HomeMy WebLinkAboutStaff Comments 1 1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570/Fax 979.764.3496
Cm'OF COLLEGE STATION
MEMORANDUM
July 2, 2007
TO: Eva Read-Warden, AIA, The Arkitex Studio, Inc, via evaarkitex.com
FROM: Jason Schubert, Staff Planner
SUBJECT: ADAMSON LAGOON (SP) — Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
One (1) complete set of construction documents for the proposed development
with the revised site and landscaping plans attached;
One (1) revised site plan;
One (1) Development Permit application (fee waived).
If there are comments that you are not addressing with the revised site plan, please attach a
letter explaining the details. If you have any questions or need additional information, please call
me at 979.764.3570.
Attachments: Staff review comments
pc: Ric Ploeger, CoCS Parks & Recreation Dept, via rploeqercstx.qov
Case file #07-00500150
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 1 of 3
STAFF REVIEW COMMENTS NO. 1
Project: ADAMSON LAGOON (SP)— 07-00500150
PLANNING
1. This project is a city project so application fees do not apply. The $200 fee will be refunded.
2. Since a site plan is required with this project, the elevations can be included with that
application. As such, the elevations and materials associated with the Non-residential
Architecture Standard application have been combined with the site plan file.
3. The zoning for the property is R-1, Single-Family Residential. Please revise the label.
4. Provide the square feet of the existing buildings on the site.
5. Since they are on the building elevation sheet, the tables for building Materials and Color
may be removed from the site plan.
6. The proposed building elevations are acceptable and there are no further comments.
7. Provide a general note on the site plan that all roof and ground-mounted mechanical
equipment shall be screened from view or isolated so as not to be visible from any public
right-of-way or residential district within 150' of the subject lot, measured from a point five
feet above grade. Such screening shall be coordinated with the building architecture and
scale to maintain a unified appearance.
Reviewed by: Jason Schubert Date: July 2, 2007
ENGINEERING COMMENTS NO. 1
1. Provide civil documents referenced on Site Plan.
2. What is "DD"?
3. Development Permit and associated documents are required. Fees are waived.
Reviewed by: Carol Cotter Date: July 2, 2007
GENERAL ELECTRICAL COMMENTS
1. Developer installs conduit per City specs and design.
2. City will provide drawings for conduit installation.
3. Developer provides 30' of rigid or IMC conduit for riser poles. City installs riser.
4. Developer to intercept existing conduit at designated transformers and extend as required.
5. If conduit does not exist at designated transformer, developer to furnish and install conduit
as shown on electrical layout.
6. Developer pours transformer pad(s) per City specs and design.
7. Developer installs pull boxes and secondary pedestals as per City specs and design (pull
boxes and secondary pedestals provided by the City).
8. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan. Email to: /
sweido@cstx.gov.
9. Developer provides load data for project.
10. To discuss any of the above electrical comments please contact Sam Weido at
979.764.6314.
Reviewed by: Weldon Davis for Sam Weido Date: June 28, 2007
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 2 of 3
FIRE
1. This will need a Knox Box
2. No other comments at this time.
Reviewed by: Eric Dotson Date: June 28, 2007
SANITATION
1. Sanitation is ok with this project.
Reviewed by: Wally Urrutia Date: June 27, 2007
MISCELLANEOUS
1. FYI, irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced
Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed
as per City Ordinance 2394.
2. FYI, all BackFlow devices must be installed and tested upon installation as per City
Ordinance 2394.
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 3 of 3
ffs.44,4 1101 Texas Avenue,P.O. Box 9960
College Station,Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
CITY OF COLLEGE STATION
MEMORANDUM
August 9, 2007
TO: Eva Read-Warden, AIA, The Arkitex Studio, Inc, via eva@arkitex.com
FROM: Jason Schubert, Staff Planner
SUBJECT: ADAMSON LAGOON (SP) — Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
Seven (7) complete sets of construction documents for the proposed
development with the revised site and landscaping plans attached (one set will
be returned to you, please submit additional copies if you want more than one
approved set)
Two (2) revised site plans
One (1) landscaping plan
One (1) 11x17 grading and erosion control plan
Other engineering documents as described in the comments.
If there are comments that you are not addressing with the revised site plan, please attach a
letter explaining the details. If you have any questions or need additional information, please
call me at 764-3570.
Attachments: Staff review comments
cc: Ric Ploeger, CoCS Parks & Recreation Dept, via rploegerc cstx.gov
Case file #07-00500150
STAFF REVIEW COMMENTS NO. 2
Project: ADAMSON LAGOON (SP) - 07-00500150
PLANNING
1. Planning has no further comments.
Reviewed by: Jason Schubert Date: August 3, 2007
ENGINEERING COMMENTS NO. 2
1. Provide plan and profile of 6" water line extension.
2. Provide fire flow report/letter.
3. Provide drainage letter addressing no need for detention.
Reviewed by: Carol Cotter Date: August 9, 2007
1101 Texas Avenue,P.O. Box 9960
College Station,Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
CII,01 COLLEGE STATION
MEMORANDUM
August 9, 2007
TO: Eva Read-Warden, AIA, The Arkitex Studio, Inc, via eva@arkitex.com
FROM: Jason Schubert, Staff Planner
SUBJECT: ADAMSON LAGOON (SP) — Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
` / Io
V S ) complete sets of construction documents for the proposed
development with the revised site and landscaping plans attached (one set will
be returned to you, please submit additional copies if you want more than one
approved set)
Two (2) revised site plans
✓/ One (1) landscaping plan
One (1) 11x17 grading and erosion control plan
Other engineering documents as described in the comments.
If there are comments that you are not addressing with the revised site plan, please attach a
letter explaining the details. If you have any questions or need additional information, please
call me at 764-3570.
Attachments: Staff review comments
cc: Ric Ploeger, CoCS Parks & Recreation Dept, via rploegercstx.gov
Case file#07-00500150