CITY OF COLLEGE STATION
MEMORANDUM
July 30, 2007
TO: Parviz Vessali, Texas Hotel Management, L.P, via parvizvessali(a�yahoo.com
FROM: Jason Schubert, Staff Planner
SUBJECT: GREENS PRAIRIE CENTER PH 5 LOT 2 BL 7 (SP) — Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
One (1) complete set of construction documents for the proposed development
with the revised site and landscaping plans attached;
One (1) revised site plan;
One (1) landscaping plan; and
Easement Dedication Sheet and required documents (please allow 4 weeks to
process).
Please note that the Easement Dedication Sheet and necessary documents are required prior
to the issuance of a building permit. If there are comments that you are not addressing with the
revised site plan, please attach a letter explaining the details. If you have any questions or need
additional information, please call me at 979.764.3570.
Attachments: Staff review comments
pc: Joe Schultz, PE, Civil Development, Ltd, via joe(a�cdlbcs.com
Case file #07-00500179
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 1 of 3
STAFF REVIEW COMMENTS NO. 1
Project: GREENS PRAIRIE CENTER PH 5 LOT 2 BL 7 (SP)— 07-00500179
PLANNING
1. Revise the site plan so that all of Lot 2, Block 7 is included within its limits.
2. If there are portions of the Lot to remain undeveloped/undisturbed, separate the lot into
phases so that undeveloped areas are in future/other phases.
3. Revise Note 2 on the site plan to include the Corridor Overlay (OV) district.
4. This Lot is within Phase 5 of Greens Prairie Center. Phase 5 has been determined to be a
building plot that will need to meet the additional standards in Section 7.9.E of the Unified
Development Ordinance (UDO)for building plots in excess of 50,000 gross square feet.
5. Revise Note 10 to state vehicle trips generated by proposed and future development may be
incorporated into a TIA for Greens Prairie Center at some future time.
Reviewed by: Jason Schubert Date: July 30, 2007
LANDSCAPING/STREETSCAPING/BUFFER
1. Revise the landscape plan according to the areas identified in Planning comment 2.
2. Revise General Note 3 on the landscape plan to include the Corridor Overlay (OV) district.
3. Revise the numbering for the General Notes (the last two).
4. All calculations round up, 17 streetscape trees required along State Hwy 6. Please revise.
5. Please revise the Landscape Plan to comply with UDO Section 7.9.E.3.
Reviewed by: Jason Schubert Date: July 30, 2007
ENGINEERING COMMENTS NO. 1
1. It appears that an off-site drainage easement and associated improvements are required.
2. Drainage report needs signature.
3. Drainage report still under review.
Reviewed by: Carol Cotter Date: July 29, 2007
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1. Developer provides temporary blanket easement for construction purposes.
2. Developer provides easements for electric infrastructure as installed for electric lines
(including street lights).
3. Additional easements may be required as a site plan develops.
GENERAL ELECTRICAL COMMENTS
1. Developer installs conduit per City specs and design.
2. City will provide drawings for conduit installation.
3. Developer provides 30' of rigid or IMC conduit for riser poles. City installs riser.
4. Developer to intercept existing conduit at designated transformers and extend as required.
5. If conduit does not exist at designated transformer, developer to furnish and install conduit
as shown on electrical layout.
6. Developer pours transformer pad(s) per City specs and design.
NOTE: Any changes made to the plans, that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 2 of 3
7. Developer installs pull boxes and secondary pedestals as per City specs and design (pull
boxes and secondary pedestals provided by the City).
8. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan. Email to
bread(a�cstx.gov.
9. Developer provides load data for project.
10. To discuss any of the above electrical comments please contact Brent Read at
979.764.5026.
Reviewed by: Brent Read Date: July 25, 2007
SANITATION
1. Sanitation is ok with this project.
Reviewed by: Wally Urrutia Date: July 24, 2007
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 3 of 3
ENGINEERING COMMENTS NO. 2
1. Why is the emergency overflow not discharging at same location of outfall? Provide flow
pathway for emergency overflow.
2. What is surface treatment of overflow spillway? The surface treatment of the spillway and
its discharge path shall give due regard to maintenance.
3. Drainage easement is required for outflow to recognized drainageway.
4. Are you indicating that the emergency spillway will only operate for design storms in excess
of 100-yr, or under plugged outlet pipe conditions?
Reviewed by: Carol Cotter Date: August 9, 2007
,
Response to
STAFF REVIEW COMMENTS NO. 1
Project: GREENS PRAIRIE CENTER PH 5 LOT 2 BL 7 (SP) — 07-00500179
7PL NNING
1. Revise the site plan so that all of Lot 2, Block 7 is included within its limits.
The Site Plan has been revised to include all of Lot 2, Block 7.
/f there are portions of the Lot to remain undeveloped/undisturbed, separate the lot into
phases so that undevelo•ed area are in future/other phases.
.41 /t:�Ne!.otai tAsi. m,,. .Ali 1;14a iS_�Tal i�'t\ may- 7
There are no portions of the Lot that will remain undeveloped/undisturbed.
3. evise Note 2 on the site plan to include the Corridor Overlay (OV) district.
q
Trz 1,101-,ez Ca qc,i n) - 1 t5t- a aveir-IGw olt ricAs
Note 2 on the Site Plan Has been revised.
.7
his Lot is within Phase 5 of Greens Prairie Center. Phase 5 has been determined to be a
building plot that will need to meet the additional standards in Section 7.9.E of the Unified
Development Ordinance (UDO) for building plots in excess of 50,000 gross square feet.
This issue was discussed with Jason Schubert and the building on site has been revised to
40,000 gross square feet, therefore, no changes to the landscaping requirement was
needed.
-evise Note 10 to state vehicle tri erated by proposed and future development may be
incorporated into a TIA fo reens Prairie Cente9t some future time.
Note 10 on the Site Plan was revised. S�-u4--� " w5 S\
L., , DSCAPING/STREETSCAPING/BUFFER
oRevise the landscape plan according to the areas identified in Planning comment 2.
The acreage on the landscape plan was revised to include all 7.040 acres.
v2 Revise General Note 3 on the landscape plan to include the Corridor Overlay (OV) district.
General Note 3 on the Landscape Plan was revised to include the Corridor Overlay district.
/Revise the numbering for the General Notes (the last two).
The numbering for the General Notes on the Landscape Plan was revised.
/All calculations round up, 17 streetscape trees required along State Hwy 6. Please revise.
The calculations were revised and there are 17 streetscape trees along State Hwy 6.
Please revise the Landscape Plan to comply with UDO Section 7.9.E.3.
NA The Landscape Plan was revised to comply with UDO Section 7.9.E.3.
ENGINEERING COMMENTS NO. 1
1. It appears that an off-site drainage easement and associated improvements are required.
An off-site drainage easement could not be obtained. A structure was designed to allow
water to flow into the natural channel at sheet flow conditions.
2. Drainage report needs signature.
Two signed copies are being provided with this resubmittal.
3. Drainage report still under review.
Noted.
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1 `2 Developer provides temporary blanket easement for construction purposes.
Developer provides easements for electric infrastructure as installed for electric lines
(including street lights).
3. Additional easements may be required as a site plan develops.
GENERAL ELECTRICAL COMMENTS
1. Developer installs conduit per City specs and design.
2. City will provide drawings for conduit installation.
3. Developer provides 30' of rigid or IMC conduit for riser poles. City installs riser.
4. Developer to intercept existing conduit at designated transformers and extend as required.
5. If conduit does not exist at designated transformer, developer to furnish and install conduit
as shown on electrical layout.
6. Developer pours transformer pad(s) per City specs and design.
7. Developer installs pull boxes and secondary pedestals as per City specs and design (pull
boxes and secondary pedestals provided by the City).
8. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan. Email to
breadcstx.qov.
9. Developer provides load data for project.
10. To discuss any of the above electrical comments please contact Brent Read at
979.764.5026.
SANITATION
1. Sanitation is ok with this project.
Noted.
Response to (dated August 9, 2007)
ENGINEERING COMMENTS NO. 2
1. Why is the emergency overflow not discharging at same location of outfall? Provide flow
pathway for emergency overflow.
The location has been moved and a rock rip-rap channel provided below the emergency
overflow.
2. What is surface treatment of overflow spillway? The surface treatment of the spillway
and its discharge path shall give due regard to maintenance.
The top of the overflow will be grassed, except for the last two feet where water begins to
cascade down the backside of the spillway. That portion of the overflow and the pathway
down the slope shall received rock rip-rap. This is shown on the revised plans.
3. Drainage easement is required for outflow to recognized drainageway.
The developers of this property have been unable to reach an agreement with the
downstream property owner for a drainage easement. Since this was not possible, we have
devised a system that will effectively return flow from the detention pond to sheet flow. The
system shown on the plans uses a curb at a uniform height across its entire length to evenly
release water onto the adjacent site in much the same manner as it is currently flows prior to
any development.
4. Are you indicating that the emergency spillway will only operate for design storms in
excess of 100-yr, or under plugged outlet pipe conditions.
That is correct. The pond and the outlet control structure are designed to handle all design
storms up to and including the 100-year event. The emergency spillway will only be
operative when the outlet structure is blocked or during rainfall events in excess of the 100-
yr design storm.
1 1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
CITY OF COLLEGE STATION
MEMORANDUM
September 5, 2007
TO: Parviz Vessali, Texas Hotel Management, L.P, via parvizvessali c(�,yahoo.com
FROM: Jennifer Prochazka, AICP, Senior Planner
SUBJECT: GREENS PRAIRIE CENTER PH 5 LOT 2 BL 7 (SP) — Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. The next submittal will be the third
and final review by staff for this round of reviews. If all items have not been addressed on the
next submittal, another $200 processing fee will need to be submitted for the subsequent set of
three (3) reviews. Please address the comments and submit the following information for
further staff review:
Seven (7) complete sets of construction documents for the proposed
development with the revised site and landscaping plans attached (one set will
be returned to you, please submit additional copies if you want more than one
approved set)
Two (2) revised site plans
One (1) landscaping plan
One (1) 11x17 grading and erosion control plan
Please note that the Easement Dedication Sheet and necessary documents are required prior
to the issuance of a building permit. If there are comments that you are not addressing with the
revised site plan, please attach a letter explaining the details. If you have any questions or need
additional information, please call me at 979.764.3570.
Attachments: Staff review comments
pc: Joe Schultz, PE, Civil Development, Ltd, via joena cdlbcs.com
Case file #07-00500179
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 1 of 2
STAFF REVIEW COMMENTS NO. 2
Project: GREENS PRAIRIE CENTER PH 5 LOT 2 BL 7 (S - 07-00500179
PLANNING
1. Please revise Note 2, it lists two overlay districts.
2. Please revise Note 10 to state "vehicle trips generated by proposed and future
development may be incorporated into a TIA for Greens Prairie Center at some future
time."
3. Is knock-off curbing proposed at dead-end drives?
4. Please note that any changes made to the plans, that have not been requested by the
City of College Station, must be explained in your next transmittal letter and "bubbled" on
your plans. Any additional changes on these plans that the City has not been made
aware of will constitute a completely new review.
Reviewed by: Jennifer Prochazka Date: August 29, 2007
ENGINEERING COMMENTS NO. 3
1. Site Plan cannot be approved or development permit issued until the lot is platted (mylar
filed).
Reviewed by: Carol Cotter Date: August 30, 2007
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 2 of 2
Response to
STAFF REVIEW COMMENTS NO. 2
Project: GREENS PRAIRIE CENTER PH 5 LOT 2 BL 7 (S - 07-00500179
PLANNING
1. Please revise Note 2, it lists two overlay districts.
Note revised.
2. Please revise Note 10 to state "vehicle trips generated by proposed and future
development may be incorporated into a TIA for Greens Prairie Center at some future
time."
Note revised.
3. Is knock-off curbing proposed at dead-end drives?
Yes, this has been noted on the Site Plan.
4. Please note that any changes made to the plans, that have not been requested by the
City of College Station, must be explained in your next transmittal letter and "bubbled" on
your plans. Any additional changes on these plans that the City has not been made
aware of will constitute a completely new review.
Note: The site plan was not scaled correctly. It has been revised and is to scale.
ENGINEERING COMMENTS NO. 3
1. Site Plan cannot be approved or development permit issued until the lot is platted (mylar
filed).
Noted.