General Information
Location: Saddle Creek Subdivision is located in southern Brazos County, near the
intersection of Wade Road and Stousland Road.
General Note: There are 35 lots in the subdivision.
Land Use: Single Family Residential
WATER SYSTEM ANALYSIS
Design Criteria
Primary Water Supply: Existing 12"line along Stousland Road operated by Wellborn SUD.
Domestic Demand:
Avg. Pop Density: 2.67 people per lot
Average Flow: 100 gpd/cap or 267 gpd per lot=0.18 gpm per lot
Peaking Factor: 4
Peak Flow: 0.74 gpm per lot
Design Flow: 1.50 gpm per lot
Fire Demand:
Fire Flow: 1000 gpm at most hydraulically remote point
Pipe: PVC DR-14 C909
Roughness Coeff 150(Hazen Williams)
Hydraulic Software: Haestad Methods WaterCAD v.6.0
Existing System Pressure Tests
Flow Hydrant: Fire Hydrant on Stousland Road, south of Wade Road.
Flowrate: 1300 gpm
Guage Location: 5401 Stousland Road(hose bib on side of house)
Static Pressure: 78 psi(180 ft water)
Residual Pressure: 75 psi(173 ft water)
Applicable Exhibits: Exhibit B—Flow Test Report
Water System Analysis Summary
As
Criteria Required •
Designed Location
Min. Pressure-fire(psi) 20 • 75.56 SC 101 *
Max. Velocity(fps) 12 2.93 P101
Max. Length of 6"pipe(ft)
(connected to > 8"on both 1500 NA
ends)
Max Length of 6"pipe(ft) 1800 NA
(not connected on both ends)
Max. Length of 3"pipe(ft) 500 270
Note: The lowest water pressure occurred at SC101. The nearest fire hydrant to
that point is at SC1 FH1. That is the location where a 1000 gpm fire demand was
added for modeling purposes.
Applicable Exhibits: Exhibit A—Water System Schematic
Exhibit C—Summary of Results—Domestic Flow
Exhibit D -Summary of Results—Fire Flow
Conclusion
The proposed water system for Saddle Creek Subdivision meets or exceeds all of
the design criteria for the City of College Station. It will provide adequate water
pressure and flow for both domestic and fire demands.
. /
•
•
tn
0
U
G.
ON dik/ .4 .-,-,;,0
f
II U
i N
1 \/\
i1 r •
H
111' '�
IIS 1
%, F
0 1i ."
lch,,,,,
ja
U
_-^"` p,
0 4
v) I1.
I 11 LI
1 C
1-2-20
w
I--
.. --
•
EXHIBITSADDLE CREEK, *Cop"�nrLw
.* 111. 11.1. 1111.11111111.1111111.1119
A WATER SYSTEM SCHEPHASEMATIC1
" 300 150 0 300
SCAT f- H f L.H T
Exhibit B
Water System Flow Test Report
Date: November 16,2006
Water System Owner: Wellborn Special Utility District
Development Project: Saddle Creek Subdivision
Flow Test Location: Fire Hydrant @ 5401 Stousland
Nozzle size (in.): 2.5 Discharge Coef: (c): 0.9
Pitot Reading (psi): 60 Flowrate formula: Q=29.84cd2p 1 i2
c=discharge coef.
d=orifice size(in)
p=pitot pressure(psi)
Flowrate (gpm): 1300 computed
Pressure Guage Location: Hose Bib on House at 5401 Straub
Static (psi): 78
Residual (psi): 75
Report prepared by: 4, ,► -
signature
Kent Laza
printed name
Others present: Steven Cast
Exhibit C
Saddle Creek Subdivision
Water System Analysis
Static Flow Conditions
Label Elevation Demand Hydraulic Grade Pressure
(ft) (gpm) (ft) (Psi)
SC1 FH1 284 3 466.00 78.74
SC1 FH2 276 0 465.99 82.20
SC1 FH3 273 6 465.99 83.50
SC1 FH4 273 0 465.99 83.50
SC1 FH5 282 0 465.99 79.60
SC101 286 0 466.00 77.88
SC102 275 7.5 465.99 � 82.63
SC103 274 9 465.92 83.04
SC104 273 4.5 465.99 83.50
SC105 275 4.5 465.99 82.63
Lowest Pressure in Ph 2&3= 77.88
Note: The lowest pressures shown above represent the most hydraulically remote
location in the Ph 1 system. The nearest fire hydrant is SC1 FH1. This is the
location where a 1000 gpm fire demand is placed for modeling purposes.
Exhibit D
Saddle Creek Subdivision
Water System Analysis - Junction Summary
Fire Flow Conditions
? Hydraulic
Label Elevation Demand Grade Pressure
(ft) (gpm) (ft) (psi)
SC1 FH1 284 j 1,003.0 459.72 76.03
SC1 FH2 276 0.0 459.72 79.49
SC1 FH3 273 6.0 459.72 80.78
SC1 FH4 273 0.0 459.72 80.78
SC1 FH5 282 0.0 459.72 76.89
SC101 286 0.0 460.65 75.56
SC102 275 7.5 459.72 79.92
SC103 274 9.0 459.65 80.32
SC104 273 4.5 459.72 80.78
SC105 275 4.5 459.72 79.92
Lowest Pressure = 75.56
Exhibit E
Saddle Creek Subdivision
Water System Analysis - Pipe Summary
Fire Flow Conditions
Length Diameter Hazen- Discharge Velocity
Label Material Williams C
(ft) (in) (gpm) (ft/s)
P101 446 12 PVC 150 -1,034.50 1 2.93
P102 898 12 PVC 1 150 -31.50 0.09
P103 103 12 1 PVC 1 150 -31.50 1 0.09
P104 264 3 PVC 150 9.00 0.41
P105 610 12 PVC 150 15.00 0.04
P106 796 12 PVC I 150 -9.00 0.03
P107 23 8 PVC 150 0.00 1 0.00
P108 994 8 1 PVC 150 0.00 0.00
P109 634 12 I PVC 150 -4.50 0.01
Highest Velocity= 2.93
Water System Report
for
Saddle Creek Subdivision
College Station, Texas
November 2006
Prepared By:
Civil Development, Ltd.
2900 Longmire Drive, Suite K
College Station, Texas 77845
(979) 764-7743
65923/4,7„0/06
0
00;
GU
.Q\-/
\\(\;\ \
c,(r)
General Information
Location: Saddle Creek Subdivision is located in southern Brazos County, near the
intersection of Wade Road and Stousland Road.
General Note: There are 35 lots in the subdivision.
Land Use: Single Family Residential
WATER SYSTEM ANALYSIS
Design Criteria
Primary Water Supply: Existing 12"line along Stousland Road operated by Wellborn SUD.
Domestic Demand:
Avg. Pop Density: 2.67 people per lot
Average Flow: 100 gpd/cap or 267 gpd per lot=0.18 gpm per lot
Peaking Factor: 4
Peak Flow: 0.74 gpm per lot
Design Flow: 1.50 gpm per lot
Fire Demand:
Fire Flow: 1000 gpm at most hydraulically remote point
Pipe: PVC DR-14 C909
Roughness Coeff 150(Hazen Williams)
Hydraulic Software: Haestad Methods WaterCAD v.6.0
Existing System Pressure Tests
Flow Hydrant: Fire Hydrant on Stousland Road,south of Wade Road.
Flowrate: 1300 gpm
Guage Location: 5401 Stousland Road(hose bib on side of house)
Static Pressure: 78 psi(180 ft water)
Residual Pressure: 75 psi(173 ft water)
Applicable Exhibits: Exhibit B—Flow Test Report
Water System Analysis Summary
As
Criteria RequiredDes
Designed
Location
Min. Pressure-fire(psi) 20 75.56 SC101 *
Max. Velocity(fps) 12 2.93 P101
Max. Length of 6"pipe(ft)
(connected to > 8"on both 1500 NA
ends)
Max Length of 6"pipe(ft) 800 NA
(not connected on both ends)
Max. Length of 3"pipe(ft) 500 270
Note: The lowest water pressure occurred at SC101. The nearest fire hydrant to
that point is at SC1 FHI. That is the location where a 1000 gpm fire demand was
added for modeling purposes.
Applicable Exhibits: Exhibit A—Water System Schematic
Exhibit C—Summary of Results—Domestic Flow
Exhibit D -Summary of Results—Fire Flow
Conclusion
The proposed water system for Saddle Creek Subdivision meets or exceeds all of
the design criteria for the City of College Station. It will provide adequate water
pressure and flow for both domestic and fire demands.
/
In
c)
a 1 c) 11)
4ir EL'
._,
...t. ''•,,,-
iNO
4 *\„
1 4
Lik4•
.------"'..
I
V) I I 1
i I I
V/ r .
. ‘.. le
c, ,. 5...-
\
L.-; - ••-'
0\...
4•4,tit,
=
--
v) .
___--- 0-
E'
—. 1
(-)
v) 11
I ! i i
u_
1 c)
LI!
F
0
1.1
I-
- ' ----
i I
EXHIBIT SADDLE CREEK, PHASE 1 *CIVIL DEVELOPMENT,La* .==
r011,-,,,;II it,, 1 ,,7'.., 0
WATER SYSTEM SCHEMATIC 300 150 0 30
SCALL IN ILI F
Exhibit B
Water System Flow Test Report
Date: November 16, 2006
Water System Owner: Wellborn Special Utility District
Development Project: Saddle Creek Subdivision
Flow Test Location: Fire Hydrant @ 5401 Stousland
Nozzle size(in.): 2.5 Discharge Coef: (c): 0.9
Pitot Reading (psi): 60 Flowrate formula: Q=29.84cd2p1i2
c=discharge coef.
d=orifice size(in)
p=pitot pressure(psi)
Flowrate (gpm): 1300 computed
Pressure Guage Location: Hose Bib on House at 5401 Straub
Static (psi): 78
Residual (psi): 75
Report prepared by: td, ► i -
signature I
Kent Laza
printed name
Others present: Steven Cast
Exhibit C
Saddle Creek Subdivision
Water System Analysis
Static Flow Conditions
Label Elevation Demand Hydraulic
Pressure
Grade
(ft) (gpm) (ft) (psi)
SC1 FH1 284 3 466.00 78.74
SC1 FH2 276 0 465.99 82.20
SC1 FH3 273 6 465.99 83.50
SC1 FH4 273 0 465.99 83.50
SC1 FH5 282 0 465.99 79.60
SC101 286 0 466.00 77.88
SC102 275 7.5 465.99 82.63
SC103 274 9 465.92 83.04
SC104 273 4.5 465.99 83.50
SC105 275 4.5 465.99 82.63
Lowest Pressure in Ph 2&3= 77.88
Note: The lowest pressures shown above represent the most hydraulically remote
location in the Ph 1 system. The nearest fire hydrant is SC1 FH1. This is the
location where a 1000 gpm fire demand is placed for modeling purposes.
Exhibit D
Saddle Creek Subdivision
Water System Analysis - Junction Summary
Fire Flow Conditions
Hydraulic
Label Elevation Demand Grade Pressure
(ft) (gpm) (ft) (psi)
SC1 FH1 284 1,003.0 459.72 76.03
SC1 FH2 276 0.0 459.72 79.49
SC1 FH3 273 6.0 459.72 80.78
SC1 FH4 273 0.0 459.72 80.78
SC1 FH5 282 0.0 459.72 76.89
SC101 286 0.0 460.65 75.56
SC102 275 7.5 459.72 79.92
SC103 274 9.0 459.65 80.32
SC104 273 4.5 459.72 80.78
SC105 % 275 4.5 459.72 79.92
Lowest Pressure = 75.56
Exhibit E
Saddle Creek Subdivision
Water System Analysis - Pipe Summary
Fire Flow Conditions
Length Diameter ' Hazen- Discharge Velocity
Label Material
9 i
(ft) (in) Williams C (gpm) (ft/s)
P101 446 12 I PVC 150 I -1,034.50 2.93
P102 898 12 1 PVC 150 -31.50 0.09
P103 103 12 PVC 150 -31.50 0.09
P104 264 3 PVC 150 9.00 0.41
P105 610 12 PVC 150 15.00 0.04
P106 796 12 PVC 150 I -9.00 0.03
P107 23 j 8 PVC 150 0.00 I 0.00
P108 994 8 1 PVC 150 0.00 0.00
P109 634 12 I PVC 150 -4.50 0.01
Highest Velocity= 2.93