MEMORANDUM
March 12,2007
•
TO: Brett McCully,Bleyl&Associates via fax# 979.260.3849
FROM: Crissy Hard,Staff Planner
SUBJECT: MID SOUTH BANK(SP) - Site Plan
Staff reviewed the above-mentioned site plan ments on the site plan or
engineering documents. Please submit the follow - ktb. royal:
Seven (7) complete sets of cons osed development with the
revised site and landscaping p . returned to you, please
submit additional copies if yo
d set)
iff
Two (2) revised individual site p.
One (1) landscaping plan
One (1) 11x17 grading and erosic
ja 1( -r E SBA professionalUSSD
RArchtte
ActuSrSal°CCoripoAration)
Easement Dedication Sheet and
JAMES K. BROUSSARD,AIA
Architect
If you have any questions or need additional infori ;570.
1023 East St.Mary Blvd.
Attachments: Staff review commentsP.O.Box 5351.7.
Lafayette,Louisiana 70505-3517
(337)235-5004 Fax(337)235-5089
james.bajbaarchitect.com
cc: H.E. Butt Grocery Company,PO Box 839111111.0.1.11.1111.1111
James Broussard,via fax# 337.235.5089
Case file#07-00500020
Home of Texas A&M University
Adak, James
r;10, I BROUSSARD & ASSOCIATES
(A Professional Architectural Corporation)
Ms. Crissy Hart
City of College Station
Planning&Development Services
P. 0.Box 9960
College Station,Texas 77842
979-764-3570
RE: MidSouth Bank(SP)—Site Plan
Staff Review Comments No. 2
College Station,TX
Dear Ms.Hart:
The following is our response to your memo dated February 19,2007 and changes have been made to our
documents.
PLANNING AND LANDSCAPING/STREETSCAPING:
1)Please dimension three queing spaces for the ATM window on the north side of the building and verify that this
requirement as well as other standards,such as drive-aisle widths,is also being met.
Three queing spaces are shown,all with dimensions at the ATM location.Four queing spaces are shown,all
with dimensions at the Teller Drive Thru location.The drive aisles are designed meeting the manufacture's
requirements.
Re: Sheet C1.02
2) Staffs calculation of the proposed landscaping points indicated that 5,672 points were proposed as opposed to the
5,822 points on the legend. Please verify.
Re: Sheet L2
3) Staff was only able to verify that 15 street trees were being provided within 50'of the property line along the two
thoroughfares. Please provide an additional two canopy trees along the streets. As a reminder,two non-canopy may
be substituted for one canopy tree.
Re: Sheet L2
4) Staff noticed that the dumpster is located on an easement. Please be aware of the following and add a note to the
site plan that states that if utilities need to be accessed within the easement and the dumpster enclosure needs to be
removed,that it will be the owner's responsibility to repair or replace the structure. Additionally,please keep the
structure at least 5 feet away from the manhole to provide a workspace.
The dumpster has been relocated meet the requested(5)five feet distance from the manhole to structure.The
requested note has been added to the site plan.
Re: Sheet C1.02
P. 0. BOX 53517 LAFAYETTE, LOUISIANA 70505-3517 PH.: (337) 235-5004 FAX: (337) 235-5089
NON-RESIDENTIAL ARCHITECTURAL COMMENTS:
1) Per Section 7.9 NRA Standards,two architectural elements are required on facades facing a public ROW for
every 45'horizontal feet. This standard applies to the facades facing Texas Avenue(east)and Holleman Drive
(south). Additionally,two architectural elements are required on all other facades for every 60'horizontal feet
(north and west). Please find evaluations of each façade below and revise the building plans as necessary:
a. East elevation: Staff counted the wall plane projection as two elements,but it is still lacking two
required elements. Canopies over the windows would satisfy this requirement.
Canopies have been added to the east elevation.
Re: Sheet A3.01
b. South elevation: Staff counted the canopy and wall plane projection as two elements,but it is still
lacking two required elements.
Canopies have been added to the south elevation.
Re: Sheet A3.01
c. West elevation: Staff counted the canopy as one element out of the two required elements. Extending
the teller window projection to 4'would satisfy this requirement.
A canopy over the reader board has been added to the west elevation.
Re: Sheet A3.01
d. North elevation: Staff counted the canopy as one element out of the two required elements. Please
provide another architectural feature.
Canopies have been added to the north elevation.
Re: Sheet A3.01
2) Please provide a sample of the proposed roof material to verify that it is either copper or silver metallic as
required by the UDO.
Color samples and materials will be submitted.
3) Please be aware that all signs will be permitted separately.
We are aware and addressed this issue on the previous comments from your department.
ENGINEERING COMMENTS NO. 1
1) A 4-in. sanitary sewer service line requires a 1%slope,please illustrate.
Re: Bleyl&Associates response dated February 26,2007
2) Please provide water and sewer demands and specify size of water meters.
Re:Bleyl&Associates response dated February 26,2007 and M&E Consulting,Inc. response.
3) Please illustrate proposed location for the domestics and irrigation meter. These meters need to be located within
an easement. It appears the proposed meter location is outside of an easement,please dedicate.
Re:Bleyl&Associates response dated February 26,2007 and M&E Consulting,Inc.response.
4) Please dedicate an easement for any on-site public utility that are not already located in an easement.
Re:Bleyl&Associates response dated February 26,2007.
5) Please illustrate canopy height on site plan.
Canopy has been noted on the site plan.
Re: Sheet C1.02
6) Please label the existing water service/fire line to be removed.
Re: Bleyl&Associates response dated February 26,2007 and M&E Consulting,Inc.response.
7) Fire Flow: The fire flow report is needed to verify the number of hydrants required per tables B105.1 and
C105.1 of the fire code,using the proposed square footage and building material type,please submit.
Re:Bleyl&Associates response dated February 26,2007.
8) Drainage Report: It appears from the grading plan that the existing and proposed contours are very similar,I
assume the overall drainage pattern for the proposed site will remain the same as the existing site,please verify.
Re:Bleyl&Associates response dated February 26,2007.
9) Please submit development permit and fees.
Re:Bleyl&Associates response dated February 26,2007.
Please call our office should you need any additional information.
Sincerely,
Ronald Ayo—Assoc. AIA
ronald.a@jbaarchictect.com
James Broussard&Associates
(A Professional Architectural Corporation)
337-235-5004
RJA/rja
Enclosures
CC: MidSouth Bank
F.D.Freeman Associates,Inc.
Bleyl&Associates
M&E Consulting,Inc.
,. • ,
I I I M 4' E CONSULTING, INC.
MI A PROFESSIONAL ENGINEERING CORPORATION
m= 1304 BERTRAND DRIVE • SUITE A6
MI LAFAYETTE.LOUISIANA 70506
MN „ i3:3•fl 234-7474 • FAX(337)234-7774
--- .... ......--- www.meconsulting.corn
February 26, 2007
James Broussard
James Broussard & Associates
P.O. Box 53517
Lafayette, LA 70505-3517
Re: Midsouth Bank -College Station,TX
M&E 06197.00
Dear James:
The following are Mechanical/Electrical responses to the 19Feb07 comments from the City of College
Station.
Engineering Comments
1 Item No. 1:
A. A 4" sanitary sewer service line requires a I%slope-please illustrate.
Response: A slope of 1/8" per foot is specified. Reference Specification 15350.
2. Item No. 2:
A. Please provide water and sewer demands and specify size of water meters.
Response: These are indicated on Drawings M1.01.
3, Item No. 3:
A. Please illustrate proposed location for the domestic and irrigation meter. These
meters need to be located within an easement. It appears the proposed meter
location is outside of an casement. Please dedicate,
Response: These items arc addressed on Drawings M1.01,and in Addendum No. 1.
4. Item No. 6:
A. Please label the existing water service/fire line to be removed.
Response: This is shown on Drawing M1.01 and Note No.2.
_I SCOTTY J. BAUDOIN, RE. JAY BREAUX. RE RICHARD M. LEH LANc L
The following are Mechanical/Electrical responses to the 19Feb07 comments from the City of College
Station.
1. Item No. 1:
A. Provide emergency exterior"Exit Discharge" lighting requirement for all exits to
comply with Section 1006.3#5 of the 2003 IBC.
Response: Emergency lighting will be specified, in the next addendum,at exterior
exits as required.
2. Item No. 8:
A. Submit Lighting and Mechanical Compliance data to comply with the 2003
IECC,
Response: This was submitted. A copy is attached.
-End of Items-
If you need additional information please contact our office.
Sincerely,
410
/
Richard M. LeBlanc
Electrical Project Manager
M&E Consulting,Inc.
!I'4605197`,0t197 02,..pd
(*#"11114
CITY OF COLLEGE STATION
Planning es Development Services
1101 Texas Avenue,P.O. Box 9960
College Station,Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
February 19, 2007
TO: Brett McCully, PE via fax # 260.3849
FROM: Crissy Hartl, Staff Planner
SUBJECT: MID SOUTH BANK (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. The next submittal will be the third
and final review by staff for this round of reviews. If all items have not been addressed on the
next submittal, another $200 processing fee will need to be submitted for the subsequent set of
three (3) reviews. Please address the comments and submit the following information for
further staff review:
One (1) revised site and landscaping plan.
If there are comments that you are not addressing with the revised site plan, please attach a
letter explaining the details. If you have any questions or need additional information, please
call me at 764-3570.
Attachments: Staff review comments
cc: H.E. Butt Grocery Company, PO Box 839999, San Antonio, TX 78283
James Broussard, AIA via fax # 337.235.5089
Case file #07-00500020
= B
Bleyl & Associates 1722 Broadmoor
1. & Suite 210
Project Engineering & Management Bryan, TX 77802
liL
A
: 11111111111114M111. I-r}
CnW7 ,
,,� ka. 1)3
February 26, 2007 '
k
Ms. Crissy Hartl, Staff Planner l ^ ,, ��`
Planning and Development Sevices
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 778420`Y- 'S
RE: Mid-South Bank Site Plan Comment ��
Case #07-005000205
Dear Ms. Hartl,
Following are your planning comments from the February 12 review of the referenced
project. Our resolution is shown next to each comment in italics.
PLANNING AND LANDSCAPING /STREETSCAPING
1. Please dimension three queuing spaces for ATM window on the north side of the
building and verify that this requirement as well as other standards, such as
drive-aisle width, is also being met. Queuing spaces are now shown.
2. Staff's calculation of the proposed landscaping points indicated that 5,672 points
were proposed as opposed to the 5,822 points on the legend. Please verify.
This will addressed by Landscape Architect.
3. Staff was only able to verify that 15 street trees were being provided within 50' of
the property line along the two thoroughfares. Please provide an additional two
canopy trees along the streets. As a reminder, two non-canopy trees may be
substituted for one canopy tree. This will addressed by Landscape Architect.
4. Staff noticed the dumpster is located on an easement. Please be aware of the
following and add a note to the site plan that states that if utilities need to be
accessed within the easement and the dumpster enclosure needs to be
removed, that it will be the owner's responsibility to repair or replace the
structure. Additionally, please keep the structure at least 5 feet away from the
manhole to provide a workspace. A note describing the owner's responsibility
has been added and the structure has been moved.
ENGINEERING COMMENTS NO. 1
ie
. A 4-in sanitary sewer service line requires a 1% slope, please illustrate. The
proposed slope of the pipe is now shown.
Plea - • - .: -nd sewer demands and specify size of water meters. The
•emand ha a add-• an• -eter size called out for the domestic meter. The
Bryan Austin Conroe
(979)-268-1125 (512)-328-7878 (936)-441-7833
(979)-260-3849 (512)-328-7884 Fax (936)-760-3833 Fax
irrigation meter will be located in the same place as the original water meter.
Meter size will be determined by licensed irrigator.
701. Please illustrate proposed location for the domestic and irrigation meter. These
meters need to be located within an easement. It appears the proposed me er
2 locati•• • ide of an easement, please dedicate. A proposed
•edication i , shown.
4. ' - -ge dedicate an easement for any on-site public utility that are not already
located in an easement. A proposed easement dedication is now shown.
Please illustrate canopy height. A note calling out the minimum elevation is now
shown.
Please label existing water service / fire line to be removed. A note has been
0 added.
Fire Flow: The fire flow report is needed to verify the number of hydrants
required per tables B105.1 and C105.1 of the fire code, using the proposed
square footage and building material type, please submit.
Drainage Report: It appears from the grading plan that the existing and
roposed contours are very similar. I assume the overall drainage pattern for the
proposed site will remain the same as the existing site, please verify.
Please submit development permit and fees. These have been submitted.
Please do not hesitate to contact me with any questions, or if you require additional
information.
Sinc- ely,
//9Y1f/
-ttA. M ully, P.E.
Senior En ineer
_ B
Bleyl & Associates 1722 Broadmoor
ilk& Suite 210
A Project Engineering & Management Bryan, TX 77802
/tel
February 26, 2007
Josh Norton
Planning& Development Services `-''
City of College Station
P.O. Box 9960
College Station, TX 77840
Re: Mid South Bank
Supporting Drainage and Fire Flow Information
Josh,
This letter should serve to address comments 7 and 8 of your February 19th comments
regarding this project.
Fire Demand
The proposed building will be approximately 3242 square feet. Based upon the worst
building construction category (Type V-B), IFC Table B105.1 states that only 1500 gpm
would be required. For this flow rate, IFC Table C105.1 allows the use of a single fire
hydrant. Since we are retaining the existing fire hydrant onsite, we believe the fire
demand issue has been resolved.
Developed Drainage
As your comment notes, the existing drainage patterns are being followed to remain
compliant with the latest HEB site drainage analysis. The proposed site also will provide
slightly less impervious area than the existing structures, reducing flow somewhat.
As always, please feel free to contact me shoul,. rou have any further questions, or
comments. i `"`" ,.
At?,
Oen i
&_..��,yy:'t9 Yom° ,¢y r' �'
Sincerely, `' '
B -tt/if
ul , P.E. K.
�r f
Sr. En neer/Branch Manager0,1',:,.2 !:,-'”,m rs c
';:,-, .-L„.,,-,..
Bryan Austin Conroe
(979)-268-1125 (512)-328-7878 (936)-441-7833
(979)-260-3849 (512)-328-7884 Fax (936)-760-3833 Fax
•
Appendix C
FIRE HYDRANT LOCATIONS AND DISTRIBUTION
SECTION C101 SECTION C104
GENERAL CONSIDERATION OF EXISTING FIRE HYDRANTS
C101.1 Scope.Fire hydrants shall be provided in accordance C104.1 Existing fire hydrants.Existing fire hydrants on pub-
with this appendix for the protection of buildings,or portions of lic streets are allowed to be considered as available. Existing
buildings,hereafter constructed. fire hydrants on adjacent properties shall not be considered
available unless fire apparatus access roads extend between
SECTION C102 properties and easements are established to prevent obstruction
LOCATION of such roads.
C102.1 Fire hydrant locations. Fire hydrants shall be pro-
vided along required fire apparatus access roads and adjacent
public streets. SECTION C105
• DISTRIBUTION OF FIRE HYDRANTS
SECTION C103 C105.1 Hydrant spacing.The average spacing between fire
NUMBER OF FIRE HYDRANTS hydrants shall not exceed that listed in Table C105.1.
C103.1 Fire hydrants available.The minimum number of fire Exception: The fire chief is authorized to accept a defi-
hydrants available to a building shall not be less than that listed ciency of up to 10 percent where existing fire hydrants pro-
in Table C105.1. The number of fire hydrants available to a vide all or a portion of the required fire hydrant service.
complex or subdivision shall not be less than that determined
by spacing requirements listed in Table C105.1 when applied to Regardless of the average spacing,fire hydrants shall be 10-
(
fire apparatus access roads and perimeter public streets from cated such that all points on streets and access roads adjacent to
which fire operations could be conducted. a building are within the distances listed in Table C105.1.
TABLE C105.1
NUMBER AND DISTRIBUTION OF FIRE HYDRANTS
AVERAGE SPACING MAXIMUM DISTANCE FROM
ARE-FLOW REQUIREMENT MINIMUM NUMBER BETWEEN HYDRANTS'b'` ANY POINT ON STREET OR ROAD
(gpm) OF HYDRANTS (feet) FRONTAGE TO A HYDRANTa
—�� 1,750 or less 1 500 250
•2,000-2,250 2 450 225
2,500 3 450 225
3,000 3 400 225
3,500-4,000 4 350 210
4,500-5,000 5 300 180
5,500 6 300 180
6,000 . 6 250 150
6,500-7,000 7 250 150
7,500 or more 8 or moree 200 120
For SI: 1 foot=304.8 mm,1 gallon per minute=3.785 Um.
a. Reduce by 100 feet for dead-end streets or roads.
b. Where streets are provided with median dividers which can be crossed by fire fighters pulling hose lines,or where arterial streets are provided with four or more
traffic lanes and have a traffic count of more than 30,000 vehicles per day,hydrant spacing shall average 500 feet on each side of the street and be arranged on an al-
ternating basis up to a fire-flow requirement of 7,000 gallons per minute and 400 feet for higher fire-flow requirements.
c. Where new water mains are extended along streets where hydrants are not needed for protection of structures or similar fire problems,fire hydrants shall be pro-
vided at spacing not to exceed 1,000 feet to provide for transportation hazards.
d. Reduce by 50 feet for dead-end streets or roads. •
e. One hydrant for each 1,000 gallons per minute or fraction thereof.
2000 INTERNATIONAL FIRE CODE® • 359
APPENDIX B . .RE-FLOW REQUIREMENTS FOR Btu,
TABLE B105.1
MINIMUM REQUIRED FIRE FLOW AND FLOW DURATION FOR BUILDINGS
FIRE AREA(square feet) FIRE FLOW FLOW
Type IA and IB' Type IIA and IIIA' Type IV and V-Aa Type JIB and IIIB' Type V-B' (gallons per minute)" DURATION(hours)
0-22,700 0-12,700 0-8,200 0-5,900 _ 0-3,600 1,500 mewn•.--
22,701-30,200
22,701-30,200 12,701-17,000 8,201-10,900 - 5,901-7,900 3,601-4,800 1,750
30,201-38,700 17,001-21,800 10,901-12,900 7,901-9,800 4,801-6,200 2,000
38,701-48,300 21,801-24,200 12,901-17,400 9,801-12,600 6,201-7,700 _ 2,250 2
48,301-59,000 24,201-33,200 17,401-21,300 _ 12,601-15,400 7,701-9,400 2,500
59,001-70,900 33,201-39,700 21,301-25,500 15,401-18,400 9,401-11,300 2,750
70,901-83,700 39,701-47,100 25,501-30,100 18,401-21,800 11,301-13,400 3,000
83,701-97,700 47,101-54,900 30,101-35,200 21,801-25,900 -13,401-15,600 3,250
97,701-112,700 54,901-63,400 35,201-40,600 25,901-29,300 15,601-18,000 3,500 3
112,701-128,700 63,401-72,400 40,601-46,400 29,301-33,500 18,001-20,600 3,750
128,701-145,900 72,401-82,100 46,401-52,500 33,501-37,900 ;20,601-23,300 4,000
145,901-164,200 . 82101-92,400 52501-59,100 37,901-42,700 23,301-26,300 4,250
164,201-183,400 92,401-103,100 59,101-66,000 42,701-47,700 26,301-29;300 4,500
183,401-203,700 • 103,101-114,600 66,001-73,300 47,701-53,000 29,301-32,600 4,750
203,701.225,200 114,601-126,700 73,301-81,100 53,001-58,600 ,32601-36,000 5,000
225,201-247,700 126,701-139,400 81,101-89,200 58,601-65,400 36,001-39,600 5,250
247,701-271,200 139,401-152,600 89,201-97,700 65,401-70,600 39,601-43,400 5,500
271,201-295,900 152,601-166,500 97,701-106,500 70,601-77,000 43,401-47,400 _ 5,750
295,901-Greater 166,501-Greater 106,501-115,800 77,001-83,700 47,401-51,500 6,000 4
115,801-125,500 83,701-90,600 51,501-55,700 6,250
125,501-135,500 90,601-97,900 55,701-60,200 6,500
- 135,501-145,800 97,901-106,800 60,201-64,800 6,750
- , - 145,801-156,700 106,801-113,200 64,801-69,600 7,000
- -• 156,701-167,900 113,201-121,300 69,601-74,600 7,250 _
167,901-179,400 121,301-129,600 74,601-79,800 7,500
179,401-191,400 129,601-138,300 79,801-85,100 7,750
• - 191,401-Greater 138,301-Greater 85,101-Greater 8,000
For SI: 1 square foot=0.0929 m2, I gallon per minute=3.785 L/m, I pound per square inch=6.895 kPa.
a. Types of construction are based on the International Building Code.
b. Measured at 20 psi.
•
358 - - ?Mn INTF RN ATI/lKIAr.r.r......
ENGINEERING COMMENTS NO. 1
to A 4-in sanitary sewer service line requires a 1% slope,please illustrate.
'
i ase provide water and sewer demands and specify size of water meters.
3. 'ease 1 . trate proposed location for the domestics and irrigation meter. These meters
need to b: located within an easement. It appears the proposed meter location is outside of
an ease nt,please dedicate.
(
4. Pose dedicate an easement for any on-site public utility that are not already located in an
----- easement.
. illustrate canopy height on site plan.
fi
Please label the existing water service / fire line to be removed.calee
ie Fire Flow: The fire flow report is needed to verify the number of hydrants required per
tables B105.1 and C105.1 of the fire code, using the proposed square footage and building
material type,please submit.
bel rainage Report: It appears from the grading plan that the existing and proposed contours
are very similar, I assume the overall drainage pattern for the proposed site will remain the
s the existing site,please verify.
.9. P e submit development permit and fees.
Reviewed by: Josh Norton Date: February 19, 2007
�� AI.
(4:L.
,,,,, /,,....-6(A.14E
(*//"14
CITY Or COLLEGE STATION
Planning d Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570/ Fax 979.764.3496
MEMORANDUM
February 5, 2007
TO: Brett McCully, PE
FROM: Crissy Hartl, Staff Planner
SUBJECT: MID SOUTH BANK (SP)- Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
One (1) revised site and landscaping plan.
Easement Dedication Sheet and required documents.
Please note that the Easement Dedication Sheet and necessary documents are required prior
to the issuance of a building permit. If there are comments that you are not addressing with the
revised site plan, please attach a letter explaining the details. If you have any questions or need
additional information, please call me at 979.764.3570.
Attachments: Staff review comments
pc: H.E. Butt Grocery Company, PO Box 839999, San Antonio, TX 78283
James Broussard, AIA via fax# 337.235.5089
Case file #07-00500020
Home of Texas A&M University
TRANSMISSION VERIFICATION REPORT
TIME : 02/05/2007 17:04
NAME :
FAX
TEL
SER.# : 0@0L53596800
DATE,TIME 02/05 17:00
FAX NO./NAME 913372355089-10897#
DURATION 00:03:35
PAGE(S) 09
RESULT OK
MODE STANDARD
ECM
(*dr"
CITY or COLLEGE STATION ,sir
Plow*&Development Service
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.35701 Fax 979.764.3496
MEMORANDUM
February 5, 2007
TO: Brett McCully, PE
FROM: Crissy Hartl, Staff Planner
SUBJECT: MID SOUTH BANK(SP)- Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
One (1) revised site and landscaping plan.
Easement Dedication Sheet and required documents.
Please note that the Easement Dedication Sheet and necessary documents are required prior
to the issuance of a building permit. If there are comments that you are not addressing with the
revised site plan, please attach a letter explaining the details. if you have any questions or need
additional information, please call me at 979.764.3570.
Attachments: Staff review comments
al-I o
q:4c1
C*Or"I cd
CITY OF COLLEGE STATION :�::, a"
PJg»ei,.a�'DecSlnpnanc Serraer _ ..
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 I Fax 979764.3496
MEMORANDUM
February 5, 2007
TO: Brett McCully, PE
FROM: Crissy Harti, Staff Planner
SUBJECT: M1D SOUTH BANK (SP)- Site Plan
Staff reviewed the above-mentioned site plan as requested_ The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit thehefollowing information for further staff review:
V One (1) revised site and landscaping plan_ N 2M
Easement Dedication Sheet and required documents. U. D SE's TG"
� -
Please note that the Easement Dedication Sheet and necessary documents are required prior
to the issuance of a buildingph letter explain ng the details_If you have any git. If there re comments tat you are not durestio essin9 or need
with the
revised site plan please attttac
additional information, please call me at 979.764.3570.
Attachments: Staff review comments
pc: H.E. Butt Grocery Company, PO Box 839999, San Antonio,TX 78283
James Broussard, AIA via fax#337.235.5089
Case file#07-00500020
Home of Texas A&M University
.
Bii, Bleyl & Associates
1722 Broadmoor
Suite 210
A
Project Engineering & Management Bryan, TX 77802
4
February 12, 2007
Ms. Crissy Hartl, Staff Planner
Planning and Development Sevices
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
RE: Mid-South Bank Site Plan Comments
Case #07-00500020
Dear Ms. Hartl,
Following are your planning comments from the February 5 review of the referenced
project. Our resolution is shown next to each comment in italics.
1. Please provide a key map of the project to identify area location. A project
location map now appears on the Site Plan.
2. Provide the legal description, date of submittal, and site area it title block. The
requested information has been added to the site plan.
3. Please relocate fencing and screening details, with the exception of dumpster
screening, to another sheet and enlarge the site plan to a scale of 1" = 10'. Site
Plan has been enlarged, and details have been moved.
4. Identify the ownership and current zoning of parcel and all abutting parcels.
Ownership and zoning is now shown.
5. Provide the gross square footage of all buildings and structures and proposed
use of each. Square footage of each structure and use is now shown.
6. Dimension and label all setbacks on the site plan. Dimensions have been added.
7. Please provide building elevations, color samples, and a materials list according
to section 7.9 of the UDO. Approval of the elevations is required before a
building permit will be issued. Separate review of the elevations will count as
one round of review out of three allowed. This will be submitted separately by
Architect.
8. Please identify and dimension all existing sidewalks. Existing sidewalks have
been labeled and dimensioned.
9. Please add the curb and pavement detail to the site plan. Curb and pavement
details appear on the Grading Plan.
10. Please provide your parking calculations on the site plan, and include what is
required by ordinance and what was provided. Requested information now
appears on Site Plan.
11. Per UDO Section 7.2.J. Drive-Through Facility Queuing Requirements, a
minimum three queuing spaces are required from the window for an ATM and
four queuing spaces are required from the teller of a bank teller lane. These
Bryan Austin
(979)-268-1125 Conroe
(979)-260-384911 (512)-328-7878 (936)-441-7833
(512)-328-7884 Fax (936)-760-3833 Fax
spaces have an area of 10' x 18.5'. Please dimension these spaces. Please
dimension these spaces and verify that this requirement as well as other
standards, such as drive-aisle widths, is also being met. Queuing spaces are
now delineated and dimensioned on the Site Plan.
12. Per UDO Section 7.2.D. End Islands, a 180 sq. ft. island is required at the ends
of every parking row. Please dimension the islands on the plan and verify that
this requirement is being met. Islands are now dimensioned and square
footages are shown.
13. What is your intent for sanitation service? Please see UDO Section 7.7 Solid
Waste for our minimum design standards. Wally Urrutia of the Solid Waste
Department was contacted. One 90 gallon trash container can be used. The
enclosure is adequate for this size container.
14. Please remove all sigh details or add a note to the site plan that reads "All signs
to be permitted separately". Note has been added.
15. Provide a general note that all roof and ground-mounted mechanical equipment
shall be screened from view or isolated so s not to be visible from any public
right-of-way or residential district within 150' of the subject lot, measured from a
point five feet above grade. Such screening shall be coordinated with the
building architecture and scale to maintain a unified appearance. Note has been
added.
Please do not hesitate to contact me with any questions, or if you require additional
information.
Sinc ely,
Brett A. McCuII , P.E.
Senior Engineer
B Bleyl & Associates
g� y ate s 1722 Broadmoor
(X Suite 210
iiiik.
A Project Engineering & Management Bryan, TX 77802
oK
February 12, 2007
Mr. Josh Norton, E.I.T.
Development Services
City of College Station
P.O. Box 9960
College Station, Texas 77842
RE: LETTER ACKNOWLEDGING CITY STANDARDS
MID-SOUTH BANK, COLLEGE STATION, TEXAS
Dear Mr. Norton:
The purpose of this letter is to acknowledge that the construction plans for the water,
sanitary sewer, streets and drainage for the referenced project, to the best of my
knowledge, do not deviate from the B/CS Design Guideline Manual.
I also acknowledge, to the best of my knowledge that the details provided in the
construction plans are in accordance with the Bryan/College Station Standard Details.
Since the detention requirements for Lot 6 and a portion of Lot 5 were satisfied as part of
the overall development plan submitted for Anderson Ridge Phase IV by the H. E. Butt
Grocery Company, we do not believe a drainage report is required.
We are also asking that the fire flow report be waived. There is an existing fire hydrant
on the southwest corner of the Mid-South site that satisfies the City's Fire Code with
respect to its distance from the building, so no new infrastructure is required. Given the
proximity of the elevated storage tank, we are confident that sufficient pressure exists at
this existing hydrant.
Please contact me if you have any questions or require any other information for your
review.
Sincerely,
/47,
, / 0,„,,,,, ,c?...d,„.., .711 et. 'eri.,
, evitee * '''fb*'1:ti,
Brett A. c' ly, P.E. ce wisesi,� 03
P a i 1 aR 1,
Senior n•meer � �'
leiteeea“seeI U) :Q ,s•s G
1 1 kt°47 l Sjoris.4
-1a/
Bryan Austin
(979)-268-1125 Conroe
(979)-260-384911 (512)-328-7878 (936)-441-7833
(512)-328-7884 Fax (936)-760-3833 Fax
-,, A r. f ; ,._ , . ,
I
II' N i /C.:1'., Ell , ,, . , c...: ,,,,f ,,,,, r, (_:. -r-\-,-r-,,
II A' \ V ; 4 A_,,,,,, . .%) ...,, A.:-I ,i., \ 7> A, ' , ..
MB A l'HUFES6IONAI,EN(; N'I'',FRI NG CORPOIZATION
MN '304 PIATT; ND )1'1'..`'-' • ''.1:1``'F'Af;
MI LAKWETTE.LOUISIANA 70:'..f.
. . ME i.X.-37 2:34,7474 • FAX II..7:i7)44-7774
www.msxtrw-iuting.t.14n:
February 8, 2007
James Broussard
James Broussard & Associates
P.O. Box 53517
Lafayette, LA 70505-3517
Re: Midsouth Bank-College Station,TX
M&E 06197.00
Dear James:
We have received a copy of the City of College Station, Planning Department comments.and offer the
following responses to items relative to Mechanical and Electrical:
Mechanical Comments:
Miscellaneous
1. Miscellaneous Item No. 1:
A. Irrigation system must be protceted by either a pressure vacuum breaker,a
reduced pressure principle backflow device or a double check back flow device
and installed as per City Ordinance 2394.
Response: Backflow preventer is shown on Drawings Sheet Ml.01 but has not been
included in the specifications this will be added by addendum and noted
to comply.
2. Miscellaneous hem No.2:
A. All backflow devices must be installed and tested upon installation as per City
Ordinance 2394.
Response: This item w ill be added by addendum and will be noted to comply.
Engineering Comments No. 1
3. Engineering Comments No. 1, Item No 3:
A. Please illustrate proposed sanitary sewer serv:ee the sie, slope, material type.
Response: Size of sanitary sewer line will be 4" as noted on Drawings Sheet M1.01
and will be connected to existing 6" sewer service from existing building
to he removed.
Slope of sewer line shall be as per Section 15350.
Material shall be as per Section 15100.
...i SCOTTY •J BAUDOIN, P.E. .;AY" Mux, PE. RIUHAN” NI :.RP,LANC
L..
4. Eihtineering Comments No, 1. Item No 4:
A. Please illustrate proposed water serv:ce line and material type.
Response: Water service line vill be as per Drawing Sheet M1.01.A backflow
prevention device wiil be added by addendum.
Material type shall be as specified in Section 15100.
5. Engineering Comments No. 1, Item No 5:
A. Please illustrate proposed location for the domestics and irrigation meter. These
meters need to be located within an easement. The irrigation system will require
hackflow preventer,
Response: Water meters shall be located in easement which will be clarified in the
addendum.
Electrical Comments:
Electrical Comments item No. 1:
A. Developer provales temporary blanket easement for construction purposes.
Response:(OwnerlDeveloper Civil)
2. Electrical Comments Item No, 2:
A. Developer provides easement for electric infrastructure as installed ear electric
lines (including street lights).
Response: (Owner,DeveloperiCivil)
General Electrical Comments:
. General Electrical Comments Item No. :
Developer installs eonduit per City specs and design.
Response: Covered by specification, 16010-1: -Electrical installations-.
2. General Electrical Comments Item No, 2:
A. Ciry will provide drawings for conduit installation,
Response: Covered by specification, 16010-1: -Electrical Installations-and electrical
riser on Drawings E3.0l.
General Electrical Comments Item No. 3:
A. Developer to intercept existing,conduit at designated transformers and extend as
requtred,
Response: Shown on Electrical Site Plan 111.01,
4, Gni Electrical Comments hem No,4:
A. If concEiit does not exist at designated t.ransformer developer to iiii•nish and
install conduit as shown on electricaay011I.
Response: Shown on Electrical Site Plan E1.0:,and electrical riser on Drawing E3.0 I.
5, General Electrical Comments Item N . 5:
A. Developer pours transformer:pad(s)per City specs and design.
Response: Shown on electrical riser on Sheet E.3.01,
6. General Electrical Comments Item No, 6:
A. Developer installs pull boxes as per City specs and design pull boxes provided
by the City.
Response: Shown or:electrical riser on Sheet E3.0 I
. General Electrical Comments Item No, 7:
A. Developer provides digital AutoCAD 2000 or later version of plan and/or site
plan. E-mail to sweidixiestx.20v.
ResponsutoCad drawings were e-mailed from Nati Consulting to Stmi Weido on
P/5/07.
8. General Electrical Comments Item No, 8:
A. Developer provides load data for project.
Response: Load Summary was sent to Sam Weida and also appears on Drawings E3.01
9. General Electrical Comments Item No. 9:
A. To discuss any of the above electrical comments, please contact SainWeido at
979-784-8'314.
Response: Acknowledged.
If you need additional information please contact our office,
Sincerely,
Richar . LeBlanc
Electrical Project Mamager
M&F,Consultinsz. Inc.
•