HomeMy WebLinkAboutStaff Comments 1 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM December 10, 2007 TO: Steve Duncan, via email to sduncan@jonescarter.com FROM: Matt Robinson and Crissy Hartl, Staff Planners SUBJECT: AGGIELAND DENTAL (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Seven (7) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (one set will be returned to you, please submit additional copies if you want more than one approved set) Two (2) revised site plans One (1) landscaping plan One (1) 11x17 grading and erosion control plan Temporary Blanket Easement Dedication Sheet and required documents. Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Spence Family Partnership, LTD, via fax#979.693.1693 Case file #07-00500278 STAFF REVIEW COMMENTS NO. 2 Project: AGGIELAND DENTAL (SP) - 07-00500278 PLANNING 1. Please include dimensions for storage building and add the square footage to the overall square footage of the Dental Office. 2. Please account for the added square footage from the storage building in the parking space requirements and add spaces as needed. 3. Please note that any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that the City has not been made aware of will constitute a completely new review. Reviewed by: Matt Robinson and Crissy Hartl Date: December 10, 2007 (*lir" 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 (.-H•1 010-ill 1 Y;)..'tiim ioN MEMORANDUM November 12, 2007 TO: Steve Duncan, via email to sduncan@jonescarter.com FROM: Matt Robinson and Crissy Hart!, Staff Planners SUBJECT: AGGIELAND DENTAL (SP)-Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised site and landscaping plan. Easement Dedication Sheet and required documents. Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments pc: Spence Family Partnerhsip, LTD, via fax#979.693.1693 Case file#07-00500278 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 1 of 3 STAFF REVIEW COMMENTS NO. 1 Project: AGGIELAND DENTAL (SP)—07-00500278 PLANNING 1. The rear lines that abut Graham Corner Plaza Block 1, Lot 6R and the greenway dedication will be the rear property lines for the purposes of setbacks. Please show the 15' rear setback lines along these property lines. 2. Edit the spelling of"acces easement" to"access easement." 3. Please submit an NRA Application with building elevations, color samples, and material samples according to the requirements of the application. 4. The driveway along the access easement is not easily distinguishable. Please make the lines darker so that features such are easier to see. 5. Is the bolded line 50' from the property line to measure streetscaping? If so, please label the line as such. 6. According to Section 7.9.B.5 Pedestrian/Bike Circulation & Facilities, a facility capable of storing a minimum of four bicycles is required for all non-residential buildings. Please provide a bicycle facility near the building. 7. The length of the parking space is determined by the length of the striping. The use of a 19' parking space is acceptable where the space abuts a landscape island with a minimum depth of 4', which is the case for the parking along the access easement. It is also acceptable where the spaces abut a minimum 6' sidewalk. The sidewalk along the building only measures 4'. Please lengthen the spaces to a full 20' or provide a 6' sidewalk along these spaces. 8. Please provide easy to read easements by using a darker print and labels. 9. Please add a note that states the following: "For the purposes of signage and NRA, this site is considered to be in the same building plot as Graham Corner Plaza." 10. Please specify the type of solid waste site screening that will be used. 11. Please note that any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that the City has not be made of aware of will constitute a completely new review. Reviewed by: Matt Robinson and Crissy Hartl Date: November 12, 2007 LANDSCAPING/STREETSCAPING/BUFFER 1. Please make existing landscaping details easier to read by using a darker font and remove point information in the legend for landscape not provided. 2. Staff has noted that several trees are being barricaded during construction. Before a development permit can be issued, staff must verify that the barricades are up. At that time, we will also perform an inspection to approve the health of the tree. )! Given the length of frontage along State Highway 6, 9 streetscape trees are required. Please revise the legend and landscape plan accordingly . Reviewed by: Matt Robinson and Crissy Hartl Date: November 12, 2007 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 2 of 3 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. ENGINEERING COMMENTS NO. 1 1. Please submit drainage report. 2. Please provide water and sewer demands on site plan. 3. Please provide existing sanitary manhole flow line and proposed service flow line. Reviewed by: Josh Norton Date: November 5, 2007 ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION 1. Developer provides tern porary blanket easement for construction purposes. 2. Developer provides easements for electric infrastructure as installed for electric lines 3. Transformer lead time is approximately 36 to 40 weeks. Electric load information is needed as soon as possible to avoid delays in construction. GENERAL ELECTRICAL COMMENTS 1. Developer installs conduit per City specs and design. 2. City will provide drawings for conduit installation. 3. Developer provides 30' of rigid or IMC conduit for riser poles. City installs riser. 4. Developer to intercept existing conduit at designated transformers and extend as required. 5. If conduit does not exist at designated transformer, developer to furnish and install conduit as shown on electrical layout. 6. Developer pours tran sformer pad(s) per City specs and design. 7. Developer installs pull boxes as per City specs and design (pull boxes provided by the City). 8. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan. Email to: sweido@cstx.gov. 9. Developer provides load data for project. See note 3 above. 10. To discuss any of the above electrical comments please contact Sam Weido at 979.764.6314. Reviewed by: Sam Weido Date: 11-7-07 FIRE 1. Remove Fire Lane marking from entrance to parking area. We can reach the building from the main drive. Reviewed by: Steve Smith Date: 11/07/07 SANITATION 1. Sanitation is ok with this project. Reviewed by: Wally Urrutia Date: November 9, 2007 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 3 CITY OF COLLEGE STATION Planning d Development Services 1101 Texas Avenue,P.O. Box 9960 College Station,Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM February 7, 2007 TO: Strong Surveying via fax 979.731.0096 FROM: Josh Norton, Project Engineer SUBJECT: Lot 3 of Graham Corner Plaza (DP) Development Permit Staff reviewed the above-mentioned development permit as requested. The following page is a list of staff review comments detailing items that need to be addressed. One (1) 24" x 36" copy of the Grading and Erosion Control Plan If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Dr. Kenneth R. Spence, via fax 979.693.1693 Case file#07-00500005 ENGINEERING COMMENTS NO. 1 1. Please provide a full size (24" x 36") grading and erosion control plan. The grading plan will need to illustrate the existing and proposed contours, the floodplain elevation, and the location of the floodway. 2. Please illustrate existing utility lines. 3. Once the grading and erosion control plan have been reviewed, we will need 3 sets of these documents for stamping and permitting. Reviewed by: Josh Norton Date: February 7, 2007