General Information
Location: Saddle Creek Subdivision, Phases 1-2 are located in southern Brazos County, near
the intersection of Wade Road and Stousland Road. Phase 1 was completed in the
Spring of 2007.
No. of Lots: Phase 1 - 35 lots
Phase 2 - 14 lots
Land Use: Single Family Residential—rural estate lots that are I acre or larger
WATER SYSTEM ANALYSIS
Design Criteria
Prirnaiy Water Supply: Existing 12"line along Stousland Road operated by Wellborn SUD.
Domestic Demand:
Avg. Pop Density: 2.67 people per lot
Average Flow: 100 gpd/cap or 267 gpd per lot=0.18 gpm per lot
Peaking Factor: 4
Peak Flow: 0.74 gpm per lot
Design Flow: 1.50 gpm per lot
Fire Demand:
Fire Flow: 1000 gpm at most hydraulically remote hydrant in Ph 2
Pipe: PVC DR-14 C909
Roughness Coeff. 150(Hazen Williams)
Hydraulic Software: Haestad Methods WaterCAD v.6.0
Existing System Pressure Tests
Flow Hydrant: Fire Hydrant on Stousland Road,south of Wade Road.
Flowrate: 1300 gpm
Guage Location: 5401 Stousland Road(hose bib on side of house)
Static Pressure: 78 psi (180 ft water)
Residual Pressure: 75 psi(173 ft water)
Applicable Exhibits: Exhibit B—Flow Test Report
Water System Analysis Summary
As
Criteria E Required DesignedLocation
Min. Pressure-fire(psi) 20 71.13 SC204 *
•
Max. Velocity(fps) 12 2.93 P201
Max. Length of 6"pipe(ft)
(connected to > 8"on both 1500 NA
ends) •
Max Length of 6"pipe(ft) 800 NA
(not connected on both ends)
•
Max. Length of 3"pipe(ft) 1 500 257
Note: The lowest water pressure occurred at SCIOI. The nearest fire hydrant to
that point is at SC2 FH1. That is the location where a 1000 gpm fire demand was
added for modeling purposes.
Applicable Exhibits: Exhibit A—Water System Schematic
Exhibit C—Water System Analysis—Junction Summary
Exhibit D—Water System Analysis—Pipe Summary
Conclusion
The proposed water system for Saddle Creek Subdivision, Phases 1 and 2 meets or
exceeds all of the design criteria for the City of College Station. It will provide
adequate water pressure and flow for both domestic and fire demands.
Exhibit B
Water System Flow Test Report
Date: November 16, 2006
Water System Owner: Wellborn Special Utility District
Development Project: Saddle Creek Subdivision
Flow Test Location: Fire Hydrant @ 5401 Stousland
Nozzle size (in.): 2.5 Discharge Coef: (c): 0.9
Pitot Reading (psi): 60 Flowrate formula: Q=29.84cd2p1/2
c=discharge coef.
d=orifice size(in)
p=pitot pressure(psi)
Flowrate (gpm): 1300 computed
Pressure Guage Location: Hose Bib on House at 5401 Straub
Static (psi): 78
Residual (psi): 75
Report prepared by:
signature .
Kent Laza r; 65623
printed name ',
Others present: Steven Cast
Exhibit C
Saddle Creek Subdivision, Phases 1-2
Water System Analysis - Junction Summary
Fire Flow Conditions
Label Elevation Demand Hydraulic Pressure
Grade
(ft) (gpm) (ft) (psi)
SC1 FH1 284 3.0 459.57 75.96
SC1 FH2 276 0.0 457.64 78.59
SC1 FH3 273 6.0 457.42 79.79
SC1 FH4 273 0.0 457.42 79.79
SC2 FH1 277 1,000.0 443.40 71.99 Phase 2
SC102 275 7.5 457.42 78.92
SC103 274 9.0 457.35 79.33
SC104 273 4.5 457.42 79.79
SC105 275 4.5 457.42 78.92
SC106 282 0.0 457.42 75.90
SC201 277 15.0 443.40 71.99
SC202 277 0.0 443.40 71.99 Phase 2
SC203 274 7.5 443.34 7327
SC204 279 0.0 443.40 7113
Lowest Pressure= 71.13 Phase 2
Exhibit D
Saddle Creek Subdivision, Phases 1-2
Water System Analysis - Pipe Summary
Fire Flow Conditions
Label Length Diameter Material Hazen- Discharge ] Velocity
(ft) (in) Williams C
(gpm) (ft/s)
(ft/s)
P101 446 12 PVC 150 -1,057.00 3.00
P102 898 12 PVC 150 -1,054.00 2.99
P103 103 12 PVC 150 -1,054.00 2.99
P104 264 3 PVC 150 9.00 0.41
P105 610 12 PVC 150 15.00 0.04
P106 796 12 PVC 150 -9.00 0.03
P107 23 8 PVC 150 0.00 0.00
P108 994 8 PVC 150 0.00 0.00
P109
634 12 PVC 150 -4.50 0.01
P201 960 8 PVC 150 -1,022.50 6.53
P202 22 8 PVC 150 -22.50 0.14
P203 81 8 PVC 150 -7.50 0.05 Phase 2
P204 292 3 PVC 150 7.50 0.34
P205 292 8 PVC 150 0.00 0.00
Highest Velocity= 6.53 Phase 2
f
/i
,/,/ ES E1 FH
i
/// '\p101
/ , S FH1
\
//
/ ,,` // P1-0-2--
Ca.N.J. C1 C1 4'7.
SC 13� \ --
P11 -. /, P103
--
SC102 UIII
- '105
.11
if SC FH3 P201
/7/
ill{
\ '10:. g a
P202
\SC11 ' --- - P205
&jai,
` 21 SC204
.77�' \ - ----- , i3P. 04 �. b02
P109 ---
___
SC105 ._._._ i�I ._ _. _._._ ._.__
l
it I P108
111
j1
Y C106
EXHIBIT SADDLE CREEK, PHASE 2 *CMDEVILLOPMEN,Lcc*
A 2990 eStatire neves 77845 SCALE: NOT TO SCALE
WATER SYSTEM SCHEMATIC uite K
College Station,Texas 77645