage areas as warehouse requirements.
Question:
Please dimension the island strip along the 20 parking spaces to verify that the interior
island requirement is being met. Staff estimates that 432 square feet of interior island is
required for this site.
Answer:
This area has been dimensioned.
Question:
Please submit building elevations, including square footages of the materials and colors
used on the building.
Answer:
Attached
Question:
Because the access easements will be constructed with this development and landscaping
will not be provided, please add a note to the site plan that reads: "The area within the
access easements will be included in the calculations for landscape points with the
development of Lot 13."
Answer:
See site plan note #9
Question:
Please allow more time for the fire department to provide comments.
Answer:
Understood, please let us know if they have any comments with this round of review.
LANDSCAPING/STREETSCAPING PLAN
Question:
Please submit a landscape plan. Additional review of these plans outside of the three
allowed reviews will require an additional site plan review fee.
Answer:
Attached. We understand that we will have to pay an additional fee if we go over our
allowed 3 reviews and we have already used 1 .
MISCELLANEOUS
Question:
Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced
Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as
per City Ordinance 2394.
Answer:
Understood
Question:
All Back Flow devices must be installed and tested upon installation as per City Ordinance
2394.
Answer:
Understood
ENGINEERING COMMENTS NO. 1
Question:
Site Plan cannot be approved until Property is platted.
Answer:
Acknowleged
Question:
As proposed, Site Plan cannot be approved until water and sewer are constructed to serve
this lot.
Answer:
Acknowleged
Question:
Show limits of PUE's for public water and electric proposed with this project.
Answer:
Now shown on the site plan.
Question:
Show all existing and proposed PUE's. Provide volume and page numbers of existing.
PUE's to be dedicated plat can be noted as such or the volume and page numbers provided
once Plat is filed.
Answer:
This has been shown.
Question:
Temporary Blanket Easement or actual PUE's are required for the Site Plan approval.
Submit Easement dedication documents.
Answer:
Attached
Question:
Add note on the plans that fire suppression lines shall have a lockable lid on the isolation
valve. The lockable lid shall, at a minimum supply protection as the AMP or USA, LL562
Locking Lid. Alternate lockable lids shall be approved by College Station Utilities Director
or his designee.
Answer:
See note on Sheet 02 on 6" waterline profile.
Question:
Show limits of structural fill on plans.
Answer:
See embedment details and general construction note # 5 on Sheet 01 .
Question:
Provide Engineers estimate for public water main.
Answer:
Attached
Question:
The "Typical Water and Sewer Trench Detail" provided does not match BCS Unified.
Please provide letter for our review stating why it is better, or use standard.
Answer:
We changed to use the B/CS standard detail.
Question:
Submit Drainage Report/Letter. Also, ensure that appropriate velocity dissipation is
provided for resulting discharge velocities.
Answer:
Attached
ELECTRICAL COMMETS REQUIRING IMMEDIATE ATTENTION
Question:
Developer provides easements for electric infrastructure as installed for electric lines
(including street lights)
Answer:
Acknowledged
GENERAL ELECTRICAL COMMENTS
Question:
Developer installs conduit per City specs and design.
Answer:
Acknowledged
Question:
City will provide drawings for conduit installation.
Answer:
Acknowledged, please send the drawing and we will attach in our set.
Question:
Developer provides 30' of rigid or IMC conduit for riser poles, City installs riser.
Answer:
Acknowledged
Question:
Developer pours transformer pad(s) per City specs and design.
Answer:
Acknowledged
Question:
Developer installs pull boxes as per City specs and design (pull boxes provided by the City).
Answer:
Acknowledged
Question:
Developer provides digital AutoCAD 2000 or later version of plat and/or site plan. Email
to: sweido@cstx.gov
Answer:
The drawing will be sent to Sam Weido.
Question:
Developer provides load data for project.
Answer:
This data will be sent to Sam Weido.
Question:
To discuss any of the above electrical comments please contact Sam Weido at
979.764.6314
Answer:
Thank You!
SANITATION
Question:
Sanitation has no issues with this project.
Answer:
Thank You!
Ple.se let us know if you have any questions.
Si - erely, r' ___,
Veronica J. M gain, P.E., C.F.M.
Managing Part r
Cc. File
Hi Gina,
As per our conversation I have enclosed 2 different locations.The motel will be
Any were from 78 to 83 rooms.
Sincerely,
Gene pillai 12/08106
SU4'ht 23 nay
5505 So. General Bruce Dr
Temple, TX 76502
6'd LZ9 6-8LL (1792) lePLI d017ti0 90 90 080
MITCHELL
MM 3 a�
MORGAN
March 12, 2007
Crissy Hartl
City of College Station
Development Services
PO Box 9960
College Station, TX 77842
Re: National Tire & Battery (SP) -07-00500022
Site Plan Submittal
Dear Crissy,
Attached are the following items for the National Tire & Battery site plan
submittal.
Dear Crissy,
Attached are the following items for the National Tire & Battery site plan
submittal.
• One (1) revised site and landscape plan.
• One (1) revised set of civil plans.
• One (1) copy of the drainage supplement.
• One (1) copy of the Corporate Filing with the State of Texas
• One (3) revised set of architectural drawings
STAFF REVIEW COMMENTS NO.2
PLANNING/LANDSCAPE PLAN COMMENTS
Question:
Staff has no comments for the site plan
Answer: Thanks! We like this comment!!!
Question:
Only one type of architectural element (pilaster) was provided along Façade B
and in the first 60' along the Facade D. Please provide an additional element to
511 UNIVERSITY DRIVE EAST,SUITE 204• COLLEGE STATION,TX 77840• T 979.260.6963• F 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES• STREETS• SITE PLANS• SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
satisfy the Non-Residential Architectural Standards. Suggestion: Extending the
projection along Façade B to 4-feet would satisfy this requirement.
Answer:
On Façade "B", "C" and "D" awnings were added to satisfy the articulation and
architectural element requirements.
Question:
According to Section 7.5D Streetscape Requirements, 300 additional points shall
be required for every 50 linear feet of frontage on a right of way. This site has
approximately 233' of frontage on State Highway 6 which results in an additional
1,398 landscaping points. The total number of landscape points required for this
site is 5,084 points. Please revise the plan accordingly.
Answer: As discussed we have discounted approximately 80 linear feet of
frontage from the streetscape requirements because we are allowed to discount
undeveloped floodplain from our calculations. Therefore utilizing only 157 linear
feet toward these calculations.
Question:
Please clearly illustrate the property lines on the landscape plan and dimension
the lengths of each line.
Answer: These lines have been clarified and dimensions written.
Question:
Streetscaping will be required for this site because it has 233' of frontage along
State Highway 6. The trees need to be planted on the site within 50' of the
property line. Please provide streetscaping calculations in the legend and verify
that the requirement is being met.
Answer: As discussed we have discounted approximately 80 linear feet of
frontage from the streetscape requirements because we are allowed to discount
undeveloped floodplain from our calculations. Therefore utilizing only 157 linear
feet toward these calculations.
Question:
Please be aware that the required buffer plantings cannot be counted towards
the required landscape points. Please provide a separate legend of the
calculation and the required plantings. Also be aware that buffers will be required
along every property line that bounds property R-1 Single Family Residential. In
this case, buffers would be required along the north and west property lines.
Answer:
We have added the buffer plantings per section 7.6 (f) 4 (b) to meet these
requirements. We will be appealing the decision to require these plantings to the
DRB.
Question:
Staff noted that the calculated points for 96 Buford Hollies was incorrect. Please
adjust the plan accordingly.
Answer: This has been corrected.
ENGINEERING COMMENTS NO.2
Question:
Provide documentation that adjacent property owner (Lot 13) is acceptable to the
proposed grading on his property.
Answer: This documentation is forthcoming from Posadas. We understand that
you cannot stamp the plans until you receive this data. We will forward as soon
as we have it.
Question:
Easement dedication needs copy of filed plat and corporate resolution
Answer: A copy of the corporate paperwork is attached. The signed plat to be
filed for record is forthcoming from Posadas owner. As soon as we have this
mylar we will submit it to you.
Question:
Need your opinion as to impacts from increased drainage runoff in drainage
letter. (No negative impacts?)
Answer: Please see attached drainage report supplement.
Question:
Provide velocity appropriate permanent erosion control at stormwater outlets.
Answer: There is some rip rap at the stormwater outfalls, but we have added
additional on the plans.
Question:
Access easements are private, not public. Make sure revised Mylar indicates so.
Answer: We have corrected this notation on the plans and the mylar is silent to
this. The mylar simply indicates it as a PAE so we will clarify this and define PAE
in the legend as a Private Access Easement.
Question:
Add additional gate valve to southeast leg of fire hydrant tee.
Answer: This additional gate valve has been added.
Question:
Why the bend in the 12" storm sewer pipe? Can it be easily unclogged at the
distance from inlet/junction box?
Answer: The bend has been removed.
Question:
Be aware that all disturbed areas will be required to have vegetation
reestablished prior to full CO, including adjacent property.
Answer: Understood, please see note #9 on sheet 01 which covers this item.
Please let us know if you have any questions.
Si -rely,
Veronica J.131. ! or., :n, P.E., C.F.M.
Managing Partner
Cc. File
ri_... ,,
MITCHELL 4a3- 1
MM
qg
MORGAN
April 22, 2007
Crissy Hartl
City of College Station
Development Services
PO Box 9960
College Station, TX 77842
Re: NTB Resubmittal
Dear Crissy & Carol,
Attached you will find a revised submittal for NTB. During the bidding of the project there was
concern regarding the added construction cost of the rear driveway. My client asked that we try to
redesign the site to eliminate this driveway. This drive will be constructed as a drive aisle in the
future by the adjacent user to the south. To accomplish the elimination of this rear driveway, we
have added a new fire lane that loops back around the parking stalls. To meet truck turning radii
we had to lose two parking stalls, increase the island radius and add pavement on the southwest
end to accommodate the rear wheels of the 18-wheel trucks that will be delivering the tires.
We understand that this layout is a change and that we have already used our three reviews for the
previous submittal. Because of this we are submitting a new application and application fee.
The following is enclosed:
• $200 application fee
• Site plan application
• Fourteen (14) folded copies of site plan
• A copy of the site plan check list
• One (1) folded copy of the landscape plan
• One (1) full set of construction drawings
If y. have any questions please feel free to give me a call.
Sin•: ely, �/
'
r
1 - � r'
Veronica J.B. I.' •an .E.
Managing Part -r
Cc: Carol Cotter
Haynes Peery, Pavilion Development
Michael McDonald, Pavilion Development
Doug Patterson, Corinth Properties
Frank Mihalopoulas, Corinth Properties
511 UNIVERSITY DRIVE EAST,SUITE 204• COLLEGE STATION,TX 77840• T. 979.260.6963• F 979.260.3564
CIVIL ENGINEERING • HYDRAULICS• HYDROLOGY • UTILITIES• STREETS• SITE PLANS• SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
14 ((--,
MITCHELL
MM
MORGAN 1 �
May 3, 2007
Crissy Hartl
City of College Station
Development Services
PO Box 9960
College Station, TX 77842
Re: National Tire & Battery (SP) —Site Plan
Dear Crissy,
Attached are the following items for the National Tire & Battery site plan
submittal.
• Seven (7) complete sets of construction documents fro the proposed
development with the revised site and landscaping plans attached.
• Two (2) revised site plans
• One (1) landscaping plan
• One (1) 11X17 grading and erosion control plan
STAFF REVIEW COMMENTS NO. 3
PLANNING/LANDSCAPING
Question:
Please add a note to the site plan that states the following regarding signs: "All
signs to be permitted separately."
Answer:
Noted
Question:
According to UDO Section 7.5.D.5 parking screening shall be provided along
parking areas that are adjacent to a right-of-way. Please provide 10 shrubs for
every 30' of parking along the SH 6 right-of-way.
Answer:
See attached landscape plan.
511 UNIVERSITY DRIVE EAST,SUITE 204• COLLEGE STATION,TX 77840• T. 979.260.6963• F. 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES• STREETS• SITE PLANS• SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
Question:
Per our phone conversation on April 30, please indicate that the area along the
Lot 13 and 14 property line as island space and disperse the landscaping
throughout the site. Please revise the landscaping plan as needed.
Answer:
Noted
Question:
Engineering comment: Please provide a letter from Posados regarding grading
on the adjacent property.
Answer:
Attached please find the agreement between the two property owners.
Question:
Please note that any changes made to the plans, that have not been requested
by the City of College Station, must be explained in your next transmittal letter
and "bubbled" on your plans. Any additional changes on these plans that the
City has not been made aware of will constitute a completely new review.
If you have any questions, please feel free to call me at 620-6963.
Sincerely,
ames T. Batenhorst, P.E.
Civil Engineer
Page 1 of 1
James—Per my telephone conversation with you this afternoon, I have attached copies of our Reciprocal
Easement Agreement and First Amendment to the REA between Posados and Gateway Six Partners. Reference
is made to Article 2 of the REA and Articles 2 & 3 of the First Amendment to the REA. These two references
clearly denote the right granted to us proceed with the construction of the grading and paving work necessary for
the construction of the driveway for access to Lot 14 (Developer's Parcel/NTB Site). These agreements should
clearly provide evidence to the City that we have the right for the construction of the driveway and will allow the
City to release the Site Development Permit.
I will also be by your office tomorrow morning to pick-up the two sets of updated permit/construction drawings for
the NTB site. Call me if you have any questions. Thanks -
Doug Patterson