CITY OF COLLEGE STATION
MEMORANDUM
SEE PLANNING NOTE 2; NRA AND SITE PLAN FILES COMBINED
July 2, 2007
TO: Eva Read-Warden, AIA, The Arkitex Studio, Inc, via evaarkitex.com
FROM: Jason Schubert, Staff Planner
SUBJECT: ADAMSON LAGOON (SP) — Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
One (1) complete set of construction documents for the proposed development
with the revised site and landscaping plans attached;
One (1) revised site plan.
If there are comments that you are not addressing with the revised site plan, please attach a
letter explaining the details. If you have any questions or need additional information, please
call me at 979.764.3570.
Attachments: Staff review comments
pc: Ric Ploeger, CoCS Parks & Recreation Dept, via rploeqercstx.qov
Case file #07-00500150
STAFF REVIEW COMMENTS NO. 1
Project: ADAMSON LAGOON (SP) — 07-00500150
PLANNING
1. This project is a city project so application fees do not apply. The $200 fee will be refunded.
2. Since a site plan is required with this project, the elevations can be included with that
application. As such, the elevations and materials associated with the Non-residential
Architecture Standard application have been combined with the site plan file.
3. The zoning for the property is R-1, Single-Family Residential. Please revise the label.
4. Provide the square feet of the existing buildings on the site.
5. Since they are on the building elevation sheet, the tables for building Materials and Color
may be removed from the site plan.
6. The proposed building elevations are acceptable and there are no further comments.
7. Provide a general note on the site plan that all roof and ground-mounted mechanical
equipment shall be screened from view or isolated so as not to be visible from any public
right-of-way or residential district within 150' of the subject lot, measured from a point five
feet above grade. Such screening shall be coordinated with the building architecture and
scale to maintain a unified appearance.
8. Please note that any changes made to the plans, that have not been requested by the City
of College Station, must be explained in your next transmittal letter and "bubbled" on your
plans. Any additional changes on these plans that the City has not be made of aware of will
constitute a completely new review.
Reviewed by: Jason Schubert Date: July 2, 2007
MISCELLANEOUS
1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced
Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed
as per City Ordinance 2394.
2. All BackFlow devices must be installed and tested upon installation as per City Ordinance
2394.