CITY OF COLLEGE STATION
MEMORANDUM
November 19, 2007
TO: Veronica Morgan, Mitchell & Morgan, LLP, via v(7a mitchellandmorgan.com
FROM: Jason Schubert, Staff Planner
SUBJECT: CSISD ATHLETIC FIELD RENOVATIONS (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
One (1) Development Permit application with associated construction and other
engineering documents;
One (1) revised site plan
If there are comments that you are not addressing with the revised site plan, please attach a
letter explaining the details. If you have any questions or need additional information, please call
me at 979.764.3570.
Attachments: Staff review comments
pc: Mike Ball, College Station ISD, via mballcsisd.orq
Steve Alloway, VLK Architects, via aloway(c�vlkarchitects.com
Case file #07-00500281
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 1 of 2
STAFF REVIEW COMMENTS NO. 1
Project: CSISD ATHLETIC FIELD RENOVATIONS (SP) — 07-00500281
PLANNING
1. Please clearly distinguish proposed, existing, and expanding areas of facilities.
2. It appears that a couple buildings are to be constructed or expanded over easements. The
Stadium Field House appears to be in an electrical only easement. In this instance, CSU is
allowing construction as the easement only serves that building. Please note that structures
will not be permitted within PUEs however.
Reviewed by: Jason Schubert Date: November 19, 2007
ENGINEERING COMMENTS NO. 1
1. The proposed building on southeast side of Christine Lane (formerly) is in a PUE. Please
relocate or submit PUE abandonment application.
2. Please dedicate PUE on existing 8" water line in Christine Lane (formerly).
3. My files show a 20' PUE (vol7051pg158) perpendicular to Christine Lane (formerly) along
the back property line of the proposed Ground Facility addition. Ensure that proposed
structure is not located in this PUE.
4. Show location of Base Flood Elevation (BFE) and floodway limits on the ground. Provide
Finished Floor Elevations if necessary. Be aware that some of the floodplain was revised by
LOMR 06-06-B753P in 2006.
5. Indicate whether water and sewer services are existing or proposed.
6. Submit Development Permit Application (fee is waived) with supporting Erosion Control Plan
and drainage documents.
7. Please modify Note 2 as it might lead to confusion. Public Works inspectors only inspect
public infrastructure.
8. Show existing easements on all plan sheets.
Reviewed by: Carol Cotter Date: November 6, 2007
GENERAL ELECTRICAL COMMENTS
1. No comments.
2. To discuss please contact Sam Weido at 979.764.6314.
Reviewed by: Sam Weido Date: November 7, 2007
FIRE
1. No comments at this time
Reviewed by: Eric Dotson Date: November 6, 2007
SANITATION
1. Sanitation is ok with this project.
Reviewed by: Wally Urrutia Date: November 9, 2007
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 2 of 2
MITCHELL
MM
MORGAN
Jason Shubert January 7, 2007
Development Services
1101 S. Texas Avenue
College Station, Texas 77840
RE: CSISD ATHLETIC FIELD RENOVATIONS (SP) - Site Plan Resubmittal
Dear Jason,
Attached please find the following for the above referenced project.
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
One (1) Development Permit application with 1 copy of the associated
construction documents;
One (1) revised site plan
Below are our responses to your comments.
Attachments:
pc: Jon Hall, College Station ISD
Steve Aloway, VLK Architects
ü4&
i1
511 UNIVERSITY DRIVE EAST,SUITE 204 TION,TX 77840• T 979.260.6963• F. 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
STAFF REVIEW COMMENTS NO. 1
Project: CSISD ATHLETIC FIELD RENOVATIONS (SP)— 07-00500281
PLANNING
1. Please clearly distinguish proposed, existing, and expanding areas of facilities.
RESPONSE: We have clarified on the plans which items are proposed, existing and
expanding.
2. It appears that a couple buildings are to be constructed or expanded over easements. The
Stadium Field House appears to be in an electrical only easement. In this instance, CSU is
allowing construction as the easement only serves that building. Please note that structures
will not be permitted within PUEs however.
RESPONSE: We do not believe that any of these structures are located within PUE's.
ENGINEERING COMMENTS NO. 1
1. The proposed building on southeast side of Christine Lane (formerly) is in a PUE. Please
relocate or submit PUE abandonment application.
RESPONSE: Attached is the warranty deed we found in vol. 7051 pg 158 which did not
appear to be a PUE. Can you help us locate the PUE documents so that we can see if
there is indeed a PUE at this location?
2. Please dedicate PUE on existing 8"water line in Christine Lane (formerly).
RESPONSE: It looks to us like this 8" waterline is currently within a PUE. Please call to
discuss.
3. My files show a 20' PUE (vo17051pg158) perpendicular to Christine Lane (formerly) along
the back property line of the proposed Ground Facility addition. Ensure that proposed
structure is not located in this PUE.
RESPONSE: Please see the response to comment number 1. We will be happy to work
with you on this. We just can't find the easement document.
4. Show location of Base Flood Elevation (BFE) and floodway limits on the ground. Provide
Finished Floor Elevations if necessary. Be aware that some of the floodplain was revised by
LOMR 06-06-B753P in 2006.
RESPONSE: We have indicated the floodplain on this project based upon LOMR 06-6-
B753P.
5. Indicate whether water and sewer services are existing or proposed.
RESPONSE: We have tried to clarify on the drawings what is existing vs. proposed.
6. Submit Development Permit Application (fee is waived) with supporting Erosion Control Plan
and drainage documents.
RESPONSE:A development permit application is attached.
7. Please modify Note 2 as it might lead to confusion. Public Works inspectors only inspect
public infrastructure.
RESPONSE: Note #2 has been modified as requested.
8. Show existing easements on all plan sheets.
RESPONSE: We have indicated existing easements as provided to us by the surveyor.
GENERAL ELECTRICAL COMMENTS
1. No comments.
2. To discuss please contact Sam Weido at 979.764.6314.
Page 2 of 3
FIRE
1. No comments at this time
SANITATION
1. Sanitation is ok with this project.
Please let us know if you have any questions or comments.
Si •erely,
I ' 1,
dI
N .,I
Veronica J.B More n, P.E., C.F.M
Managing Partner °✓
Page 3 of 3
11101 Texas Avenue, P.O. Box 9960
ff.„,„44-.44
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
CITY OF COLLEGE STATION
MEMORANDUM
January 14, 2008
TO: Veronica Morgan, Mitchell & Morgan, LLP, via v(a�mitchellandmorgan.com
FROM: Jason Schubert, Staff Planner
SUBJECT: CSISD ATHLETIC FIELD RENOVATIONS (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested and there are no additional
comments. Please submit the following information for further staff review and approval:
Seven (7) complete sets of construction documents for the proposed
development with the site plan attached (one set will be returned to you, please
submit additional copies if you want more than one approved set)
Two (2) site plans
One (1) 11x17 grading and erosion control plan
If you have any questions or need additional information, please call me at 764-3570.
cc: Mike Ball, College Station ISD, via mbalk csisd.orq
Jon Hall, College Station ISD, via jhall(a�csisd.orq
Steve Alloway, VLK Architects, via aloway(c�vlkarchitects.com
Case file #07-00500281